[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1033815":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1033815,755,1,"单选题","某轧钢车间有一台额定功率1450kW,额定转速500r\u002Fmin的轧钢同步电动机，电动 机的额定电压为6kV,额定容量为1.9MVA,额定启动电流倍数为5. 9倍，额定电压下启 动转矩标幺值为1。变电所6kV、50Hz母线上的最小短路容量为46MVA。启动前母线电压 为額定电压6kV，母线上的无功负载为2. 95Mvar。启动时母线允许电压标幺值为0.85。机 组的静阻转矩标幺值为0. 16。试判断电抗器降压启动方案的可行性及计算有关参数。 计算降压启动电抗器的电抗值时计算系数γ 为（ ）（选最接近的一个数据)。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","6.67;",false,{"key":16,"text":17,"correct":14},"B","4. 21",{"key":19,"text":20,"correct":21},"C","5.67;",true,{"key":23,"text":24,"correct":14},"D","0.85。","",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师供配电专业","建筑工程",0]