[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"lib-751-36":3},{"library":4,"page":9,"limit":10,"total":11,"questions":12,"related":619},{"id":5,"name":6,"category":7,"favorite":8},751,"电气工程师发输变电专业","建筑工程",0,36,50,2670,[13,34,46,58,70,82,94,106,117,129,140,152,164,176,188,200,212,224,236,247,259,271,283,295,307,319,331,343,355,367,379,391,403,415,427,439,451,463,475,487,499,511,523,535,547,559,571,583,595,607],{"id":14,"libraryId":5,"type":15,"typeLabel":16,"stem":17,"options":18,"answer":24,"analysis":33},1023509,1,"单选题","某电厂为220kV送出，220kV单相短路电流最大，为46.449kA,此时入地短路电流为28.345k A，短路的等效持续时间为0.2s，接地网为复合接地网，水平接地极为镀锌扁钢，垂直接地极为50X50X5的角钢。厂区土壤比较潮湿。 接地网总面积：S=406010m2, 水平接地体埋深：h=1.Om； 接地网边缘边线总长：L0=3820m； 水平接地体总长：L=22900m, 雷季中无雨水时，实测土壤电阻率：ρ0=55.4Ω?m； 季节系数为1.2~1.45，土壤较银时取大值； 地网设计寿命30年。 明敷的接地线表面应涂刷（）颜色相间的条纹。",[19,23,27,30],{"key":20,"text":21,"correct":22},"A","红、蓝；",false,{"key":24,"text":25,"correct":26},"B","绿、黄；",true,{"key":28,"text":29,"correct":22},"C","黄、蓝；",{"key":31,"text":32,"correct":22},"D","红、绿。","",{"id":35,"libraryId":5,"type":15,"typeLabel":16,"stem":36,"options":37,"answer":24,"analysis":33},1023510,"某电厂为220kV送出，220kV单相短路电流最大，为46.449kA,此时入地短路电流为28.345k A，短路的等效持续时间为0.2s，接地网为复合接地网，水平接地极为镀锌扁钢，垂直接地极为50X50X5的角钢。厂区土壤比较潮湿。 接地网总面积：S=406010m2, 水平接地体埋深：h=1.Om； 接地网边缘边线总长：L0=3820m； 水平接地体总长：L=22900m, 雷季中无雨水时，实测土壤电阻率：ρ0=55.4Ω?m； 季节系数为1.2~1.45，土壤较银时取大值； 地网设计寿命30年。 该电厂的水平接地极宜采用以下（）钢材。",[38,40,42,44],{"key":20,"text":39,"correct":22},"镀辞扁钢50X5；",{"key":24,"text":41,"correct":26},"镀锌扁钢60X6；",{"key":28,"text":43,"correct":22},"镀锌扁钢60X8；",{"key":31,"text":45,"correct":22},"扁钢60X8。",{"id":47,"libraryId":5,"type":15,"typeLabel":16,"stem":48,"options":49,"answer":24,"analysis":33},1023511,"某发电厂过电压保护及绝缘配合的设计中。 以3支等高避雷针保护燃油罐区，假定针高30m，被保护物高度为7m，为使保护面积最大，避雷针向距的最大值宜取（）。",[50,52,54,56],{"key":20,"text":51,"correct":22},"161m；",{"key":24,"text":53,"correct":26},"150m；",{"key":28,"text":55,"correct":22},"210m；",{"key":31,"text":57,"correct":22},"159m。",{"id":59,"libraryId":5,"type":15,"typeLabel":16,"stem":60,"options":61,"answer":28,"analysis":33},1023512,"某发电厂过电压保护及绝缘配合的设计中。 烟囱顶面距地面高210m，顶上设有2. 5m高的避雷针，烟囱避雷针与细近1支高25m的独立避雷针的间距为100m，沿避雷针连线布置有一列高度为15m的氢管架，则氢管架的宽度不大于（）。",[62,64,66,68],{"key":20,"text":63,"correct":22},"5.1m；",{"key":24,"text":65,"correct":22},"6.1m；",{"key":28,"text":67,"correct":26},"7.1m；",{"key":31,"text":69,"correct":22},"8.1m。",{"id":71,"libraryId":5,"type":15,"typeLabel":16,"stem":72,"options":73,"answer":28,"analysis":33},1023513,"某发电厂过电压保护及绝缘配合的设计中。 电厂送出电压为110kV,共4回线路，均为同塔双回，线路长度5km，全线设有避雷线。110kV配电装置仅设置有母线避雷器，采用金屑氧化物避雷器，所有电气设备均为标准绝缘水平，试确定母线避雷器与出线隔离开关的最大电气距离应为（）。",[74,76,78,80],{"key":20,"text":75,"correct":22},"170m；",{"key":24,"text":77,"correct":22},"229.5m；",{"key":28,"text":79,"correct":26},"230m；",{"key":31,"text":81,"correct":22},"310.5m。",{"id":83,"libraryId":5,"type":15,"typeLabel":16,"stem":84,"options":85,"answer":20,"analysis":33},1023514,"某发电厂过电压保护及绝缘配合的设计中。 发电机额定电压为10.5kV，最髙电压为12kV，厂内设有发电机电压配电装置,为经消弧线圈接地系统，母线避雷器选用有串联间睐金属氧化物避雷器，其额定电压不低于（）。",[86,88,90,92],{"key":20,"text":87,"correct":26},"13.2kV；",{"key":24,"text":89,"correct":22},"15kV；",{"key":28,"text":91,"correct":22},"11.55kV；",{"key":31,"text":93,"correct":22},"13.125kV。",{"id":95,"libraryId":5,"type":15,"typeLabel":16,"stem":96,"options":97,"answer":24,"analysis":33},1023515,"某钢铁公司自备电站建有2X60MW热电联产机组，分别以发电机一变压器组单元接线接入厂内110kV配电装置，起备电源从厂内11OkV引接，出线间隔6个。 