[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1032672":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1032672,755,1,"单选题","采用独立避雷针保护突出屋面的排放爆炸危险气体、蒸气或粉尘的放散管、呼吸 阀、排风管等时，对于有管帽的管口，当装置内的压力与周围空气压力的压力差不大于 25kPa,排放物的密度小于空气时，距管帽以上垂直高度（ ）及距管口处的水平距离 ( )的空间应处于接闪器的保护范围内。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","lm, 2m；",false,{"key":16,"text":17,"correct":14},"B","2m, 2.5m；",{"key":19,"text":20,"correct":21},"C","2. 5m, 5m；",true,{"key":23,"text":24,"correct":14},"D","5m, 5m?","",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师供配电专业","建筑工程",0]