[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"lib-751-39":3},{"library":4,"page":9,"limit":10,"total":11,"questions":12,"related":614},{"id":5,"name":6,"category":7,"favorite":8},751,"电气工程师发输变电专业","建筑工程",0,39,50,2670,[13,34,46,58,70,82,94,106,118,130,142,153,165,177,189,201,212,224,235,247,259,271,283,295,307,319,330,342,354,366,378,390,402,414,424,434,446,458,470,482,494,506,518,530,542,554,566,578,590,602],{"id":14,"libraryId":5,"type":15,"typeLabel":16,"stem":17,"options":18,"answer":30,"analysis":33},1023663,1,"单选题","某2X300MW火力发电厂厂用电系统采用6kV和380V两级电压，其中每台机组设 A、B两段6kV工作段，全厂设01 A、OlB两段6kV公用段，考虑公用段工作电源取自1、2号机组6kV工作段，备用电源取自启动\u002F备用变压器。见示意图9。每台机组设一台电动给水泵，都接于机组6kV工作A段，髙压厂用分裂变压器容量为：40\u002F25—25MVA（无载调压）。 条件同（1）题，且1号机6kVA段计算负荷：19520kVA （2号机相同）电动给水泵额定容量为5000kW；B段计算负荷：20360kV6A（2号机为20450kV A）；试确定髙压厂用变压器的阻抗电压（％）范围（启动电压计算只考虑正常最大一台电动机启动，最大电动机ηdcosφd=0.8）为（）。",[19,23,26,29],{"key":20,"text":21,"correct":22},"A","13%~17%；",false,{"key":24,"text":25,"correct":22},"B","14%~18%；",{"key":27,"text":28,"correct":22},"C","15%~19%；",{"key":30,"text":31,"correct":32},"D","16%~20%。",true,"",{"id":35,"libraryId":5,"type":15,"typeLabel":16,"stem":36,"options":37,"answer":20,"analysis":33},1023664,"某2X300MW火力发电厂厂用电系统采用6kV和380V两级电压，其中每台机组设 A、B两段6kV工作段，全厂设01 A、OlB两段6kV公用段，考虑公用段工作电源取自1、2号机组6kV工作段，备用电源取自启动\u002F备用变压器。见示意图9。每台机组设一台电动给水泵，都接于机组6kV工作A段，髙压厂用分裂变压器容量为：40\u002F25—25MVA（无载调压）。 若两台机组每段6kV工作段所连系统（包括髙压厂用变压器、封闭母线和电缆）对地电容基本相同，约为1.75μF,每段公用段所连系统对地电容基本相同，约为0.81μ F，试确定本工程6kV厂用电中心点的接地方式为（）。",[38,40,42,44],{"key":20,"text":39,"correct":32},"不接地；",{"key":24,"text":41,"correct":22},"高电阻接地；",{"key":27,"text":43,"correct":22},"消弧线圈接地；",{"key":30,"text":45,"correct":22},"直接接地。",{"id":47,"libraryId":5,"type":15,"typeLabel":16,"stem":48,"options":49,"answer":24,"analysis":33},1023665,"某2X300MW火力发电厂厂用电系统采用6kV和380V两级电压，其中每台机组设 A、B两段6kV工作段，全厂设01 A、OlB两段6kV公用段，考虑公用段工作电源取自1、2号机组6kV工作段，备用电源取自启动\u002F备用变压器。见示意图9。每台机组设一台电动给水泵，都接于机组6kV工作A段，髙压厂用分裂变压器容量为：40\u002F25—25MVA（无载调压）。 若接地电咀接于高压厂用变压器中心点的接地变压器的二次侧，二次侧电压取220V，电阻值按单相接地电容8.35A选取，接地电阻的电阻值为（）。",[50,52,54,56],{"key":20,"text":51,"correct":22},"1.55Ω；",{"key":24,"text":53,"correct":32},"1.67Ω；",{"key":27,"text":55,"correct":22},"2.15Ω；",{"key":30,"text":57,"correct":22},"2.71Ω。",{"id":59,"libraryId":5,"type":15,"typeLabel":16,"stem":60,"options":61,"answer":30,"analysis":33},1023666,"某交流500kV线路，海拔小于1000m，4XLGJ—400\u002F50导线，I级污区，采用标准型绝缘子XP—160，L=360mm,h=155mm,ke=1.0。 本工程基本悬垂串的绝缘子片数为（）。",[62,64,66,68],{"key":20,"text":63,"correct":22},"32；",{"key":24,"text":65,"correct":22},"25；",{"key":27,"text":67,"correct":22},"35；",{"key":30,"text":69,"correct":32},"28。",{"id":71,"libraryId":5,"type":15,"typeLabel":16,"stem":72,"options":73,"answer":27,"analysis":33},1023667,"某交流500kV线路，海拔小于1000m，4XLGJ—400\u002F50导线，I级污区，采用标准型绝缘子XP—160，L=360mm,h=155mm,ke=1.0。 