[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1035701":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},1035701,755,2,"多选题","第一类防雷建筑物和具有爆炸危险环境的第二类防雷建筑物，应采取的防雷电感 应措施包括（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","建筑物内的设备、管道、构架、电缆金属外皮、钢屋架、钢窗等较长大金属物和突 出屋面的金属放散管、风管等均应就近连接到防雷电感应或共用接地装置上；",true,{"key":16,"text":17,"correct":18},"B","当管道、构架、电缆金属外皮等长金属物，其平行或交叉敷设的净距小于150mm时 应采用金属线跨接，跨接点的间距不应大于35m;",false,{"key":20,"text":21,"correct":18},"C","当长金属物的弯头、阀门、法兰盘等连接处的过渡电阻大于0.3n时，连接处应用 金属线跨接，但第二类防雷建筑物可不跨接；",{"key":23,"text":24,"correct":14},"D","防雷电感应的接地干线与接地装置的连接不应少于2处，第一类防雷建筑物防雷电 感应的接地装置与独立避雷针等接闪器的接地装置之间的间隔距离应符合相关要求。","AD","",{"id":6,"name":28,"category":29,"favorite":30},"电气工程师供配电专业","建筑工程",0]