[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1035679":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},1035679,755,2,"多选题","3~1OkV钢筋混凝土杆架空配电线路雷电过电压保护措施，下列正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","除少雷区外，宜采用铁横担，对供电可靠性要求高的线路宜采用高一级电压等级的 绝缘子。",false,{"key":16,"text":17,"correct":18},"B","除少雷区外，宜采用瓷或其他绝缘材料的横担；如用铁横担，对供电可靠性要求高 的线路宜采用高一级电压等级的绝缘子。",true,{"key":20,"text":21,"correct":18},"C","铁横担与绝缘子固定部分或瓷横担固定部分之间，宜有可靠的电气连接并与接地引 下线相连。",{"key":23,"text":24,"correct":14},"D","与架空线路相连接的长度不超过50m的电缆，应在其两端装设阀式避雷器或保护间隙。","BC","",{"id":6,"name":28,"category":29,"favorite":30},"电气工程师供配电专业","建筑工程",0]