[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1033789":3},{"question":4,"library":25},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":24},1033789,755,1,"单选题","某工厂有一台同步电动机，电气参数为：额定功率1250kW，额定电压交流三相 6kV,额定启动容量为9MV A，电动机启动转矩与额定转矩之比为1.1，生产机械的静阻转 矩为0.3，采用电抗器降压启动，启动电抗器每相额定电抗值为1.05Ω。6kV母线短路容量 为40MV",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","母线上预接负荷的无功功率为lMvar，要求启动时母线电压不低于额定电压的 85％。电缆或导线的线路电抗忽略不计。请选择启动电抗器参数。",false,{"key":16,"text":17,"correct":14},"B","由设备手册上查得以下设备参数见表14-5,请选择最适合本题条件启动电流 ( )、电抗器每相额定电抗（ ）的启动电抗器。",{"key":19,"text":20,"correct":21},"C","",true,{"key":23,"text":20,"correct":14},"D","《工业与民用配电设计手册》（第三版）P269，《钢铁企业电力设计手册》（上〉P276",{"id":6,"name":26,"category":27,"favorite":28},"电气工程师供配电专业","建筑工程",0]