[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1033408":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1033408,755,1,"单选题","在设计和选择给晶闸管变流装置供电的整流变压器时，以下原则（）是错误的.",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","整流变压器短路机会较多，因此，变压器的绕组和结构应有较髙的机械强度，在同 等容量下，变流变压器的体积应比一般电力变压器大些；",false,{"key":16,"text":17,"correct":14},"B","变流变压器的漏抗可限制短路电流，改善电网侧的电流波形，因此，变压器的漏抗 可略大一些；",{"key":19,"text":20,"correct":21},"C","一般的阻抗电压考虑在2%~4%范围内；",true,{"key":23,"text":24,"correct":14},"D","由于晶闸管装置发生过电压的机会较多，因此，整流变压器应就有较高的絶缘强度","",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师供配电专业","建筑工程",0]