[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1035754":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},1035754,755,2,"多选题","A类电气装置保护接地的计箅用接地故障电流I应为（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","对有效接地系统和低电阻接地系统，采用系统最大运行方式下的接地短路电流或单 相接地故障电流；",false,{"key":16,"text":17,"correct":18},"B","B对有效接地系统和低电阻接地系统，采用在接地装置内、外短路时，经接地装置流 入地中最大短路电流对称分量的最大值；",true,{"key":20,"text":21,"correct":18},"C","对装有消弧线圏的发电厂、变电所电气装置的接地装置，等于接在其上的同一系统 各消弧线囷颏定电流总和的1. 25倍；",{"key":23,"text":24,"correct":18},"D","对不装消弧线圈的发电厂、变电所电气装置的接地装置，等于系统中断开最大一台 消弧线围或最长线路被切除时的最大可能残余电流值。","BCD","",{"id":6,"name":28,"category":29,"favorite":30},"电气工程师供配电专业","建筑工程",0]