正常情况下适用的耐张串绝缘子强度为（）。",[74,76,78,80],{"key":20,"text":75,"correct":22},"双联160kN；",{"key":24,"text":77,"correct":22},"双联210kN；",{"key":27,"text":79,"correct":32},"双联300kN；",{"key":30,"text":81,"correct":22},"双联400kN。",{"id":83,"libraryId":5,"type":15,"typeLabel":16,"stem":84,"options":85,"answer":20,"analysis":33},1023668,"某交流500kV线路，海拔小于1000m，4XLGJ—400\u002F50导线，I级污区，采用标准型绝缘子XP—160，L=360mm,h=155mm,ke=1.0。 列出该线路各工况（工频、操作、带电检修）下的空气间隙分别为（）。",[86,88,90,92],{"key":20,"text":87,"correct":32},"1.3、2.7、3.2+0.5；",{"key":24,"text":89,"correct":22},"1.5、2.0、3.2+0.5；",{"key":27,"text":91,"correct":22},"1.4、2.7、3.2；",{"key":30,"text":93,"correct":22},"1.3、2.5、3.2+0.5。",{"id":95,"libraryId":5,"type":15,"typeLabel":16,"stem":96,"options":97,"answer":27,"analysis":33},1023669,"某交流500kV线路，海拔小于1000m，4XLGJ—400\u002F50导线，I级污区，采用标准型绝缘子XP—160，L=360mm,h=155mm,ke=1.0。",[98,100,102,104],{"key":20,"text":99,"correct":22},"当采用V型串，其工频电压下的空气间隙（1000m以下）为（ ）。",{"key":24,"text":101,"correct":22},"1.25；",{"key":27,"text":103,"correct":32},"1.3；C1.34；",{"key":30,"text":105,"correct":22},"1.5。",{"id":107,"libraryId":5,"type":15,"typeLabel":16,"stem":108,"options":109,"answer":24,"analysis":33},1023670,"某交流500kV线路，海拔小于1000m，4XLGJ—400\u002F50导线，I级污区，采用标准型绝缘子XP—160，L=360mm,h=155mm,ke=1.0。 设5OOkV线路导线对地高20m，测量仪高2. 5，在边导线外25m处进行测量，要使500kV线路0.5MHz时的无线电干扰满足规程规定，求在25m时测得的值应不大于（）dB。",[110,112,114,116],{"key":20,"text":111,"correct":22},"52；",{"key":24,"text":113,"correct":32},"53；",{"key":27,"text":115,"correct":22},"50；",{"key":30,"text":117,"correct":22},"54。",{"id":119,"libraryId":5,"type":15,"typeLabel":16,"stem":120,"options":121,"answer":24,"analysis":33},1023671,"某220kV线路，双分裂LGJ—300\u002F40导线，悬垂绝缘子串长为3.Om,计算弧垂用，k值取7.75X10-5l\u002Fm，使用的铁塔如图10所示。 该塔型的等效水平线间距离为（）m。",[122,124,126,128],{"key":20,"text":123,"correct":22},"8.25；",{"key":24,"text":125,"correct":32},"8.85；",{"key":27,"text":127,"correct":22},"9.85；",{"key":30,"text":129,"correct":22},"7.55。",{"id":131,"libraryId":5,"type":15,"typeLabel":16,"stem":132,"options":133,"answer":30,"analysis":33},1023672,"某220kV线路，双分裂LGJ—300\u002F40导线，悬垂绝缘子串长为3.Om,计算弧垂用，k值取7.75X10-5l\u002Fm，使用的铁塔如图10所示。 若（1）题中该塔型两两相配，其最大使用档距为（）m。",[134,136,138,140],{"key":20,"text":135,"correct":22},"925；",{"key":24,"text":137,"correct":22},"1055；",{"key":27,"text":139,"correct":22},"856；",{"key":30,"text":141,"correct":32},"987。",{"id":143,"libraryId":5,"type":15,"typeLabel":16,"stem":144,"options":145,"answer":27,"analysis":33},1023673,"某220kV线路，双分裂LGJ—300\u002F40导线，悬垂绝缘子串长为3.Om,计算弧垂用，k值取7.75X10-5l\u002Fm，使用的铁塔如图10所示。 