[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"lib-751-9":3},{"library":4,"page":9,"limit":10,"total":11,"questions":12,"related":590},{"id":5,"name":6,"category":7,"favorite":8},751,"电气工程师发输变电专业","建筑工程",0,9,50,2670,[13,34,46,58,70,81,93,103,113,125,137,149,161,173,181,193,205,216,228,240,252,262,270,282,294,305,317,329,341,353,365,377,387,398,410,422,434,446,458,469,481,493,505,517,529,537,548,560,567,579],{"id":14,"libraryId":5,"type":15,"typeLabel":16,"stem":17,"options":18,"answer":27,"analysis":33},1022150,1,"单选题","在进行绝缘配合时，220kV相间最大操作过电压宜为相对地操作过电压的（）倍。",[19,23,26,30],{"key":20,"text":21,"correct":22},"A","1.1~1.2;",false,{"key":24,"text":25,"correct":22},"B","1.2~1.3;",{"key":27,"text":28,"correct":29},"C","1.3~1.4;",true,{"key":31,"text":32,"correct":22},"D","1.4~1.5。","",{"id":35,"libraryId":5,"type":15,"typeLabel":16,"stem":36,"options":37,"answer":31,"analysis":33},1022151,"在进行变电所绝缘子串的绝缘配合时，其操作过电压配合系数取（）。",[38,40,42,44],{"key":20,"text":39,"correct":22},"1.15；",{"key":24,"text":41,"correct":22},"1.16;",{"key":27,"text":43,"correct":22},"1.17;",{"key":31,"text":45,"correct":29},"1.18。",{"id":47,"libraryId":5,"type":15,"typeLabel":16,"stem":48,"options":49,"answer":24,"analysis":33},1022152,"在进行变电所绝缘子串的绝缘配合时，其雷电过电压配合系数取（）。",[50,52,54,56],{"key":20,"text":51,"correct":22},"1.35；",{"key":24,"text":53,"correct":29},"1.45;",{"key":27,"text":55,"correct":22},"1.55,",{"key":31,"text":57,"correct":22},"1.65.",{"id":59,"libraryId":5,"type":15,"typeLabel":16,"stem":60,"options":61,"answer":27,"analysis":33},1022153,"在进行变电所相对地空气间隙绝缘配合时，其相对地空气间隙操作过电压配合系数有风时取（）。",[62,64,66,68],{"key":20,"text":63,"correct":22},"1.05；",{"key":24,"text":65,"correct":22},"1.08；",{"key":27,"text":67,"correct":29},"1.10；",{"key":31,"text":69,"correct":22},"1.12。",{"id":71,"libraryId":5,"type":15,"typeLabel":16,"stem":72,"options":73,"answer":24,"analysis":33},1022154,"在进行变电所相对地空气间隙绝缘配合时，其相对地空气间隙雷电过电压配合系数有风偏时取（）。",[74,76,78,79],{"key":20,"text":75,"correct":22},"1.35;",{"key":24,"text":77,"correct":29},"1.40；",{"key":27,"text":53,"correct":22},{"key":31,"text":80,"correct":22},"1.50。",{"id":82,"libraryId":5,"type":15,"typeLabel":16,"stem":83,"options":84,"answer":31,"analysis":33},1022155,"在进行变电所500kV相间空气间隙绝缘配合时，其相间空气间隙操作过电压配合系数取（）。",[85,87,89,91],{"key":20,"text":86,"correct":22},"1.6；",{"key":24,"text":88,"correct":22},"1.7；",{"key":27,"text":90,"correct":22},"1.8；",{"key":31,"text":92,"correct":29},"1.9。",{"id":94,"libraryId":5,"type":15,"typeLabel":16,"stem":95,"options":96,"answer":24,"analysis":33},1022156,"在进行变电所电气设备内绝缘配合时，其内绝缘相对地额定操作冲击耐压与避雷器操作过电压保护水平间的配合系数不应小于（）。",[97,98,99,101],{"key":20,"text":67,"correct":22},{"key":24,"text":39,"correct":29},{"key":27,"text":100,"correct":22},"1.20；",{"key":31,"text":102,"correct":22},"1.25。",{"id":104,"libraryId":5,"type":15,"typeLabel":16,"stem":105,"options":106,"answer":27,"analysis":33},1022157,"在进行变电所变压器内、外绝缘配合时，其内、外绝缘的全波额定雷电冲击耐压与变电所避雷器标称放电电流下的残压间的配合系数不应小于（）。",[107,109,110,111],{"key":20,"text":108,"correct":22},"1.3；",{"key":24,"text":75,"correct":22},{"key":27,"text":77,"correct":29},{"key":31,"text":112,"correct":22},"1.45。",{"id":114,"libraryId":5,"type":15,"typeLabel":16,"stem":115,"options":116,"answer":24,"analysis":33},1022158,"送电线路及变电所电瓷外绝缘的绝缘配合，不应考虑系统中出现的（）",[117,119,121,123],{"key":20,"text":118,"correct":22},"系统最高运行电压；",{"key":24,"text":120,"correct":29},"工頻过电压及谐振过电压；",{"key":27,"text":122,"correct":22},"操作过电压；",{"key":31,"text":124,"correct":22},"雷电过电压。",{"id":126,"libraryId":5,"type":15,"typeLabel":16,"stem":127,"options":128,"answer":27,"analysis":33},1022159,"输电线路如果受到雷击，架空线路导线产生的直击雷过电压可按有关公式进行计算。现假定雷电流幅值I=40kA的条件下，计算雷击点过电压最大值U0是（）。",[129,131,133,135],{"key":20,"text":130,"correct":22},"2800kV；",{"key":24,"text":132,"correct":22},"3600kV；",{"key":27,"text":134,"correct":29},"4000kV；",{"key":31,"text":136,"correct":22},"5200kV。",{"id":138,"libraryId":5,"type":15,"typeLabel":16,"stem":139,"options":140,"answer":27,"analysis":33},1022160,"当已知避雷针的高度A采用30时，按有关计算式计算出避雷针在地面上的保护半径r是（）。",[141,143,145,147],{"key":20,"text":142,"correct":22},"25m;",{"key":24,"text":144,"correct":22},"35m；",{"key":27,"text":146,"correct":29},"45m;",{"key":31,"text":148,"correct":22},"52m。",{"id":150,"libraryId":5,"type":15,"typeLabel":16,"stem":151,"options":152,"answer":24,"analysis":33},1022161,"已知某工程采用了一独立避雷针作为防雷保护，避雷针的高度A为85m，被保护物高度、为42m，按有关计算式计算出避雷针在被保护物髙度、上的保护半径rx是（）。",[153,155,157,159],{"key":20,"text":154,"correct":22},"23m；",{"key":24,"text":156,"correct":29},"26m;",{"key":27,"text":158,"correct":22},"28m;",{"key":31,"text":160,"correct":22},"31m。",{"id":162,"libraryId":5,"type":15,"typeLabel":16,"stem":163,"options":164,"answer":31,"analysis":33},1022162,"已知某工程采用高度为28m，线间距离为1Om的两根平行避雷线作为防雷保护，根据有关公式计算，两避雷线间保护范围上部边缘最低点的高度、是（）。",[165,167,169,171],{"key":20,"text":166,"correct":22},"15m；",{"key":24,"text":168,"correct":22},"19.8m；",{"key":27,"text":170,"correct":22},"23.6m；",{"key":31,"text":172,"correct":29},"25.5m。",{"id":174,"libraryId":5,"type":15,"typeLabel":16,"stem":175,"options":176,"answer":27,"analysis":33},1022163,"在变电所导线对构架的空气间隙的计算中，相对地空气间隙的正极性雷电冲击电压波50%放电电压沟.3的计算式为ul.s≥K7UR，请分析确定式中K7（变电所相对地空气间隙雷电过电压配合系数）有风偏和无风偏间暸一般取值应是（）。 