[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1034324":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},1034324,755,2,"多选题","采用需要系数法求某车间的计箅负荷。已知数据见表3-1。 本案例的单相负荷属于（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","既有线间负荷又有相负荷，应按精确法换算；",false,{"key":16,"text":17,"correct":14},"B","只有相负荷，应按简化法换算；",{"key":19,"text":20,"correct":14},"C","只有线间负荷，应按简化法换算；",{"key":22,"text":23,"correct":24},"D","设备功率不超过三相负荷设备功率之和的15%，不必换算。",true,"依据同上，第13页之（3)款。本案单相负荷只有点焊机，其设备功率20kW为三相负 荷设备功率之和195kW的10. 3%,不必换箅。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师供配电专业","建筑工程",0]