该线路气象台（站）记录的风速换算为线路设计重现风速为23m\u002Fs,按标准风压换算为22.5m,设计人员现场调查风速约24.5m\u002Fs,该线路设计最大风速应取（）m\u002Fs。",[146,148,150,151],{"key":20,"text":147,"correct":22},"23；",{"key":24,"text":149,"correct":22},"22.5；",{"key":27,"text":65,"correct":32},{"key":30,"text":152,"correct":22},"24.5。",{"id":154,"libraryId":5,"type":15,"typeLabel":16,"stem":155,"options":156,"answer":24,"analysis":33},1023674,"某220kV线路，双分裂LGJ—300\u002F40导线，悬垂绝缘子串长为3.Om,计算弧垂用，k值取7.75X10-5l\u002Fm，使用的铁塔如图10所示。 假设风速V=25m\u002Fs，覆冰b= 10mm，采用双分裂LGJ—300\u002F40导线，2号塔与相邻塔的关系如图11所示。 L1=350m,△h1=70m L2=400m,△h2=-60m 导线无冰无风时的应力σ=58.8N\u002Fmm2,导线单重：ω1=1.133kg\u002Fm,截面：S=338.99mm2。 则2号塔导线的垂直档距为（）m。",[157,159,161,163],{"key":20,"text":158,"correct":22},"450；",{"key":24,"text":160,"correct":32},"463；",{"key":27,"text":162,"correct":22},"485；",{"key":30,"text":164,"correct":22},"520。",{"id":166,"libraryId":5,"type":15,"typeLabel":16,"stem":167,"options":168,"answer":30,"analysis":33},1023675,"某220kV线路，双分裂LGJ—300\u002F40导线，悬垂绝缘子串长为3.Om,计算弧垂用，k值取7.75X10-5l\u002Fm，使用的铁塔如图10所示。 设导线悬垂串质量为100kg，上题（4）中2号塔导线的垂直荷载为（）kg。",[169,171,173,175],{"key":20,"text":170,"correct":22},"1049.2；",{"key":24,"text":172,"correct":22},"1249.2；",{"key":27,"text":174,"correct":22},"1349.2；",{"key":30,"text":176,"correct":32},"1149.2。",{"id":178,"libraryId":5,"type":15,"typeLabel":16,"stem":179,"options":180,"answer":27,"analysis":33},1023676,"某220kV线路，双分裂LGJ—300\u002F40导线，悬垂绝缘子串长为3.Om,计算弧垂用，k值取7.75X10-5l\u002Fm，使用的铁塔如图10所示。 该线路交叉跨越某11OkV线路，无冰无风时导线应力σ=5.6kg\u002Fmm2，其余参数如图12。 A、B分别为220kV线两塔的标髙（A=860m，B=820m）,C为跨越处110kV线的标髙（815m）,L1=200m,L2=350m，不考虑裕度，交叉点两线路间的净空距离为（）m。",[181,183,185,187],{"key":20,"text":182,"correct":22},"1.5；",{"key":24,"text":184,"correct":22},"3.5；",{"key":27,"text":186,"correct":32},"2.3；",{"key":30,"text":188,"correct":22},"4.0。",{"id":190,"libraryId":5,"type":15,"typeLabel":16,"stem":191,"options":192,"answer":27,"analysis":33},1023677,"某±500kV直流线路，试根据规程规定回答下列问题。 在最大弧垂前提下，导线与地表的最小距离，目前是按允许地面合成电场强度值（）来决定的。",[193,195,197,199],{"key":20,"text":194,"correct":22},"25kV\u002Fm；",{"key":24,"text":196,"correct":22},"20kV\u002Fm；",{"key":27,"text":198,"correct":32},"30kV\u002Fm；",{"key":30,"text":200,"correct":22},"35kV\u002Fm。",{"id":202,"libraryId":5,"type":15,"typeLabel":16,"stem":203,"options":204,"answer":24,"analysis":33},1023678,"某±500kV直流线路，试根据规程规定回答下列问题。 同型号绝缘子，在相同污秽条件下，直流的污闪电压17,和交流的污闪电压Uc不同，请判断两者关系为（）。",[205,207,208,210],{"key":20,"text":206,"correct":22},"Ua Uc；",{"key":24,"text":206,"correct":32},{"key":27,"text":209,"correct":22},"Ua=Uc；",{"key":30,"text":211,"correct":22},"Ua≠Uc。",{"id":213,"libraryId":5,"type":15,"typeLabel":16,"stem":214,"options":215,"answer":24,"analysis":33},1023679,"某±500kV直流线路，试根据规程规定回答下列问题。 