110kV采用双母线带旁路接线，设专用旁路断路器，母线设备占用1个间隔，屋外采用软母线，屋内采用铝管母线，配电装置占地约2500m2，试问110kV配电装置的型式为（）（假定母线端点即为配电装置的长度的端点）。",[98,100,102,104],{"key":20,"text":99,"correct":22},"屋外普通中型；",{"key":24,"text":101,"correct":26},"屋外半高型（田字形）；",{"key":28,"text":103,"correct":22},"屋外半高型（品字形）；",{"key":31,"text":105,"correct":22},"屋内型。",{"id":107,"libraryId":5,"type":15,"typeLabel":16,"stem":108,"options":109,"answer":28,"analysis":33},1023516,"某钢铁公司自备电站建有2X60MW热电联产机组，分别以发电机一变压器组单元接线接入厂内110kV配电装置，起备电源从厂内11OkV引接，出线间隔6个。 110kV配电装置采用了铝管母线，母线穿越功率130MV A，母线计算跨距7.5m，忽略跨中集中荷载，每两跨设一个伸缩接头。宜选用（）铝管母线。 A.φ30\u002F25； B.φ40\u002F35,",[110,112,114,115],{"key":20,"text":111,"correct":22},"φ0\u002F45；",{"key":24,"text":113,"correct":22},"φ60\u002F54。",{"key":28,"text":33,"correct":26},{"key":31,"text":116,"correct":22},"弹性模量E=7.1X1O5kg\u002Fcm2，φ0\u002F25的自重q1=0.68kg\u002Fm。",{"id":118,"libraryId":5,"type":15,"typeLabel":16,"stem":119,"options":120,"answer":31,"analysis":33},1023517,"某钢铁公司自备电站建有2X60MW热电联产机组，分别以发电机一变压器组单元接线接入厂内110kV配电装置，起备电源从厂内11OkV引接，出线间隔6个。 110kV如采用屋外中型配电装置，以下答案中，（）不是减少占地的措施。",[121,123,125,127],{"key":20,"text":122,"correct":22},"采用管母线配电装里；",{"key":24,"text":124,"correct":22},"将主母线架构与中央门型架构合并成联合架构；",{"key":28,"text":126,"correct":22},"采用V型隔离开关；",{"key":31,"text":128,"correct":26},"将母线及母线隔离开关抬高，使断路器、电流互感器等布置在母线的下方。",{"id":130,"libraryId":5,"type":15,"typeLabel":16,"stem":131,"options":132,"answer":24,"analysis":33},1023518,"某钢铁公司自备电站建有2X60MW热电联产机组，分别以发电机一变压器组单元接线接入厂内110kV配电装置，起备电源从厂内11OkV引接，出线间隔6个。 经技术经济比较，本自备电站的11OkV配电装置采用了屋内GIS配电装置，取消了旁路母线。GIS设备招标文件技术部分中罗列了以下技术要求，不对的是（）。 A.基本要求： 额定电压：126kV； 相间雷电冲击耐受电压（峰值）：550kV； 相间工頻耐受电压（1min有效值）：230kV； 控制回路额定电压：DC 220V B.环境及人身安全方面的要求： 在发生短路故障的情况下，外壳的感应电压不应超过：24V 无线电千扰水平（在1.1x110\u002F√3kV下）：≤500μV； 断路器在操作时，噪声水平不应超过：90dB（测试位置为距断路器外沿垂直面的水平距离为2m，离地髙1~1.5m处）； 每个SF6气体隔室的相对年泄漏率不应大于： C.断路器要求： 断口教量：1个； 首相开断系数：1.3； 額定短路持续时间：4s； 母联及变压器回路的操动机构：三相联动 D.电压互感器要求： 型式：电磁式",[133,135,136,138],{"key":20,"text":134,"correct":22},"额定电压比：",{"key":24,"text":33,"correct":26},{"key":28,"text":137,"correct":22},"准确级：1号主二次绕组0.5,2号主二次绕组0.2，剩余绕组3P",{"key":31,"text":139,"correct":22},"相数：母线为三相、出线为单相",{"id":141,"libraryId":5,"type":15,"typeLabel":16,"stem":142,"options":143,"answer":24,"analysis":33},1023519,"某发电厂高压厂用电电压采用1OkV,中性点经高阻接地，所有负荷在发生单相接地时均要求立即跳闸。热力系统中有电动给水泵1台，配套电机为3000kW。 在某电缆样本中摘得以下电缆额定电压数据，该电动给水泵的供电电缆的额定电压宜选择（）（相地额定电压\u002F相间额定电压，kv\u002Fkv）。",[144,146,148,150],{"key":20,"text":145,"correct":22},"6\u002F10；",{"key":24,"text":147,"correct":26},"8.7\u002F10；",{"key":28,"text":149,"correct":22},"10\u002F10；",{"key":31,"text":151,"correct":22},"8.7\u002F15。",{"id":153,"libraryId":5,"type":15,"typeLabel":16,"stem":154,"options":155,"answer":31,"analysis":33},1023520,"某发电厂高压厂用电电压采用1OkV,中性点经高阻接地，所有负荷在发生单相接地时均要求立即跳闸。热力系统中有电动给水泵1台，配套电机为3000kW。 该电动给水泵回路的电缆拟采用单芯电缆，截面为150,电缆外径为40mm，至电动机处需采用一段约12m长、直角弯不超过2个的电缆保护管，试问该电缆保护管宜为（）。",[156,158,160,162],{"key":20,"text":157,"correct":22},"1根φ70（内径68mm）的键锌钢管；",{"key":24,"text":159,"correct":22},"3根φ70（内径68mm）的镀锌钢管；",{"key":28,"text":161,"correct":22},"1根φ100（内径106mm）的镀锌钢管；",{"key":31,"text":163,"correct":26},"1根φ125（内径131mm）的镀锌钢管。",{"id":165,"libraryId":5,"type":15,"typeLabel":16,"stem":166,"options":167,"answer":31,"analysis":33},1023521,"某发电厂高压厂用电电压采用1OkV,中性点经高阻接地，所有负荷在发生单相接地时均要求立即跳闸。热力系统中有电动给水泵1台，配套电机为3000kW。 如该电动给水泵回路的电缆采用YJV—8. 