A.1.1，1.15; B.1.25，1.5; C.1.4，1.45； D1.45，1.6。",[177,178,179,180],{"key":20,"text":20,"correct":22},{"key":24,"text":24,"correct":22},{"key":27,"text":27,"correct":29},{"key":31,"text":31,"correct":22},{"id":182,"libraryId":5,"type":15,"typeLabel":16,"stem":183,"options":184,"answer":20,"analysis":33},1022164,"某35kV电网，全部采用架空导线，采用消弧线圈进行补偿。若导线对地电容的不对称系数为1%，补偿电网的阻尼率为0.05。采用全补偿方式运行和过补偿方式（脱谐度取为0.06）时，中性点长期位移电压分别为额定相电压的（）。",[185,187,189,191],{"key":20,"text":186,"correct":29},"20%,12.8%;",{"key":24,"text":188,"correct":22},"25%,11.6%；",{"key":27,"text":190,"correct":22},"30%,13.5%；",{"key":31,"text":192,"correct":22},"35%,14.2%。",{"id":194,"libraryId":5,"type":15,"typeLabel":16,"stem":195,"options":196,"answer":24,"analysis":33},1022165,"某500kV变电所海拔2200m,多年平均大气压力为80. 1kPa,空气绝对湿度为4.966g\u002Fm3。 工频交流电压下空气湿度校正系数为（）.",[197,199,201,203],{"key":20,"text":198,"correct":22},"1.05;",{"key":24,"text":200,"correct":29},"1.08;",{"key":27,"text":202,"correct":22},"1.11;",{"key":31,"text":204,"correct":22},"1.13.",{"id":206,"libraryId":5,"type":15,"typeLabel":16,"stem":207,"options":208,"answer":27,"analysis":33},1022166,"某500kV变电所海拔2200m,多年平均大气压力为80. 1kPa,空气绝对湿度为4.966g\u002Fm3。 雷电及操作冲击电压下空气湿度校正系数为（）。",[209,211,213,214],{"key":20,"text":210,"correct":22},"1.01；",{"key":24,"text":212,"correct":22},"1.03;",{"key":27,"text":198,"correct":29},{"key":31,"text":215,"correct":22},"1.07。",{"id":217,"libraryId":5,"type":15,"typeLabel":16,"stem":218,"options":219,"answer":27,"analysis":33},1022168,"某500kV变电所，变压器侧避雷器的额定电压为420kV，20kA标称雷电流下的额定残压值为995kV;线路断路器侧避雷器的额定电压为444kV,20kA标称雷电流下的额定残压值为1050kV。",[220,222,224,226],{"key":20,"text":221,"correct":22},"其他电气设备内绝缘全波额定雷电冲击耐压最小值为（）。",{"key":24,"text":223,"correct":22},"1461kV；",{"key":27,"text":225,"correct":29},"1466kV；",{"key":31,"text":227,"correct":22},"1470kV； a1475kV。",{"id":229,"libraryId":5,"type":15,"typeLabel":16,"stem":230,"options":231,"answer":24,"analysis":33},1022169,"某500kV变电所，变压器侧避雷器的额定电压为420kV，20kA标称雷电流下的额定残压值为995kV;线路断路器侧避雷器的额定电压为444kV,20kA标称雷电流下的额定残压值为1050kV。 变压器截波雷电冲击耐压最小值为（）。",[232,234,236,238],{"key":20,"text":233,"correct":22},"1523kV；",{"key":24,"text":235,"correct":29},"1532kV；",{"key":27,"text":237,"correct":22},"1537kV；",{"key":31,"text":239,"correct":22},"1541kV。",{"id":241,"libraryId":5,"type":15,"typeLabel":16,"stem":242,"options":243,"answer":20,"analysis":33},1022170,"塔头绝缘配合时应考虑导线绝缘子串的风偏影响，确定各种电压下风偏的风速。 