高压直流线路的对地距离是由走廊内允许的地表电场强度决定的。交流线下只考虑静电场，直流线下还存在空间电荷电场，后者的影响是（）。",[216,218,220,222],{"key":20,"text":217,"correct":22},"使对地距离减小；",{"key":24,"text":219,"correct":32},"使对地距离增加；",{"key":27,"text":221,"correct":22},"不影响对地距离；",{"key":30,"text":223,"correct":22},"视具体情况可増可减。",{"id":225,"libraryId":5,"type":15,"typeLabel":16,"stem":226,"options":227,"answer":27,"analysis":33},1023680,"电压等级为（）及以上屋外配电装置的构架荷载条件及安全距离，有条件时宜考虑带电检修的要求。",[228,230,232,233],{"key":20,"text":229,"correct":22},"1OkV;",{"key":24,"text":231,"correct":22},"35kV；",{"key":27,"text":229,"correct":32},{"key":30,"text":234,"correct":22},"220kV。",{"id":236,"libraryId":5,"type":15,"typeLabel":16,"stem":237,"options":238,"answer":27,"analysis":33},1023681,"选择屋外高压电器及导体的气候环境参数，应取在短时间内出现的温度和湿度的()。",[239,241,243,245],{"key":20,"text":240,"correct":22},"极端最高值；",{"key":24,"text":242,"correct":22},"多年最高值;",{"key":27,"text":244,"correct":32},"年最高值的多年平均值;",{"key":30,"text":246,"correct":22},"多年平均值。",{"id":248,"libraryId":5,"type":15,"typeLabel":16,"stem":249,"options":250,"answer":27,"analysis":33},1023682,"500kV配电装置设计及选择导体和电器时的最大风速，宜采用离地（）高，()一遇1Omin平均最大风速。",[251,253,255,257],{"key":20,"text":252,"correct":22},"1Om，30年；",{"key":24,"text":254,"correct":22},"15m，30年；",{"key":27,"text":256,"correct":32},"1Om，50年;",{"key":30,"text":258,"correct":22},"15m，50年。",{"id":260,"libraryId":5,"type":15,"typeLabel":16,"stem":261,"options":262,"answer":27,"analysis":33},1023683,"配电装置紧邻居民区时，其围墙外侧的连续噪声级白天不应超过( )、夜间不应超过55dB。",[263,265,267,269],{"key":20,"text":264,"correct":22},"55dB；",{"key":24,"text":266,"correct":22},"60dB；",{"key":27,"text":268,"correct":32},"65dB;",{"key":30,"text":270,"correct":22},"70dB。",{"id":272,"libraryId":5,"type":15,"typeLabel":16,"stem":273,"options":274,"answer":24,"analysis":33},1023684,"地震动峰加速度超过( )的地区，配电装置设计应按有关的抗震规定采取抗震措施。",[275,277,279,281],{"key":20,"text":276,"correct":22},"0.15g；",{"key":24,"text":278,"correct":32},"0.2g；",{"key":27,"text":280,"correct":22},"0.25g；",{"key":30,"text":282,"correct":22},"0.3g。",{"id":284,"libraryId":5,"type":15,"typeLabel":16,"stem":285,"options":286,"answer":24,"analysis":33},1023685,"屋内配电装置电气设备外绝缘体最低部位距地小于（）时，应装设固定遮栏。",[287,289,291,293],{"key":20,"text":288,"correct":22},"2.Om；",{"key":24,"text":290,"correct":32},"2.3m；",{"key":27,"text":292,"correct":22},"2.5m;",{"key":30,"text":294,"correct":22},"3m。",{"id":296,"libraryId":5,"type":15,"typeLabel":16,"stem":297,"options":298,"answer":24,"analysis":33},1023686,"屋外配电装置玖值的确定（）。",[299,301,303,305],{"key":20,"text":300,"correct":22},"B1=A1+25cm;",{"key":24,"text":302,"correct":32},"B1=A1+75cm;",{"key":27,"text":304,"correct":22},"B1=A1+230cm;",{"key":30,"text":306,"correct":22},"B1=A1+250cm。",{"id":308,"libraryId":5,"type":15,"typeLabel":16,"stem":309,"options":310,"answer":30,"analysis":33},1023687,"高型布置的220kV屋外配电装置，应设高层通道和必要的围栏，通道宽度可采用()。",[311,313,315,317],{"key":20,"text":312,"correct":22},"8OOmm；",{"key":24,"text":314,"correct":22},"1.8m；",{"key":27,"text":316,"correct":22},"2m；",{"key":30,"text":318,"correct":32},"3~3.6m。",{"id":320,"libraryId":5,"type":15,"typeLabel":16,"stem":321,"options":322,"answer":27,"analysis":33},1023688,"普通中型布置的屋外配电装置内的环形道路及500kV配电装置内的相间道路宽度可采用（）。",[323,325,326,328],{"key":20,"text":324,"correct":22},"1.5m；",{"key":24,"text":316,"correct":22},{"key":27,"text":327,"correct":32},"3m；",{"key":30,"text":329,"correct":22},"4.5m。",{"id":331,"libraryId":5,"type":15,"typeLabel":16,"stem":332,"options":333,"answer":27,"analysis":33},1023689,"屋外配电装置的导体，应根据当地气象条件和不同受力状态进行力学计算。其荷载长期作用时的安全系数不应小于（）。",[334,336,338,340],{"key":20,"text":335,"correct":22},"2.5；",{"key":24,"text":337,"correct":22},"1.67；",{"key":27,"text":339,"correct":32},"4.0；",{"key":30,"text":341,"correct":22},"2.0。",{"id":343,"libraryId":5,"type":15,"typeLabel":16,"stem":344,"options":345,"answer":27,"analysis":33},1023690,"330~500kV配电装置宜采用屋外（）布置，海拔髙度大于1000m地区及发电厂场地狭小时，也可采用气体绝缘金属封闭开关设备（GIS）。",[346,348,350,352],{"key":20,"text":347,"correct":22},"高型；",{"key":24,"text":349,"correct":22},"半高型；",{"key":27,"text":351,"correct":32},"中型；",{"key":30,"text":353,"correct":22},"组合式配电装置（PASS)。",{"id":355,"libraryId":5,"type":15,"typeLabel":16,"stem":356,"options":357,"answer":20,"analysis":33},1023691,"一个半断路器接线的500kV配电装置布置型式一般有三列式布置、平环式布置和单列式布置三种，其中占地面积最小的是（）。",[358,360,362,364],{"key":20,"text":359,"correct":32},"三列式布里；",{"key":24,"text":361,"correct":22},"平环式布置；",{"key":27,"text":363,"correct":22},"单列式布置；",{"key":30,"text":365,"correct":22},"三个方案相同。",{"id":367,"libraryId":5,"type":15,"typeLabel":16,"stem":368,"options":369,"answer":20,"analysis":33},1023692,"屋内配电装置中，开关柜采用手车式双列布置时，操作通道的最小宽度为（）。",[370,372,374,376],{"key":20,"text":371,"correct":32},"双车长+900mm;",{"key":24,"text":373,"correct":22},"双车长+1000mm;",{"key":27,"text":375,"correct":22},"单车长+1200mm;",{"key":30,"text":377,"correct":22},"单车长+1500mm。",{"id":379,"libraryId":5,"type":15,"typeLabel":16,"stem":380,"options":381,"answer":24,"analysis":33},1023693,"发电厂和变电站的屋外配电装置，其周围宜围以髙度不低于（）的围栏，以防止外人任意进入。",[382,384,386,388],{"key":20,"text":383,"correct":22},"1.2m；",{"key":24,"text":385,"correct":32},"1.5m;",{"key":27,"text":387,"correct":22},"1.7m；",{"key":30,"text":389,"correct":22},"1.9m。",