7\u002F10—3X185，根据图纸测量，电缆实际路径为120m，无中间接头，1OkV开关柜处的电缆引接端子距地高度可按低压配电盘考虑，则该电缆的订货长度宜取（）。",[168,170,172,174],{"key":20,"text":169,"correct":22},"120m;",{"key":24,"text":171,"correct":22},"123m；",{"key":28,"text":173,"correct":22},"127m；",{"key":31,"text":175,"correct":26},"130m。",{"id":177,"libraryId":5,"type":15,"typeLabel":16,"stem":178,"options":179,"answer":24,"analysis":33},1023522,"某发电厂高压厂用电电压采用1OkV,中性点经高阻接地，所有负荷在发生单相接地时均要求立即跳闸。热力系统中有电动给水泵1台，配套电机为3000kW。 该电动给水泵回路宜装设的保护是（）。",[180,182,184,186],{"key":20,"text":181,"correct":22},"纵联差动保护（含电缆）、电流速断保护、过电流保护；",{"key":24,"text":183,"correct":26},"纵联差动保护（含电缆）、过电流保护、单相接地保护；",{"key":28,"text":185,"correct":22},"纵联差动保护（含电缆）、单相接地保护、过负荷保护；",{"key":31,"text":187,"correct":22},"纵联差动保护（含电缆）、过电流保护、单相接地保护、过负荷保护。",{"id":189,"libraryId":5,"type":15,"typeLabel":16,"stem":190,"options":191,"answer":20,"analysis":33},1023523,"某电厂新建2X300MW国产亚临界燃煤机组，机组以发电机一变压器组单元接线接入220kV系统双母线，220kV配电装g采用双母线母联兼旁路母线接线方式，启动\u002F备用电源由老厂11OkV母线引接，主变压器中性点和启动\u002F备用变中性点经隔离开关接地，根据系统需要可直接接地或不接地运行，发电机中性点经二次侧接有电阻的单相变压器接地，髙厂变压器及启备变压器低压侧中性点经电阻接地，电阻为9.1Ω,400A,发电机次暂态电抗为16.01%。髙压启动\u002F备用变压器的中性点采用固定接地方式，主变压器中性点经隔离开关接地方式，髙压厂用变压器及启\u002F备变半穿越阻抗为21%，高压厂用变压器及髙压启动\u002F备用变压器均采用分裂绕组型变压器，髙压厂用电设两段公用段及脱硫段，分别由机组髙压厂用工作段供电。 关于发电机变压器组保护配置，下列说法错误的是（）。",[192,194,196,198],{"key":20,"text":193,"correct":26},"发电机变压器组主保护应具有发电机纵联差动保护和变压器纵联差动保护，不必按照双重化的原则配置；",{"key":24,"text":195,"correct":22},"发电机应配里过励磁保护，宜配置突然加电压保护和失步保护；",{"key":28,"text":197,"correct":22},"发电机变压器组主保护，宜配置发电机纵联差动保护和变压器纵联差动保护；",{"key":31,"text":199,"correct":22},"纵联差动倮护，应装设电流回路断线监视装置。",{"id":201,"libraryId":5,"type":15,"typeLabel":16,"stem":202,"options":203,"answer":28,"analysis":33},1023524,"某电厂新建2X300MW国产亚临界燃煤机组，机组以发电机一变压器组单元接线接入220kV系统双母线，220kV配电装g采用双母线母联兼旁路母线接线方式，启动\u002F备用电源由老厂11OkV母线引接，主变压器中性点和启动\u002F备用变中性点经隔离开关接地，根据系统需要可直接接地或不接地运行，发电机中性点经二次侧接有电阻的单相变压器接地，髙厂变压器及启备变压器低压侧中性点经电阻接地，电阻为9.1Ω,400A,发电机次暂态电抗为16.01%。髙压启动\u002F备用变压器的中性点采用固定接地方式，主变压器中性点经隔离开关接地方式，髙压厂用变压器及启\u002F备变半穿越阻抗为21%，高压厂用变压器及髙压启动\u002F备用变压器均采用分裂绕组型变压器，髙压厂用电设两段公用段及脱硫段，分别由机组髙压厂用工作段供电。 关于发电机变压器组保护的出口动作方式，下列说法正确的是（）。",[204,206,208,210],{"key":20,"text":205,"correct":22},"发电机定子接地保护，带时限动作于信号，也可动作于发电机减功率；",{"key":24,"text":207,"correct":22},"发电机定子绕组过负荷的反时限部分应动作于解列或程序跳闸；",{"key":28,"text":209,"correct":26},"发电批励磁回路一点接地、頻率异常、励磁电流异常下降或消失等异常运行方式，保护动作于停机，宜采用程序跳闸方式；",{"key":31,"text":211,"correct":22},"发电机励磁统组过负荷保护的反时限部分应动作于解列。",{"id":213,"libraryId":5,"type":15,"typeLabel":16,"stem":214,"options":215,"answer":24,"analysis":33},1023525,"某电厂新建2X300MW国产亚临界燃煤机组，机组以发电机一变压器组单元接线接入220kV系统双母线，220kV配电装g采用双母线母联兼旁路母线接线方式，启动\u002F备用电源由老厂11OkV母线引接，主变压器中性点和启动\u002F备用变中性点经隔离开关接地，根据系统需要可直接接地或不接地运行，发电机中性点经二次侧接有电阻的单相变压器接地，髙厂变压器及启备变压器低压侧中性点经电阻接地，电阻为9.1Ω,400A,发电机次暂态电抗为16.01%。髙压启动\u002F备用变压器的中性点采用固定接地方式，主变压器中性点经隔离开关接地方式，髙压厂用变压器及启\u002F备变半穿越阻抗为21%，高压厂用变压器及髙压启动\u002F备用变压器均采用分裂绕组型变压器，髙压厂用电设两段公用段及脱硫段，分别由机组髙压厂用工作段供电。 本工程发电机保护TA变比为15000\u002F5 A，5P20,发电机定子額定电流10190 A，发电机次暂态电抗Xd\"=16.01%,请根据上述已知条件回答下列有关定子绕组过负荷保护问题。 定子绕组过负荷保护的定时限部分的动作电流可选择（）。",[216,218,220,222],{"key":20,"text":217,"correct":22},"3.12A；",{"key":24,"text":219,"correct":26},"3.75A；",{"key":28,"text":221,"correct":22},"4.50A；",{"key":31,"text":223,"correct":22},"5.24A。",{"id":225,"libraryId":5,"type":15,"typeLabel":16,"stem":226,"options":227,"answer":24,"analysis":33},1023526,"某电厂新建2X300MW国产亚临界燃煤机组，机组以发电机一变压器组单元接线接入220kV系统双母线，220kV配电装g采用双母线母联兼旁路母线接线方式，启动\u002F备用电源由老厂11OkV母线引接，主变压器中性点和启动\u002F备用变中性点经隔离开关接地，根据系统需要可直接接地或不接地运行，发电机中性点经二次侧接有电阻的单相变压器接地，髙厂变压器及启备变压器低压侧中性点经电阻接地，电阻为9.1Ω,400A,发电机次暂态电抗为16.01%。髙压启动\u002F备用变压器的中性点采用固定接地方式，主变压器中性点经隔离开关接地方式，髙压厂用变压器及启\u002F备变半穿越阻抗为21%，高压厂用变压器及髙压启动\u002F备用变压器均采用分裂绕组型变压器，髙压厂用电设两段公用段及脱硫段，分别由机组髙压厂用工作段供电。 