工频电压下风偏的风速为（ ）。",[244,246,248,250],{"key":20,"text":245,"correct":29},"最大设计风速;",{"key":24,"text":247,"correct":22},"最大设计风速的0.8倍；",{"key":27,"text":249,"correct":22},"最大设计风速的0.5倍；",{"key":31,"text":251,"correct":22},"10m\u002Fs或15m\u002Fs（最大设计风速≥35m\u002Fs时）。",{"id":253,"libraryId":5,"type":15,"typeLabel":16,"stem":254,"options":255,"answer":27,"analysis":33},1022171,"塔头绝缘配合时应考虑导线绝缘子串的风偏影响，确定各种电压下风偏的风速。 操作过电压下风偏的风速为（）。",[256,258,259,260],{"key":20,"text":257,"correct":22},"最大设计风速；",{"key":24,"text":247,"correct":22},{"key":27,"text":249,"correct":29},{"key":31,"text":261,"correct":22},"10m\u002Fs或15nVs（最大设计风速≥35m\u002Fs时）。",{"id":263,"libraryId":5,"type":15,"typeLabel":16,"stem":264,"options":265,"answer":31,"analysis":33},1022172,"塔头绝缘配合时应考虑导线绝缘子串的风偏影响，确定各种电压下风偏的风速。 雷电过电压下风偏的风速为（ ）。",[266,267,268,269],{"key":20,"text":257,"correct":22},{"key":24,"text":247,"correct":22},{"key":27,"text":249,"correct":22},{"key":31,"text":251,"correct":29},{"id":271,"libraryId":5,"type":15,"typeLabel":16,"stem":272,"options":273,"answer":27,"analysis":33},1022173,"一发电厂的220kV配电装置出线挂线髙度为15m,现拟在配电装置外侧四周装设h=35m的等髙避雷针作为防雷保护措施。现按有关公式计算出各避雷针外侧在被保护物髙度的保护半径和任何两支避雷针之间的最大距离。 避雷针外侧在被保护物高度的保护半径rx为（）。",[274,276,278,280],{"key":20,"text":275,"correct":22},"11.6m;",{"key":24,"text":277,"correct":22},"13.5m;",{"key":27,"text":279,"correct":29},"16.Om；",{"key":31,"text":281,"correct":22},"20.9m。",{"id":283,"libraryId":5,"type":15,"typeLabel":16,"stem":284,"options":285,"answer":27,"analysis":33},1022174,"一发电厂的220kV配电装置出线挂线髙度为15m,现拟在配电装置外侧四周装设h=35m的等髙避雷针作为防雷保护措施。现按有关公式计算出各避雷针外侧在被保护物髙度的保护半径和任何两支避雷针之间的最大距离。 设四支避雷针，整个配电装置即能得到保护。除按边界条件：一侧最小宽度bx≥0边界条件外，任何两支避雷针之间的距离宜小于（）。",[286,288,290,292],{"key":20,"text":287,"correct":22},"156m；",{"key":24,"text":289,"correct":22},"168m；",{"key":27,"text":291,"correct":29},"175m;",{"key":31,"text":293,"correct":22},"195m。",{"id":295,"libraryId":5,"type":15,"typeLabel":16,"stem":296,"options":297,"answer":27,"analysis":33},1022176,"某个500kV变电所的海拔高度为2000m,按标准规定，外绝缘放电电压应该根据不同海拔髙度的气象条件进行修校正。可根据标准査得海拔高度为2000m的空气绝对湿度h值。