{"id":391,"libraryId":5,"type":15,"typeLabel":16,"stem":392,"options":393,"answer":20,"analysis":33},1023694,"总油量超过()的屋内油浸电力变压器，宜装设在单独的防爆间内，并应设置消防设施。",[394,396,398,400],{"key":20,"text":395,"correct":32},"1OOkg5",{"key":24,"text":397,"correct":22},"200kg,",{"key":27,"text":399,"correct":22},"300kg；",{"key":30,"text":401,"correct":22},"500kg。",{"id":403,"libraryId":5,"type":15,"typeLabel":16,"stem":404,"options":405,"answer":27,"analysis":33},1023695,"发电厂内容量为（）及以上的油浸变压器，应设置火灾探测报警及水喷雾灭火系统或其他灭火设施。",[406,408,410,412],{"key":20,"text":407,"correct":22},"31500kVA,;",{"key":24,"text":409,"correct":22},"63000kVA;",{"key":27,"text":411,"correct":32},"90000kVA;",{"key":30,"text":413,"correct":22},"125000kVA。",{"id":415,"libraryId":5,"type":15,"typeLabel":16,"stem":416,"options":417,"answer":27,"analysis":33},1023696,"在500kV及以下电压等级的发电厂和变电站中，容量为（)以上的主变压器，在有条件时宜设置水喷雾灭火装置。",[418,420,421,423],{"key":20,"text":419,"correct":22},"31500kVA；",{"key":24,"text":409,"correct":22},{"key":27,"text":422,"correct":32},"90000kVA；",{"key":30,"text":413,"correct":22},{"id":425,"libraryId":5,"type":15,"typeLabel":16,"stem":426,"options":427,"answer":24,"analysis":33},1023697,"当屋外油浸变压器之间需设置防火墙时，防火墙高度不宜低于变压器油枕的顶端高程，其长度应大于变压器储油池两侧各（）。",[428,430,432,433],{"key":20,"text":429,"correct":22},"0.5m;",{"key":24,"text":431,"correct":32},"1m;",{"key":27,"text":324,"correct":22},{"key":30,"text":294,"correct":22},{"id":435,"libraryId":5,"type":15,"typeLabel":16,"stem":436,"options":437,"answer":24,"analysis":33},1023698,"配电装置室的长度大于7m时,应有两个出口，并宜布置在配电装置室的两端；长度超过（）时，宜增添一个出口。",[438,440,442,444],{"key":20,"text":439,"correct":22},"50m；",{"key":24,"text":441,"correct":32},"60m；",{"key":27,"text":443,"correct":22},"70m；",{"key":30,"text":445,"correct":22},"80m。",{"id":447,"libraryId":5,"type":15,"typeLabel":16,"stem":448,"options":449,"answer":20,"analysis":33},1023699,"对于导线跨中有引下线的（）及以上电压的构架，应考虑导线上人，并分别验算单相作业和三相作业的受力状态。",[450,452,454,456],{"key":20,"text":451,"correct":32},"11OkV,",{"key":24,"text":453,"correct":22},"220kV;",{"key":27,"text":455,"correct":22},"330kV;",{"key":30,"text":457,"correct":22},"500kV。",{"id":459,"libraryId":5,"type":15,"typeLabel":16,"stem":460,"options":461,"answer":30,"analysis":33},1023700,"基本烈度为9度的地区不宜建()变电站。",[462,464,466,468],{"key":20,"text":463,"correct":22},"35~66kV;",{"key":24,"text":465,"correct":22},"66~110kV;",{"key":27,"text":467,"correct":22},"110~220kV;",{"key":30,"text":469,"correct":32},"220~500kV。",{"id":471,"libraryId":5,"type":15,"typeLabel":16,"stem":472,"options":473,"answer":24,"analysis":33},1023701,"关于高烈度地震地区配电装置的设计，下列论述中错误的是（）。",[474,476,478,480],{"key":20,"text":475,"correct":22},"电压为330kV及以