[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1033784":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1033784,755,1,"单选题","某工厂有一台同步电动机，电气参数为：额定功率1250kW，额定电压交流三相 6kV,额定启动容量为9MV A，电动机启动转矩与额定转矩之比为1.1，生产机械的静阻转 矩为0.3，采用电抗器降压启动，启动电抗器每相额定电抗值为1.05Ω。6kV母线短路容量 为40MV A，母线上预接负荷的无功功率为lMvar，要求启动时母线电压不低于额定电压的 85％。电缆或导线的线路电抗忽略不计。请选择启动电抗器参数。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","采用电抗器降压启动时，同步电动机端子电压相对值为（ ）。",false,{"key":16,"text":17,"correct":14},"B","0. 589；",{"key":19,"text":20,"correct":21},"C","0. 639, C 0.675;",true,{"key":23,"text":24,"correct":14},"D","0. 754.","",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师供配电专业","建筑工程",0]