[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1033777":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},1033777,755,1,"单选题","某工厂有一台同步电动机，电气参数为：额定功率1250kW,额定电压交流三相 6kV,额定电流0.144kA,额定启动电流倍数6倍，电动机启动转矩与额定转矩之比为 1.1, 6kV母线短路容量为40MVA,母线上预接负荷的无功功率为1Mvar,要求启动时母 线电压不低于额定电压的85%。选择启动方式和计算启动的有关参数。 电缆或导线的线路电抗忽略不计，试计算采用启动电抗器并满足启动要求时每相电 抗器额定电抗值最小为（ ）（选最接近的一个数据)。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","1. 6Ω；",false,{"key":16,"text":17,"correct":14},"B","0.16Ω;",{"key":19,"text":20,"correct":14},"C","9. 7 Ω；",{"key":22,"text":23,"correct":24},"D","0. 97 Ω",true,"",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师供配电专业","建筑工程",0]