[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1032634":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},1032634,755,1,"单选题","主控制室、配电装置室和35kV及以下变电所的屋顶上一般不装设直击雷保护装 I、 置；如需要装设，下列做法不正确的是（）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","若为金属屋顶或屋顶上有金属结构，则将金属部分接地；",false,{"key":16,"text":17,"correct":14},"B","B若屋顶为钢筋混凝土结构，则将其焊接成网接地；",{"key":19,"text":20,"correct":14},"C","若屋顶为非导电结构（如砖木结构）时，则采用在屋顶敷设避雷带保护，该避雷带 网格尺寸为8~1〗0m，每隔10~20m设引下线接地；",{"key":22,"text":23,"correct":24},"D","上述接地引下线处应单独设置接地装置，并与主接地网相距3m以上。",true,"",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师供配电专业","建筑工程",0]