对定子绕组过负荷保护的反时限部分的上限电流为（）。",[228,230,232,234],{"key":20,"text":229,"correct":22},"5.48A；",{"key":24,"text":231,"correct":26},"26.52A；",{"key":28,"text":233,"correct":22},"8.22A；",{"key":31,"text":235,"correct":22},"10.96A,",{"id":237,"libraryId":5,"type":15,"typeLabel":16,"stem":238,"options":239,"answer":28,"analysis":33},1023527,"某电厂新建2X300MW国产亚临界燃煤机组，机组以发电机一变压器组单元接线接入220kV系统双母线，220kV配电装g采用双母线母联兼旁路母线接线方式，启动\u002F备用电源由老厂11OkV母线引接，主变压器中性点和启动\u002F备用变中性点经隔离开关接地，根据系统需要可直接接地或不接地运行，发电机中性点经二次侧接有电阻的单相变压器接地，髙厂变压器及启备变压器低压侧中性点经电阻接地，电阻为9.1Ω,400A,发电机次暂态电抗为16.01%。髙压启动\u002F备用变压器的中性点采用固定接地方式，主变压器中性点经隔离开关接地方式，髙压厂用变压器及启\u002F备变半穿越阻抗为21%，高压厂用变压器及髙压启动\u002F备用变压器均采用分裂绕组型变压器，髙压厂用电设两段公用段及脱硫段，分别由机组髙压厂用工作段供电。 对定子绕组过负荷保护的反时限部分的下限电流可选择（）。",[240,241,243,245],{"key":20,"text":217,"correct":22},{"key":24,"text":242,"correct":22},"3.84A；",{"key":28,"text":244,"correct":26},"4.41A；",{"key":31,"text":246,"correct":22},"6.24A,",{"id":248,"libraryId":5,"type":15,"typeLabel":16,"stem":249,"options":250,"answer":24,"analysis":33},1023528,"某电厂新建2X300MW国产亚临界燃煤机组，机组以发电机一变压器组单元接线接入220kV系统双母线，220kV配电装g采用双母线母联兼旁路母线接线方式，启动\u002F备用电源由老厂11OkV母线引接，主变压器中性点和启动\u002F备用变中性点经隔离开关接地，根据系统需要可直接接地或不接地运行，发电机中性点经二次侧接有电阻的单相变压器接地，髙厂变压器及启备变压器低压侧中性点经电阻接地，电阻为9.1Ω,400A,发电机次暂态电抗为16.01%。髙压启动\u002F备用变压器的中性点采用固定接地方式，主变压器中性点经隔离开关接地方式，髙压厂用变压器及启\u002F备变半穿越阻抗为21%，高压厂用变压器及髙压启动\u002F备用变压器均采用分裂绕组型变压器，髙压厂用电设两段公用段及脱硫段，分别由机组髙压厂用工作段供电。 关于直流系统电压，下列说法正确的是（），",[251,253,255,257],{"key":20,"text":252,"correct":22},"控制负荷专用的蓄电池组的电压宜采用110V或220V；",{"key":24,"text":254,"correct":26},"动力负荷和直流亊故照明负荷专用蓄电池组的电压宜采用220V；",{"key":28,"text":256,"correct":22},"蓄电池组在正常浮充电方式下，直流母线电压应为直流系统額定电压的110%；",{"key":31,"text":258,"correct":22},"动力负荷系统的直流母线电压允许在直流系统額定电压的变化范S是85%~110%。",{"id":260,"libraryId":5,"type":15,"typeLabel":16,"stem":261,"options":262,"answer":31,"analysis":33},1023529,"某电厂新建2X300MW国产亚临界燃煤机组，机组以发电机一变压器组单元接线接入220kV系统双母线，220kV配电装g采用双母线母联兼旁路母线接线方式，启动\u002F备用电源由老厂11OkV母线引接，主变压器中性点和启动\u002F备用变中性点经隔离开关接地，根据系统需要可直接接地或不接地运行，发电机中性点经二次侧接有电阻的单相变压器接地，髙厂变压器及启备变压器低压侧中性点经电阻接地，电阻为9.1Ω,400A,发电机次暂态电抗为16.01%。髙压启动\u002F备用变压器的中性点采用固定接地方式，主变压器中性点经隔离开关接地方式，髙压厂用变压器及启\u002F备变半穿越阻抗为21%，高压厂用变压器及髙压启动\u002F备用变压器均采用分裂绕组型变压器，髙压厂用电设两段公用段及脱硫段，分别由机组髙压厂用工作段供电。 关于直流负荷统计时间，下列说法正确的是（）。",[263,265,267,269],{"key":20,"text":264,"correct":22},"本工租控制保护、监控系统直流负荷的亊故放电计算时间应为3h；",{"key":24,"text":266,"correct":22},"本工程氢密封油泵的亊故放电计算时同应为2h；",{"key":28,"text":268,"correct":22},"本工程直流润滑油泵的亊故放电计算时间应为3h；",{"key":31,"text":270,"correct":26},"UPS的亊故放电计算时闽为0.5h。",{"id":272,"libraryId":5,"type":15,"typeLabel":16,"stem":273,"options":274,"answer":28,"analysis":33},1023530,"某电厂新建2X300MW国产亚临界燃煤机组，机组以发电机一变压器组单元接线接入220kV系统双母线，220kV配电装g采用双母线母联兼旁路母线接线方式，启动\u002F备用电源由老厂11OkV母线引接，主变压器中性点和启动\u002F备用变中性点经隔离开关接地，根据系统需要可直接接地或不接地运行，发电机中性点经二次侧接有电阻的单相变压器接地，髙厂变压器及启备变压器低压侧中性点经电阻接地，电阻为9.1Ω,400A,发电机次暂态电抗为16.01%。髙压启动\u002F备用变压器的中性点采用固定接地方式，主变压器中性点经隔离开关接地方式，髙压厂用变压器及启\u002F备变半穿越阻抗为21%，高压厂用变压器及髙压启动\u002F备用变压器均采用分裂绕组型变压器，髙压厂用电设两段公用段及脱硫段，分别由机组髙压厂用工作段供电。 本工程动力用直流系统选用密封铅酸蓄电池组，浮充电压范围为2.25~2.30V，实际取值2.25V\u002F只，请问蓄电池组应选用蓄电池(1.05Un\u002FUf）（）只。",[275,277,279,281],{"key":20,"text":276,"correct":22},"100;",{"key":24,"text":278,"correct":22},"102；",{"key":28,"text":280,"correct":26},"103；",{"key":31,"text":282,"correct":22},"118。",{"id":284,"libraryId":5,"type":15,"typeLabel":16,"stem":285,"options":286,"answer":28,"analysis":33},1023531,"某电厂新建2X300MW国产亚临界燃煤机组，机组以发电机一变压器组单元接线接入220kV系统双母线，220kV配电装g采用双母线母联兼旁路母线接线方式，启动\u002F备用电源由老厂11OkV母线引接，主变压器中性点和启动\u002F备用变中性点经隔离开关接地，根据系统需要可直接接地或不接地运行，发电机中性点经二次侧接有电阻的单相变压器接地，髙厂变压器及启备变压器低压侧中性点经电阻接地，电阻为9.1Ω,400A,发电机次暂态电抗为16.01%。髙压启动\u002F备用变压器的中性点采用固定接地方式，主变压器中性点经隔离开关接地方式，髙压厂用变压器及启\u002F备变半穿越阻抗为21%，高压厂用变压器及髙压启动\u002F备用变压器均采用分裂绕组型变压器，髙压厂用电设两段公用段及脱硫段，分别由机组髙压厂用工作段供电。 单体莆电池均衡充电电压范围为2.33~2.35V，请问根据本工程的实际计算，动力用蓄电池组单体蓄电池均衡充电电压应选择（）为宜（Uc≤1.125Un\u002Fn）。",[287,289,291,293],{"key":20,"text":288,"correct":22},"2.25V；",{"key":24,"text":290,"correct":22},"2.75V；",{"key":28,"text":292,"correct":26},"2.35V；",{"key":31,"text":294,"correct":22},"2.50V,",{"id":296,"libraryId":5,"type":15,"typeLabel":16,"stem":297,"options":298,"answer":31,"analysis":33},1023532,"某电厂新建2X300MW国产亚临界燃煤机组，机组以发电机一变压器组单元接线接入220kV系统双母线，220kV配电装g采用双母线母联兼旁路母线接线方式，启动\u002F备用电源由老厂11OkV母线引接，主变压器中性点和启动\u002F备用变中性点经隔离开关接地，根据系统需要可直接接地或不接地运行，发电机中性点经二次侧接有电阻的单相变压器接地，髙厂变压器及启备变压器低压侧中性点经电阻接地，电阻为9.1Ω,400A,发电机次暂态电抗为16.01%。髙压启动\u002F备用变压器的中性点采用固定接地方式，主变压器中性点经隔离开关接地方式，髙压厂用变压器及启\u002F备变半穿越阻抗为21%，高压厂用变压器及髙压启动\u002F备用变压器均采用分裂绕组型变压器，髙压厂用电设两段公用段及脱硫段，分别由机组髙压厂用工作段供电。 本工程动力用蓄电池的放电终止电压应选择（）为宜（Um≥0.875Un\u002Fn）。",[299,301,303,305],{"key":20,"text":300,"correct":22},"1.75V；",{"key":24,"text":302,"correct":22},"1.80V;",{"key":28,"text":304,"correct":22},"1.85V；",{"key":31,"text":306,"correct":26},"1.87V。",{"id":308,"libraryId":5,"type":15,"typeLabel":16,"stem":309,"options":310,"answer":24,"analysis":33},1023533,"某电厂新建2X300MW国产亚临界燃煤机组，机组以发电机一变压器组单元接线接入220kV系统双母线，220kV配电装g采用双母线母联兼旁路母线接线方式，启动\u002F备用电源由老厂11OkV母线引接，主变压器中性点和启动\u002F备用变中性点经隔离开关接地，根据系统需要可直接接地或不接地运行，发电机中性点经二次侧接有电阻的单相变压器接地，髙厂变压器及启备变压器低压侧中性点经电阻接地，电阻为9.1Ω,400A,发电机次暂态电抗为16.01%。髙压启动\u002F备用变压器的中性点采用固定接地方式，主变压器中性点经隔离开关接地方式，髙压厂用变压器及启\u002F备变半穿越阻抗为21%，高压厂用变压器及髙压启动\u002F备用变压器均采用分裂绕组型变压器，髙压厂用电设两段公用段及脱硫段，分别由机组髙压厂用工作段供电。 本工程动力用直流负荷统计如下：经常负荷电流5 A，事故放电初期（1min）电流768 A，持续事故放电（30min）电流433.2A,持续事故放电（60min）电流215 A，事故放电末期或随机放电电流为147A,另外假定本工程蓄电池事故放电终止电压为1.90V，此时蓄电池组1min放电时的容量换算系数为1.18，29min为0.764，30min为0.755,59min为0.548，6Omin为0.520，随机负褕的容量换算系数为1.27，则本工程动力用蓄电池组容量应选择（）为宜。",[311,313,315,317],{"key":20,"text":312,"correct":22},"8OOAh；",{"key":24,"text":314,"correct":26},"1200Ah；",{"key":28,"text":316,"correct":22},"1500Ah；",{"key":31,"text":318,"correct":22},"2000Ah。",{"id":320,"libraryId":5,"type":15,"typeLabel":16,"stem":321,"options":322,"answer":28,"analysis":33},1023534,"某电厂新建2X300MW国产亚临界燃煤机组，机组以发电机一变压器组单元接线接入220kV系统双母线，220kV配电装g采用双母线母联兼旁路母线接线方式，启动\u002F备用电源由老厂11OkV母线引接，主变压器中性点和启动\u002F备用变中性点经隔离开关接地，根据系统需要可直接接地或不接地运行，发电机中性点经二次侧接有电阻的单相变压器接地，髙厂变压器及启备变压器低压侧中性点经电阻接地，电阻为9.1Ω,400A,发电机次暂态电抗为16.01%。髙压启动\u002F备用变压器的中性点采用固定接地方式，主变压器中性点经隔离开关接地方式，髙压厂用变压器及启\u002F备变半穿越阻抗为21%，高压厂用变压器及髙压启动\u002F备用变压器均采用分裂绕组型变压器，髙压厂用电设两段公用段及脱硫段，分别由机组髙压厂用工作段供电。 本工程动力用直流负荷统计如下：经常负荷电流5 A，事故放电初期（1min）电流768 A，持续事故放电（30min）电流433.2A,持续事故放电（60min）电流215 A，事故放电末期或随机放电电流为147A,另外假定本工程蓄电池事故放电终止电压为1.90V，此时蓄电池组1min放电时的容量换算系数为1.18，29min为0.764，30min为0.755,59min为0.548，6Omin为0.520，随机负褕的容量换算系数为1.27，则 本工程假定动力用蓄电池组容量为1200Ah，经常负荷电流4.5A,充电机额定电流应选择（）。",[323,325,327,329],{"key":20,"text":324,"correct":22},"80A；",{"key":24,"text":326,"correct":22},"120A；",{"key":28,"text":328,"correct":26},"160A；",{"key":31,"text":330,"correct":22},"200A。",{"id":332,"libraryId":5,"type":15,"typeLabel":16,"stem":333,"options":334,"answer":31,"analysis":33},1023535,"某电厂新建2X300MW国产亚临界燃煤机组，机组以发电机一变压器组单元接线接入220kV系统双母线，220kV配电装g采用双母线母联兼旁路母线接线方式，启动\u002F备用电源由老厂11OkV母线引接，主变压器中性点和启动\u002F备用变中性点经隔离开关接地，根据系统需要可直接接地或不接地运行，发电机中性点经二次侧接有电阻的单相变压器接地，髙厂变压器及启备变压器低压侧中性点经电阻接地，电阻为9.1Ω,400A,发电机次暂态电抗为16.01%。