上的电气设施设防烈度7度及以上时，应进行抗震设计；",{"key":24,"text":477,"correct":32},"当设防烈度为9度时，电压为11OkV及以上管型母线配电装置的管型母线宜采用支持式结构；",{"key":27,"text":479,"correct":22},"当设防烈度为8度或9度时，限流电抗器不宜采用三相垂直布置；",{"key":30,"text":481,"correct":22},"当设防烈度为7度及以上时，电气设备的引线和设备间连线宜釆用软导线，其长度应留有余量。",{"id":483,"libraryId":5,"type":15,"typeLabel":16,"stem":484,"options":485,"answer":20,"analysis":33},1023702,"污秽地区配电装置悬垂绝缘子串的片数与耐张绝缘子串片数的关系是（）。",[486,488,490,492],{"key":20,"text":487,"correct":32},"两者片数相同；",{"key":24,"text":489,"correct":22},"两者片数不等；",{"key":27,"text":491,"correct":22},"悬垂串片数比耐张串多1片；",{"key":30,"text":493,"correct":22},"悬垂串片数比耐张串少1片。",{"id":495,"libraryId":5,"type":15,"typeLabel":16,"stem":496,"options":497,"answer":30,"analysis":33},1023703,"对于安装在海拔高度超过1000m地区的电气设备外绝缘一般应预加强。当海拔高度在（）以下时，其工频和冲击试验电压应乘以系数 ，H为安装地点的海拔高度。",[498,500,502,504],{"key":20,"text":499,"correct":22},"2500m;",{"key":24,"text":501,"correct":22},"3000m；",{"key":27,"text":503,"correct":22},"3500m；",{"key":30,"text":505,"correct":32},"4000m。",{"id":507,"libraryId":5,"type":15,"typeLabel":16,"stem":508,"options":509,"answer":27,"analysis":33},1023704,"户外电容器组中电容器底部距地面的最小距离是（）。",[510,512,514,516],{"key":20,"text":511,"correct":22},"1OOmm；",{"key":24,"text":513,"correct":22},"200mm；",{"key":27,"text":515,"correct":32},"300mm；",{"key":30,"text":517,"correct":22},"400mm。",{"id":519,"libraryId":5,"type":15,"typeLabel":16,"stem":520,"options":521,"answer":24,"analysis":33},1023705,"500kV配电装置采用软母线，导线直径为50mm,其局部断面图如图8-1所示（母线挂线点髙度为20m,导线弧垂尺寸，跨线为3500mm，母线弧垂为2000mm)，请根据以下各题要求分析（或计算）回答问题。 试计算出线构架梁高度H1的最小值为（）。",[522,524,526,528],{"key":20,"text":523,"correct":22},"2690.8cm;",{"key":24,"text":525,"correct":32},"2707.5cm;",{"key":27,"text":527,"correct":22},"2660.6cm;",{"key":30,"text":529,"correct":22},"2750.3cm。",{"id":531,"libraryId":5,"type":15,"typeLabel":16,"stem":532,"options":533,"answer":27,"analysis":33},1023706,"500kV配电装置采用软母线，导线直径为50mm,其局部断面图如图8-1所示（母线挂线点髙度为20m,导线弧垂尺寸，跨线为3500mm，母线弧垂为2000mm)，请根据以下各题要求分析（或计算）回答问题。 假定500kV配电装置间隔宽度为30m，图8-1中H1=28m，试通过计算确定图中H2的最小值为(）。",[534,536,538,540],{"key":20,"text":535,"correct":22},"36m;",{"key":24,"text":537,"correct":22},"38m；",{"key":27,"text":539,"correct":32},"37m；",{"key":30,"text":541,"correct":22},"39m。",{"id":543,"libraryId":5,"type":15,"typeLabel":16,"stem":544,"options":545,"answer":20,"analysis":33},1023707,"500kV配电装置采用软母线，导线直径为50mm,其局部断面图如图8-1所示（母线挂线点髙度为20m,导线弧垂尺寸，跨线为3500mm，母线弧垂为2000mm)，请根据以下各题要求分析（或计算）回答问题。 