按此条件计算空气湿度校正系数H值。",[298,300,301,303],{"key":20,"text":299,"correct":22},"雷电及操作冲击波时的H正确值是（）.",{"key":24,"text":210,"correct":22},{"key":27,"text":302,"correct":29},"1.03； C1.05；",{"key":31,"text":304,"correct":22},"1.08。",{"id":306,"libraryId":5,"type":15,"typeLabel":16,"stem":307,"options":308,"answer":31,"analysis":33},1022177,"已知两支避雷针高度A分别为25m、45m,被保护物髙度为18m，请分别计算出在被保护物髙度、水平面的保护半径rx值。",[309,311,313,315],{"key":20,"text":310,"correct":22},"当避雷针髙度A为25m时，rx的计算结果是（）。",{"key":24,"text":312,"correct":22},"31.5m；",{"key":27,"text":314,"correct":22},"33.5m; C35.5m；",{"key":31,"text":316,"correct":29},"7m。",{"id":318,"libraryId":5,"type":15,"typeLabel":16,"stem":319,"options":320,"answer":20,"analysis":33},1022178,"已知两支避雷针高度A分别为25m、45m,被保护物髙度为18m，请分别计算出在被保护物髙度、水平面的保护半径rx值。 当避雷针髙度A为45m时，rx的计算结果是（ ）.",[321,323,325,327],{"key":20,"text":322,"correct":29},"25.8m;",{"key":24,"text":324,"correct":22},"58.5m;",{"key":27,"text":326,"correct":22},"61.8m；",{"key":31,"text":328,"correct":22},"62.3m。",{"id":330,"libraryId":5,"type":15,"typeLabel":16,"stem":331,"options":332,"answer":31,"analysis":33},1022179,"由于空载线路开断时，如断路器发生重击穿，将产生严重的操作过电压，对范围II的线路断路器的要求是在（）的条件下开断空载线路不发生重击穿。",[333,335,337,339],{"key":20,"text":334,"correct":22},"电源对地电压为1.lp.u.；",{"key":24,"text":336,"correct":22},"电源对地电压为1.15p.u.；",{"key":27,"text":338,"correct":22},"电源对地电压为1.2p.u.；",{"key":31,"text":340,"correct":29},"电源对地电压为1.3p.u.。",{"id":342,"libraryId":5,"type":15,"typeLabel":16,"stem":343,"options":344,"answer":31,"analysis":33},1022180,"对于66kV及以下系统，为防止空载线路开断时产生操作过电压，在选用操作断路器时应该使其开断空载线路过电压不超过（）。",[345,347,349,351],{"key":20,"text":346,"correct":22},"1.Op.u.；",{"key":24,"text":348,"correct":22},"1.3p.u.；",{"key":27,"text":350,"correct":22},"3.Op.u.；",{"key":31,"text":352,"correct":29},"4.Op.u.。",{"id":354,"libraryId":5,"type":15,"typeLabel":16,"stem":355,"options":356,"answer":24,"analysis":33},1022181,"对于开断具有冷轧硅钢片的变压器时产生的操作过电压，一般采取的对策是（）。",[357,359,361,363],{"key":20,"text":358,"correct":22},"在断路器的非电源侧装设阀式避雷器加以限制；",{"key":24,"text":360,"correct":29},"过电压一般不超过2.Op.u.,可不采取保护措施；",{"key":27,"text":362,"correct":22},"选用性能优良的断路器；",{"key":31,"text":364,"correct":22},"变压器中性点装设阀式避雷器限制。",{"id":366,"libraryId":5,"type":15,"typeLabel":16,"stem":367,"options":368,"answer":27,"analysis":33},1022182,"开断空载变压器由于断路器强制熄弧（截流）产生的过电压，与一些因素有关。在下面的说法中，不正确的是（）。",[369,371,373,375],{"key":20,"text":370,"correct":22},"与变压器铁芯材料和绕组型式有关；",{"key":24,"text":372,"correct":22},"与断路器型式有关；",{"key":27,"text":374,"correct":29},"与变压器中性点接地方式有关；",{"key":31,"text":376,"correct":22},"与回路元件参数有关。",{"id":378,"libraryId":5,"type":15,"typeLabel":16,"stem":379,"options":380,"answer":20,"analysis":33},1022183,"空载变压器和并联电抗补偿装置合闸产生的操作过电压一般不超过（）。",[381,383,385,386],{"key":20,"text":382,"correct":29},"2.Op.u.