髙压启动\u002F备用变压器的中性点采用固定接地方式，主变压器中性点经隔离开关接地方式，髙压厂用变压器及启\u002F备变半穿越阻抗为21%，高压厂用变压器及髙压启动\u002F备用变压器均采用分裂绕组型变压器，髙压厂用电设两段公用段及脱硫段，分别由机组髙压厂用工作段供电。 蓄电池组至直流屏的电缆选择，下列说法正确的是（）。",[335,337,339,341],{"key":20,"text":336,"correct":22},"该电缆只需满足蓄电池组1h放电率电流即可；",{"key":24,"text":338,"correct":22},"该电缆只需满足蓄电池组至皇流屏的电压降小于1%即可；",{"key":28,"text":340,"correct":22},"该电缆只需满足蓄电池组至直流屏的电压降小于3%即可；",{"key":31,"text":342,"correct":26},"该电缆除应满足蓄电池组1h放电率电流外，还应满足蓄电池组至直流屏的电压降小于1%。",{"id":344,"libraryId":5,"type":15,"typeLabel":16,"stem":345,"options":346,"answer":24,"analysis":33},1023536,"某电厂新建2X300MW国产亚临界燃煤机组，机组以发电机一变压器组单元接线接入220kV系统双母线，220kV配电装g采用双母线母联兼旁路母线接线方式，启动\u002F备用电源由老厂11OkV母线引接，主变压器中性点和启动\u002F备用变中性点经隔离开关接地，根据系统需要可直接接地或不接地运行，发电机中性点经二次侧接有电阻的单相变压器接地，髙厂变压器及启备变压器低压侧中性点经电阻接地，电阻为9.1Ω,400A,发电机次暂态电抗为16.01%。髙压启动\u002F备用变压器的中性点采用固定接地方式，主变压器中性点经隔离开关接地方式，髙压厂用变压器及启\u002F备变半穿越阻抗为21%，高压厂用变压器及髙压启动\u002F备用变压器均采用分裂绕组型变压器，髙压厂用电设两段公用段及脱硫段，分别由机组髙压厂用工作段供电。 本工程髙压厂用变压器采用自然油循环风冷无载调压分裂绕组变压器，额定容量：髙压侧：40MVA低压侧：25-25MVA,接于发电机出线侧，发电机中性点经二次侧接有电阻的单相变压器接地，高压厂用变压器低压拥中性点经电阻接地，电阻为9.1Ω，400A。下列说法错误的是（）。",[347,349,351,353],{"key":20,"text":348,"correct":22},"高压厂用变压器高压側不单独装设单相接地保护，由发电机变压器組保护完成；",{"key":24,"text":350,"correct":26},"高压厂用变压器高压侧主保护可装设纵联差动保护，或装设电流速断保护；",{"key":28,"text":352,"correct":22},"高压厂用变压器低压侧应装设分支过流保护；",{"key":31,"text":354,"correct":22},"髙压厂用变压器低压側应装设中性点接地保护。",{"id":356,"libraryId":5,"type":15,"typeLabel":16,"stem":357,"options":358,"answer":28,"analysis":33},1023537,"某电厂新建2X300MW国产亚临界燃煤机组，机组以发电机一变压器组单元接线接入220kV系统双母线，220kV配电装g采用双母线母联兼旁路母线接线方式，启动\u002F备用电源由老厂11OkV母线引接，主变压器中性点和启动\u002F备用变中性点经隔离开关接地，根据系统需要可直接接地或不接地运行，发电机中性点经二次侧接有电阻的单相变压器接地，髙厂变压器及启备变压器低压侧中性点经电阻接地，电阻为9.1Ω,400A,发电机次暂态电抗为16.01%。髙压启动\u002F备用变压器的中性点采用固定接地方式，主变压器中性点经隔离开关接地方式，髙压厂用变压器及启\u002F备变半穿越阻抗为21%，高压厂用变压器及髙压启动\u002F备用变压器均采用分裂绕组型变压器，髙压厂用电设两段公用段及脱硫段，分别由机组髙压厂用工作段供电。 关于厂用电源切换，下列说法错误的是（）。",[359,361,363,365],{"key":20,"text":360,"correct":22},"高压厂用电源的正常切换宜采用手动并联切换，切换回路宜经同期闭锁；",{"key":24,"text":362,"correct":22},"高压厂用电源的事故切换宜采用快速串联断电切换方式，如快速不成功，应自动转为慢速切换方式；",{"key":28,"text":364,"correct":26},"低压厂用电源的正常切换宜采用手动断电切换方式，不允许电源并列；",{"key":31,"text":366,"correct":22},"低压厂用电源的亊故切换应采用延时自动断电切换方式，在时间上应与髙压厂用电源的切换相配合。",{"id":368,"libraryId":5,"type":15,"typeLabel":16,"stem":369,"options":370,"answer":31,"analysis":33},1023538,"某电厂新建2X300MW国产亚临界燃煤机组，机组以发电机一变压器组单元接线接入220kV系统双母线，220kV配电装g采用双母线母联兼旁路母线接线方式，启动\u002F备用电源由老厂11OkV母线引接，主变压器中性点和启动\u002F备用变中性点经隔离开关接地，根据系统需要可直接接地或不接地运行，发电机中性点经二次侧接有电阻的单相变压器接地，髙厂变压器及启备变压器低压侧中性点经电阻接地，电阻为9.1Ω,400A,发电机次暂态电抗为16.01%。髙压启动\u002F备用变压器的中性点采用固定接地方式，主变压器中性点经隔离开关接地方式，髙压厂用变压器及启\u002F备变半穿越阻抗为21%，高压厂用变压器及髙压启动\u002F备用变压器均采用分裂绕组型变压器，髙压厂用电设两段公用段及脱硫段，分别由机组髙压厂用工作段供电。 关于本工程电能表的装设，下列说法错误的是（）。",[371,373,375,377],{"key":20,"text":372,"correct":22},"高压厂用工作变压器应装设电能表；",{"key":24,"text":374,"correct":22},"髙压启动\u002F备用变压器应装设电能表；",{"key":28,"text":376,"correct":22},"低压厂用变压器可装设电能表；",{"key":31,"text":378,"correct":26},"低压电动机均应装设电能表，",{"id":380,"libraryId":5,"type":15,"typeLabel":16,"stem":381,"options":382,"answer":31,"analysis":33},1023539,"某电厂新建2X300MW国产亚临界燃煤机组，机组以发电机一变压器组单元接线接入220kV系统双母线，220kV配电装g采用双母线母联兼旁路母线接线方式，启动\u002F备用电源由老厂11OkV母线引接，主变压器中性点和启动\u002F备用变中性点经隔离开关接地，根据系统需要可直接接地或不接地运行，发电机中性点经二次侧接有电阻的单相变压器接地，髙厂变压器及启备变压器低压侧中性点经电阻接地，电阻为9.1Ω,400A,发电机次暂态电抗为16.01%。髙压启动\u002F备用变压器的中性点采用固定接地方式，主变压器中性点经隔离开关接地方式，髙压厂用变压器及启\u002F备变半穿越阻抗为21%，高压厂用变压器及髙压启动\u002F备用变压器均采用分裂绕组型变压器，髙压厂用电设两段公用段及脱硫段，分别由机组髙压厂用工作段供电。 