[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1033981":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},1033981,755,1,"单选题","某工厂有一台同步电动机，电气参数为：额定功率1250kW，额定电压交流三相 6kV,额定启动容量为9MV A，电动机启动转矩与额定转矩之比为1.1，生产机械的静阻转 矩为0.3，采用电抗器降压启动，启动电抗器每相额定电抗值为1.05Ω。6kV母线短路容量 为40MV A，母线上预接负荷的无功功率为lMvar，要求启动时母线电压不低于额定电压的 85％。电缆或导线的线路电抗忽略不计。请选择启动电抗器参数。 采用电抗器降压启动后，启动回路输入的启动容量为（ ）（选最接近的一个数据）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","7.13MVA；",true,{"key":16,"text":17,"correct":18},"B","6. 51MVA；",false,{"key":20,"text":21,"correct":18},"C","5. 36MVA；",{"key":23,"text":24,"correct":18},"D","2. 35MV","",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师供配电专业","建筑工程",0]