[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1032630":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},1032630,755,1,"单选题","保护变电所屋外配电装置的独立避雷针（线〉的接地装置。当需要与屋外配电装置 的主接地网相连接时，从避雷针与主接地网的地下连接点至及以下设备与主接地网的 地下连接点之间，沿接地体的长度不得小于（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","3m；",false,{"key":16,"text":17,"correct":14},"B","5m；",{"key":19,"text":20,"correct":14},"C","10m；",{"key":22,"text":23,"correct":24},"D","15m。",true,"",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师供配电专业","建筑工程",0]