关于电动机低电压保护，下列说法错误的是（）。",[383,385,387,389],{"key":20,"text":384,"correct":22},"I类电动机应装设9~1Os的低电压保护；",{"key":24,"text":386,"correct":22},"II类、III类电动机应装设0.5s的低电压保护；",{"key":28,"text":388,"correct":22},"I类电动机低电压保护的电压整定值应为额定电压的45%~50%；",{"key":31,"text":390,"correct":26},"II类、III类电动机低电压保护的电压整定值与I类电动机相同。",{"id":392,"libraryId":5,"type":15,"typeLabel":16,"stem":393,"options":394,"answer":20,"analysis":33},1023540,"某500kV变电站已知系统阻抗和变压器参数如图4所示，站址位于一块荒地上，围墙外面有水塘。 计算变压器标么值阻抗值为（）。",[395,397,399,401],{"key":20,"text":396,"correct":26},"X3=0.018,X4=0、X5=O.0407；",{"key":24,"text":398,"correct":22},"X3=O.01,X4=0.09,X5=0.407；",{"key":28,"text":400,"correct":22},"X3=O.03，X4=0.002.X5=O.0307；",{"key":31,"text":402,"correct":22},"X3=O.009、X4=0.01,X5=O.0207。",{"id":404,"libraryId":5,"type":15,"typeLabel":16,"stem":405,"options":406,"answer":24,"analysis":33},1023541,"某500kV变电站已知系统阻抗和变压器参数如图4所示，站址位于一块荒地上，围墙外面有水塘。 根据系统阻抗和变压器参数，220kV电压母线三相短路电流值应为（）。",[407,409,411,413],{"key":20,"text":408,"correct":22},"35.05kA；",{"key":24,"text":410,"correct":26},"33.05kA；",{"key":28,"text":412,"correct":22},"30.05kA；",{"key":31,"text":414,"correct":22},"27.05kA。",{"id":416,"libraryId":5,"type":15,"typeLabel":16,"stem":417,"options":418,"answer":24,"analysis":33},1023544,"某500kV变电站已知系统阻抗和变压器参数如图4所示，站址位于一块荒地上，围墙外面有水塘。 变电站接地网的接地电阻值应为（）。",[419,421,423,425],{"key":20,"text":420,"correct":22},"0.15Ω；",{"key":24,"text":422,"correct":26},"0.11Ω；",{"key":28,"text":424,"correct":22},"0.22Ω；",{"key":31,"text":426,"correct":22},"0.33Ω。",{"id":428,"libraryId":5,"type":15,"typeLabel":16,"stem":429,"options":430,"answer":20,"analysis":33},1023545,"某500kV变电站已知系统阻抗和变压器参数如图4所示，站址位于一块荒地上，围墙外面有水塘。 若变电站接地网的接地电阻实测值为0.5Ω，接地电阻值未达到0.11Ω目标要求值，需要采取措施降阻，试分析以下降阻措施可行的是（）。",[431,433,435,437],{"key":20,"text":432,"correct":26},"因为围墙外有水塘，可采用引外接地网；",{"key":24,"text":434,"correct":22},"扩大接地网面积到围墙外2m变电站的征地红线范围内",{"key":28,"text":436,"correct":22},"在地网中心地带设里深井接地极；",{"key":31,"text":438,"correct":22},"在地网内増加打入2.5m短垂直接地极。",{"id":440,"libraryId":5,"type":15,"typeLabel":16,"stem":441,"options":442,"answer":31,"analysis":33},1023546,"某500kV变电站已知系统阻抗和变压器参数如图4所示，站址位于一块荒地上，围墙外面有水塘。 本工程接地网设计，下面错误的是（）。",[443,445,447,449],{"key":20,"text":444,"correct":22},"采用不等同距网格接地网；",{"key":24,"text":446,"correct":22},"水平接地极实施全面换土；",{"key":28,"text":448,"correct":22},"在地网边缘的四角设置深井接地极；",{"key":31,"text":450,"correct":26},"在地网内增加打入2.5m短垂直接地极。",{"id":452,"libraryId":5,"type":15,"typeLabel":16,"stem":453,"options":454,"answer":28,"analysis":33},1023547,"某110kV变电站，位于城镇郊外，装设40MVA主变压器2台，三级电压为110kV\u002F35kV\u002F10kV；110kV出线2回，线路较长并穿过多雷山区，事故多发，线路无穿越功率；35kV出线6回；1OkV出线10回；各级电压短路电流水平为：110kV为25k A、35kV为20k A、1OkV为16kA；无功补偿电容器组装设于10kV，补偿容量按主变压器容量的20%,电网背景谐波为5次及以上。 根据特性和工程实践，各级电压适用的接线型式应为（）。",[455,457,459,461],{"key":20,"text":456,"correct":22},"110kV单母线\u002F35kV双母线\u002F1OkV单母线分段；",{"key":24,"text":458,"correct":22},"110kV单母线\u002F35kV单母线分段\u002F1OkV双母线；",{"key":28,"text":460,"correct":26},"110kV内桥接线\u002F35kV单母线分段\u002F1OkV单母线分段；",{"key":31,"text":462,"correct":22},"110kV外桥接线\u002F35kV单母线\u002F1OkV单母线分段。",{"id":464,"libraryId":5,"type":15,"typeLabel":16,"stem":465,"options":466,"answer":28,"analysis":33},1023548,"某110kV变电站，位于城镇郊外，装设40MVA主变压器2台，三级电压为110kV\u002F35kV\u002F10kV；110kV出线2回，线路较长并穿过多雷山区，事故多发，线路无穿越功率；35kV出线6回；1OkV出线10回；各级电压短路电流水平为：110kV为25k A、35kV为20k A、1OkV为16kA；无功补偿电容器组装设于10kV，补偿容量按主变压器容量的20%,电网背景谐波为5次及以上。 