[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1033780":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1033780,755,1,"单选题","某工厂有一台同步电动机，电气参数为：额定功率1250kW,额定电压交流三相 6kV,额定电流0.144kA,额定启动电流倍数6倍，电动机启动转矩与额定转矩之比为 1.1, 6kV母线短路容量为40MVA,母线上预接负荷的无功功率为1Mvar,要求启动时母 线电压不低于额定电压的85%。选择启动方式和计算启动的有关参数。 现有待选启动电抗器设备若干种，其每相额定电抗值的参数有10.7、5.7、3.3、 1.8、1.05、0.6、0.35Ω七种，最适合本题中要选的启动电抗器每相额定电抗值为（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","10. 7Ω;",false,{"key":16,"text":17,"correct":18},"B","1. 05Ω;",true,{"key":20,"text":21,"correct":14},"C","1. 8Ω；",{"key":23,"text":24,"correct":14},"D","0. 35Ω。","《工业与民用配电设计手册》（第三版）P269、274，《钢铁企业电力设计手册》（上) P276。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师供配电专业","建筑工程",0]