[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1035448":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},1035448,755,2,"多选题","继电保护、自动装置、控制、信号的二次回路线路电缆芯线截面的选择尚应符合 ( )要求。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","电流回路：应使电流互感器的工作准确等级，符合规范相应的规定。短路电流倍数 无可靠数据时，可按断路器的断流容量确定最大短路电流，电缆芯线截面不应小 于 2. 5mm2 ；",true,{"key":16,"text":17,"correct":14},"B","电压回路：当全部保护装置和安全自动装置动作时（考虑到发展，电压互感器的负 荷最大时），电压互感器至保护和自动装置屏的电缆压降不应超过额定电压的3%。。电缆芯 线截面不应小于1.5mm2;",{"key":19,"text":20,"correct":14},"C","操作回路：在最大负荷下，操作母线至设备的电压降，不应超过额定电压的10%；;",{"key":22,"text":23,"correct":24},"D","强电控制回路：不应小于2.5mm2。",false,"ABC","",{"id":6,"name":28,"category":29,"favorite":30},"电气工程师供配电专业","建筑工程",0]