；",{"key":24,"text":384,"correct":22},"2.5p.u.；",{"key":27,"text":350,"correct":22},{"key":31,"text":352,"correct":22},{"id":388,"libraryId":5,"type":15,"typeLabel":16,"stem":389,"options":390,"answer":27,"analysis":33},1022184,"在66kV及以下的经消弧线圈接地的系统，发生单相间歇性电弧接地故障时产生的过电压，一般情况下最大过电压不超过（）。",[391,393,394,396],{"key":20,"text":392,"correct":22},"2.Op.u.;",{"key":24,"text":384,"correct":22},{"key":27,"text":395,"correct":29},"3.2p.u.；",{"key":31,"text":397,"correct":22},"3.5p.u.。",{"id":399,"libraryId":5,"type":15,"typeLabel":16,"stem":400,"options":401,"answer":27,"analysis":33},1022185,"雷电活动特殊强烈地区的主厂房，如装设直击雷保护装置（避雷针），应采取防止反击的措施，在下列捎施中不正确的是（）。",[402,404,406,408],{"key":20,"text":403,"correct":22},"装设集中接地装置；",{"key":24,"text":405,"correct":22},"加强避雷装置的分流；",{"key":27,"text":407,"correct":29},"设备的接地点尽量靠近避雷针接地引下线的入地点；",{"key":31,"text":409,"correct":22},"避雷针接地引下线尽量远离电气设备。",{"id":411,"libraryId":5,"type":15,"typeLabel":16,"stem":412,"options":413,"answer":24,"analysis":33},1022186,"主控制室、配电装置室和35kV及以下变电所的屋顶上如装设直击雷保护装置时，则应该根据具体情况进行处理，下面的处理措施不正确的是（）。",[414,416,418,420],{"key":20,"text":415,"correct":22},"若为金属屋顶或屋顶上有金属结构，则将金属部分接地；",{"key":24,"text":417,"correct":29},"若结构为非导电的屋顶时，则接地引下线无需与主接地网连接，但应加装集中接地装里；",{"key":27,"text":419,"correct":22},"若屋頂为钢筋混凝土结构，则将其焊接成网接地；",{"key":31,"text":421,"correct":22},"若屋顶上采用避雷带保护，该避雷带的网格为8~10m，每隔10~20m设引下线接地。",{"id":423,"libraryId":5,"type":15,"typeLabel":16,"stem":424,"options":425,"answer":27,"analysis":33},1022187,"在发电厂的露天贮罐（氢气、天然气和易燃油贮罐）是防雷保护的重点，应采用独立避雷针保护，并有一些特殊要求。下面的要求不正确的是（）。",[426,428,430,432],{"key":20,"text":427,"correct":22},"避雷针与呼吸阀的水平距离不应小于3m;",{"key":24,"text":429,"correct":22},"避雷针的保护范围边缘高出呼吸阀顶部不应小于2m;",{"key":27,"text":431,"correct":29},"天然气贮罐与热工测量装置不能重复接地；",{"key":31,"text":433,"correct":22},"贮罐周围应设闭合环形接地体，接地电阻不宜大于30Ω。",{"id":435,"libraryId":5,"type":15,"typeLabel":16,"stem":436,"options":437,"answer":20,"analysis":33},1022188,"髙压侧电压为35kV的变电所，在变压器门型架构上装设避雷针时，变电所接地电阻（不包括架构基础的接地电阻）不应超过（）。",[438,440,442,444],{"key":20,"text":439,"correct":29},"4Ω；",{"key":24,"text":441,"correct":22},"5Ω；",{"key":27,"text":443,"correct":22},"1OΩ；",{"key":31,"text":445,"correct":22},"15Ω。",{"id":447,"libraryId":5,"type":15,"typeLabel":16,"stem":448,"options":449,"answer":31,"analysis":33},1022189,"在35、66kV配电装置中，允许将线路的避雷线引接到出线门型架构上的正确条件是（）。",[450,452,454,456],{"key":20,"text":451,"correct":22},"土壤电阻率不大于1500Ωm的地区，可不装设集中接地装置；",{"key":24,"text":453,"correct":22},"土壤电阻率不大于1OOOΩm的地区，可不装设集中接地装里；",{"key":27,"text":455,"correct":22},"