[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1033822":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1033822,755,1,"单选题","某轧钢车间有一台额定功率l450kW，额定转速500r\u002Fmin的轧钢电动机，电动机的 额定电压为6kV,额定容量为1.9MVA,额定启动电流倍数为5. 9倍，额定电压下启动转 矩标幺值为1。变电所6kV、50Hz母线上的最小短路容量为46 MVA。启动前母线电压为 额定电压6kV，母线上的无功负载为2. 95Mvar,启动时母线允许电压标幺值为0. 85。机组 的静阻转矩标么值为0.16。试选择启动方式，计算有关参数。 按母线电压水平核算此电动机采用自耦变压器启动时，与母线允许电压标幺值有关 的计算系数δ为（）（选最接近的一个数据)。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","0.09;",false,{"key":16,"text":17,"correct":18},"B","0.128;",true,{"key":20,"text":21,"correct":14},"C","0.16;",{"key":23,"text":24,"correct":14},"D","0.85。","",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师供配电专业","建筑工程",0]