[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1035577":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1035577,755,2,"多选题","已知某电厂1lOV直流系统蓄电池仅带控制负荷，经常电流为25 A，放电初期（0~ Imin)放电电流为93A, 1~30min放电电流为25A, 30~60min放电电流为25A,选用GF 型铅酸蓄电池，电池个数为53个，根据已知条件回答下列问题。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","事故放电末期，放电系数为（)。",false,{"key":16,"text":17,"correct":14},"B","0.1; B0. 12；",{"key":19,"text":20,"correct":21},"C","0.14;",true,{"key":23,"text":24,"correct":14},"D","0.16。","",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师供配电专业","建筑工程",0]