土壤电阻率不大于800Ωm的地区，应装设集中接地装置；",{"key":31,"text":457,"correct":29},"土壤电阻率不大于500Ωm的地区’应装设集中接地装置。",{"id":459,"libraryId":5,"type":15,"typeLabel":16,"stem":460,"options":461,"answer":31,"analysis":33},1022190,"独立避雷针的接地装置与发电厂、变电所接地网间的地中距离氐除应符合0.3Ri的要求外，还规定Se不宜小于（）。",[462,463,465,467],{"key":20,"text":166,"correct":22},{"key":24,"text":464,"correct":22},"10m；",{"key":27,"text":466,"correct":22},"5m；",{"key":31,"text":468,"correct":29},"3m。",{"id":470,"libraryId":5,"type":15,"typeLabel":16,"stem":471,"options":472,"answer":31,"analysis":33},1022191,"在一般情况下，以下的建筑物上可以装设避雷针的是（）。",[473,475,477,479],{"key":20,"text":474,"correct":22},"主厂房、主控制室和配电装置室；",{"key":24,"text":476,"correct":22},"变压器门型架构上，土壤电阻率大于350Ω?m时；",{"key":27,"text":478,"correct":22},"35kV及以下高压配电装置架构或房顶；",{"key":31,"text":480,"correct":29},"110kV及以上配电装里的架构或房顶（土壤电阻率小于1OOOΩ?m的地区）。",{"id":482,"libraryId":5,"type":15,"typeLabel":16,"stem":483,"options":484,"answer":20,"analysis":33},1022192,"变电所35~110kV的进线中未沿全线架设避雷线的线路，在雷季，如35~110kV进线的隔离开关或断路器可能经常断路运行，同时线路侧又带电，此时应该采取的措施是（）。",[485,487,489,491],{"key":20,"text":486,"correct":29},"在靠近隔离开关或断路器处装设一组排气式（阀式）避雷器；",{"key":24,"text":488,"correct":22},"进线的2km改为电缆进线段；",{"key":27,"text":490,"correct":22},"进线段1~2km上加装避雷线保护；",{"key":31,"text":492,"correct":22},"在靠近隔离开关或断路器处装设一组保护间隙。",{"id":494,"libraryId":5,"type":15,"typeLabel":16,"stem":495,"options":496,"answer":24,"analysis":33},1022193,"具有架空进线的35kV及以上的敞开式髙压配电装置中，如架空进线采用双回路杆塔，有同时遭到雷击的可能，确定阀式避雷器与变压器最大电气距离时，应按（）考虑。",[497,499,501,503],{"key":20,"text":498,"correct":22},"双回路运行；",{"key":24,"text":500,"correct":29},"单回路运行；",{"key":27,"text":502,"correct":22},"在单、双回路的距离中按补插法；",{"key":31,"text":504,"correct":22},"双回路均断开。",{"id":506,"libraryId":5,"type":15,"typeLabel":16,"stem":507,"options":508,"answer":31,"analysis":33},1022194,"在变电所的3~1OkV配电装置（包括电力变压器）中，装设阀式避雷器（包括电站和配电阀式避雷器）的正确选择是（）。",[509,511,513,515],{"key":20,"text":510,"correct":22},"在每组母线上装设；",{"key":24,"text":512,"correct":22},"在每条架空进线上装设；",{"key":27,"text":514,"correct":22},"在每组变压器上装设；",{"key":31,"text":516,"correct":29},"在每组母线和架空进线上均装设。",{"id":518,"libraryId":5,"type":15,"typeLabel":16,"stem":519,"options":520,"answer":27,"analysis":33},1022195,"220kV进线无电缆段的GIS变电所，在GIS管道与架空线路的连接处，已经装设金属氧化物避雷器，请问：变压器或GIS—次回路的任何电气部分至该避雷器间的最大电气距离不超过（），则无需另加避雷器即可满足保护要求。",[521,523,525,527],{"key":20,"text":522,"correct":22},"50m;",{"key":24,"text":524,"correct":22},"95m;",{"key":27,"text":526,"correct":29},"130m;",{"key":31,"text":528,"correct":22},"160m。",{"id":530,"libraryId":5,"type":15,"typeLabel":16,"stem":531,"options":532,"answer":27,"analysis":33},1022196,"对于3150~5000kVA的变电所35kV侧，可根据负荷的重要性及雷电活动的强弱等条件，适当简化保护接线，变电所进线段的避雷线长度可减少到（）。 