请确定图8-1的X1、X2、X3、X4、X5值(单位为mm)为（），并说明其校验条件值.",[546,548,550,552],{"key":20,"text":547,"correct":32},"X1=3800、X2=4300、X3=4550、X4=4550、X5=7500；",{"key":24,"text":549,"correct":22},"X1=3800、X2=4550、X3=4550、X4=4550、X5=7500；",{"key":27,"text":551,"correct":22},"X1=3800、X2=4550、X3=4300、X4=4550、X5=7500；",{"key":30,"text":553,"correct":22},"X1=3800、X2=4550、X3=5800、X4=4300、X5=7500.",{"id":555,"libraryId":5,"type":15,"typeLabel":16,"stem":556,"options":557,"answer":24,"analysis":33},1023708,"220kV配电装置的局部断面图如图8-2所示，请根据下面各题的假设条件，分析(或计算）回答相关问题。 图8-2中？处的带电距离尺寸为（）。",[558,560,562,564],{"key":20,"text":559,"correct":22},"1500mm;",{"key":24,"text":561,"correct":32},"1800mm;",{"key":27,"text":563,"correct":22},"2000mm;",{"key":30,"text":565,"correct":22},"1600mm。",{"id":567,"libraryId":5,"type":15,"typeLabel":16,"stem":568,"options":569,"answer":27,"analysis":33},1023709,"220kV配电装置的局部断面图如图8-2所示，请根据下面各题的假设条件，分析(或计算）回答相关问题。 假定经海拔修正后的A1值为1900mm，试确定图中的X值为（）。",[570,572,574,576],{"key":20,"text":571,"correct":22},"3700mm；",{"key":24,"text":573,"correct":22},"3800mm;",{"key":27,"text":575,"correct":32},"3900mm；",{"key":30,"text":577,"correct":22},"4000mm。",{"id":579,"libraryId":5,"type":15,"typeLabel":16,"stem":580,"options":581,"answer":24,"analysis":33},1023710,"220kV配电装置的局部断面图如图8-2所示，请根据下面各题的假设条件，分析(或计算）回答相关问题。 请根据220kV配电装置相关规定，当A1值为1900mm时，确定图8-2中的Y值为()。",[582,584,586,588],{"key":20,"text":583,"correct":22},"3400mm；",{"key":24,"text":585,"correct":32},"4400mm；",{"key":27,"text":587,"correct":22},"4300mm；",{"key":30,"text":589,"correct":22},"4600mm.",{"id":591,"libraryId":5,"type":15,"typeLabel":16,"stem":592,"options":593,"answer":20,"analysis":33},1023711,"220kV配电装置的局部断面图如图8-2所示，请根据下面各题的假设条件，分析(或计算）回答相关问题。 设计220kV配电装置时采用的最大设计风速，以下考虑正确的是（）。",[594,596,598,600],{"key":20,"text":595,"correct":32},"离地1Om髙，30年一遇的1Omin平均最大风速，超过35m\u002Fs时在布里上不必采取措施；",{"key":24,"text":597,"correct":22},"离地1Om高，30年一遇的1Omin平均最大风速，超过35m\u002Fs时在布置上应采取措施;",{"key":27,"text":599,"correct":22},"离地1Om高，30年一遇的15min平均最大风速，超过35m\u002Fs时在布里上应采取措施;",{"key":30,"text":601,"correct":22},"离地1Om高，30年一遇的15min平均最大风速，超过38m\u002Fs时在布里上应采取措施。",{"id":603,"libraryId":5,"type":15,"typeLabel":16,"stem":604,"options":605,"answer":20,"analysis":33},1023712,"关于三角形接线或四角、五角形接线是否可以无限制扩大到五角以上，下列说法正 确的是（ )",[606,608,610,612],{"key":20,"text":607,"correct":32},"不宜；",{"key":24,"text":609,"correct":22},"可以；",{"key":27,"text":611,"correct":22},"根据系统情况决定；",{"key":30,"text":613,"correct":22},"没有規定",[615,618,621,624,627,630],{"id":15,"name":616,"category":7,"favorite":617},"领导干部任职前廉政法规知识测试题",92,{"id":619,"name":620,"category":7,"favorite":15},595,"建筑结构与设备",{"id":622,"name":623,"category":7,"favorite":15},715,"招标采购专业知识与法律法规",{"id":625,"name":626,"category":7,"favorite":15},848,"市政方向-通用基础",{"id":628,"name":629,"category":7,"favorite":8},534,"BIM工程师",{"id":631,"name":629,"category":7,"favorite":8},535]