[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1033984":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1033984,755,1,"单选题","某工厂有一台同步电动机，电气参数为：额定功率1250kW,额定电压交流三相 6kV,额定电流0.144kA,额定启动电流倍数6倍，电动机启动转矩与额定转矩之比为 1.1, 6kV母线短路容量为40MVA,母线上预接负荷的无功功率为1Mvar,要求启动时母 线电压不低于额定电压的85%。选择启动方式和计算启动的有关参数。 为了保证启动时母线电压不低于额定电压的85%，启动回路输人的启动容量最小 应为（ ）（选最接近的一个数据）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","6. 15MVA,",false,{"key":16,"text":17,"correct":18},"B","7.24MVA；",true,{"key":20,"text":21,"correct":14},"C","8.36MVA,",{"key":23,"text":24,"correct":14},"D","9. 15MV","",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师供配电专业","建筑工程",0]