A.1000m； B.600~800m; C500~600m；D.300~500m。",[533,534,535,536],{"key":20,"text":20,"correct":22},{"key":24,"text":24,"correct":22},{"key":27,"text":27,"correct":29},{"key":31,"text":31,"correct":22},{"id":538,"libraryId":5,"type":15,"typeLabel":16,"stem":539,"options":540,"answer":24,"analysis":33},1022197,"简易保护接线的变电所35kV侧，阀式避雷器与主变压器或电压互感器间的最大电气距离-般不宜超过（）。",[541,542,544,546],{"key":20,"text":466,"correct":22},{"key":24,"text":543,"correct":29},"1Om；",{"key":27,"text":545,"correct":22},"15m;",{"key":31,"text":547,"correct":22},"20m。",{"id":549,"libraryId":5,"type":15,"typeLabel":16,"stem":550,"options":551,"answer":24,"analysis":33},1022198,"在3~IOkV配电系统中，可不装设阀式避雷器而采用击穿熔断器保护措施的是（）。",[552,554,556,558],{"key":20,"text":553,"correct":22},"配电系统中的配电变压器；",{"key":24,"text":555,"correct":29},"低压侧中性点不接地的配电变压器的中性点；",{"key":27,"text":557,"correct":22},"柱上断路器和负荷开关；",{"key":31,"text":559,"correct":22},"装设在架空线路上的电容器。",{"id":561,"libraryId":5,"type":15,"typeLabel":16,"stem":33,"options":562,"answer":27,"analysis":33},1022199,[563,564,565,566],{"key":20,"text":20,"correct":22},{"key":24,"text":24,"correct":22},{"key":27,"text":27,"correct":29},{"key":31,"text":31,"correct":22},{"id":568,"libraryId":5,"type":15,"typeLabel":16,"stem":569,"options":570,"answer":31,"analysis":33},1022200,"保护直配电机用的避雷线，对边导线的保护角的要求是（）。",[571,573,575,577],{"key":20,"text":572,"correct":22},"不应大于10°;",{"key":24,"text":574,"correct":22},"不应大于15°；",{"key":27,"text":576,"correct":22},"不应大于20°;",{"key":31,"text":578,"correct":29},"不应大于30°。",{"id":580,"libraryId":5,"type":15,"typeLabel":16,"stem":581,"options":582,"answer":24,"analysis":33},1022201,"无架空直配线的发电机，当发电机与升压变压器（该变压器低压绕组未装设避雷器）之间的母线桥或组合导线无金属屏蔽部分的长度大于（），才应采取防止感应过电压的措施。",[583,585,586,588],{"key":20,"text":584,"correct":22},"25m；",{"key":24,"text":522,"correct":29},{"key":27,"text":587,"correct":22},"85m;",{"key":31,"text":589,"correct":22},"100m。",[591,594,597,600,603,606],{"id":15,"name":592,"category":7,"favorite":593},"领导干部任职前廉政法规知识测试题",92,{"id":595,"name":596,"category":7,"favorite":15},595,"建筑结构与设备",{"id":598,"name":599,"category":7,"favorite":15},715,"招标采购专业知识与法律法规",{"id":601,"name":602,"category":7,"favorite":15},848,"市政方向-通用基础",{"id":604,"name":605,"category":7,"favorite":8},534,"BIM工程师",{"id":607,"name":605,"category":7,"favorite":8},535]