[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1033901":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1033901,755,1,"单选题","某生产车间有一台抽风机，生产要求能自启动，抽风机配套的交流异步电动机参数 为：额定电压6000V,额定功率850kW,额定电流97A,启动电流为额定电流的5. 8倍， 电动机最大转矩为额定转矩的2. 2倍。电网参数：电网电压6000V,在电网最小运行方式下 电动机端子三相短路时，流过保护的最小三相短路电流为9000A。电动机主回路电流互感器 变比为150\u002F5。电动机电源母线电压互感器变比为6000\u002F100。 电动机实际启动时间为13s,下列最适合过负荷保护装置动作时限是（ )。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","10s；",false,{"key":16,"text":17,"correct":14},"B","14s；",{"key":19,"text":20,"correct":21},"C","18s；",true,{"key":23,"text":24,"correct":14},"D","26s。","",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师供配电专业","建筑工程",0]