[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1034558":3},{"question":4,"library":23},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":21,"analysis":22},1034558,755,2,"多选题","10kV及以下配电所进线开关选型的正确原则是（）。 A.非专用电源线（树干式，T接线）进线处应设带保护的断路器； B专用电源线进线处宜设断路器或带熔断器的负荷开关，当无继电保护和自动装置 (如备用自投），且出线回路少又无需带负荷操作时，可采用隔离开关或隔离触头； C.当总配电所与分配电所由同一单位管理、维护，总配电所又以放射式专线对分配电 所供电，该分配电所电源进线处宜采用隔离开关或隔离触头，但如果分配电所需要带负荷操 作或继电保护、自动装置有要求时，应采用断路器； D.不分情况，一律采用隔离开关。",[11,14,16,18],{"key":12,"text":12,"correct":13},"A",true,{"key":15,"text":15,"correct":13},"B",{"key":17,"text":17,"correct":13},"C",{"key":19,"text":19,"correct":20},"D",false,"ABC","",{"id":6,"name":24,"category":25,"favorite":26},"电气工程师供配电专业","建筑工程",0]