每台主变压器下10kV电容器组的容量为（）。",[467,469,471,473],{"key":20,"text":468,"correct":22},"1X6000kvar；",{"key":24,"text":470,"correct":22},"2X3000kvar；",{"key":28,"text":472,"correct":26},"2X4000kvar；",{"key":31,"text":474,"correct":22},"2X5000kvar。",{"id":476,"libraryId":5,"type":15,"typeLabel":16,"stem":477,"options":478,"answer":31,"analysis":33},1023549,"某110kV变电站，位于城镇郊外，装设40MVA主变压器2台，三级电压为110kV\u002F35kV\u002F10kV；110kV出线2回，线路较长并穿过多雷山区，事故多发，线路无穿越功率；35kV出线6回；1OkV出线10回；各级电压短路电流水平为：110kV为25k A、35kV为20k A、1OkV为16kA；无功补偿电容器组装设于10kV，补偿容量按主变压器容量的20%,电网背景谐波为5次及以上。 各级电压配电装置比较适用的型式为（）.",[479,481,483,485],{"key":20,"text":480,"correct":22},"110kV屋内GIS\u002F35kV屋外软母线\u002F1OkV屋内开关柜；",{"key":24,"text":482,"correct":22},"110kV屋外软母线中型\u002F35kV屋内管母线\u002F10kV屋内开关柜；",{"key":28,"text":484,"correct":22},"110kV屋外GIS\u002F35kV屋内开关柜\u002F10kV屋内开关柜；",{"key":31,"text":486,"correct":26},"110kV屋外软母线中型\u002F35kV屋内开关柜\u002F10kV屋内开关柜。",{"id":488,"libraryId":5,"type":15,"typeLabel":16,"stem":489,"options":490,"answer":31,"analysis":33},1023550,"某110kV变电站，位于城镇郊外，装设40MVA主变压器2台，三级电压为110kV\u002F35kV\u002F10kV；110kV出线2回，线路较长并穿过多雷山区，事故多发，线路无穿越功率；35kV出线6回；1OkV出线10回；各级电压短路电流水平为：110kV为25k A、35kV为20k A、1OkV为16kA；无功补偿电容器组装设于10kV，补偿容量按主变压器容量的20%,电网背景谐波为5次及以上。 电容器组的电抗率选择为（）。",[491,493,495,497],{"key":20,"text":492,"correct":22},"K=0.1%；",{"key":24,"text":494,"correct":22},"X=12%；",{"key":28,"text":496,"correct":22},"K=5%和12%；",{"key":31,"text":498,"correct":26},"K=5%。",{"id":500,"libraryId":5,"type":15,"typeLabel":16,"stem":501,"options":502,"answer":28,"analysis":33},1023551,"某110kV变电站，位于城镇郊外，装设40MVA主变压器2台，三级电压为110kV\u002F35kV\u002F10kV；110kV出线2回，线路较长并穿过多雷山区，事故多发，线路无穿越功率；35kV出线6回；1OkV出线10回；各级电压短路电流水平为：110kV为25k A、35kV为20k A、1OkV为16kA；无功补偿电容器组装设于10kV，补偿容量按主变压器容量的20%,电网背景谐波为5次及以上。 下面关于并联电容器装置设计的说明正确的是（）。",[503,505,507,509],{"key":20,"text":504,"correct":22},"电容器组应采用三角形接线；",{"key":24,"text":506,"correct":22},"由于并联电容器装置回路装设了串联电抗器，因此，电容器组电压比母线电压低；",{"key":28,"text":508,"correct":26},"电容器组的每相或每个桥臂，由多台电容器组舍连接时，应采用先并联后串联的接线方式；",{"key":31,"text":510,"correct":22},"并联电容器装置应设置重合闸装置，以保证跌闸后快速投入不间断无功供应。",{"id":512,"libraryId":5,"type":15,"typeLabel":16,"stem":513,"options":514,"answer":20,"analysis":33},1023552,"某110kV变电站，位于城镇郊外，装设40MVA主变压器2台，三级电压为110kV\u002F35kV\u002F10kV；110kV出线2回，线路较长并穿过多雷山区，事故多发，线路无穿越功率；35kV出线6回；1OkV出线10回；各级电压短路电流水平为：110kV为25k A、35kV为20k A、1OkV为16kA；无功补偿电容器组装设于10kV，补偿容量按主变压器容量的20%,电网背景谐波为5次及以上。 现有库存电容器，额定电压为11kV,额定容量334kvar，用于上述10kV电容器组时，下面设想正确的是（）。",[515,517,519,521],{"key":20,"text":516,"correct":26},"采用单星形接线，但输出容量要降低；",{"key":24,"text":518,"correct":22},"采用三角形接线，输出容量不会降低；",{"key":28,"text":520,"correct":22},"采用桥形接线；",{"key":31,"text":522,"correct":22},"采用单星形接线和相电压差动保护。",{"id":524,"libraryId":5,"type":15,"typeLabel":16,"stem":525,"options":526,"answer":28,"analysis":33},1023553,"某500kV变电站装设2组750MVA主变压器，三级电压为：500、220、35kV,站用负荷统计为：P1动力负荷536kW，其中包括深井水泵20kW、生活水泵5kW和消防泵80kW,P2空调和电热负荷1OOkW；P3照明负荷80kW。 站用变压器台数采用（ ）台。",[527,529,531,533],{"key":20,"text":528,"correct":22},"1；",{"key":24,"text":530,"correct":22},"2；",{"key":28,"text":532,"correct":26},"3；",{"key":31,"text":534,"correct":22},"4。",{"id":536,"libraryId":5,"type":15,"typeLabel":16,"stem":537,"options":538,"answer":24,"analysis":33},1023554,"某500kV变电站装设2组750MVA主变压器，三级电压为：500、220、35kV,站用负荷统计为：P1动力负荷536kW，其中包括深井水泵20kW、生活水泵5kW和消防泵80kW,P2空调和电热负荷1OOkW；P3照明负荷80kW。 站用变压器容量应为（）。",[539,541,543,545],{"key":20,"text":540,"correct":22},"800kVA；",{"key":24,"text":542,"correct":26},"630kVA；",{"key":28,"text":544,"correct":22},"500kVA；",{"key":31,"text":546,"correct":22},"1000kVA?",{"id":548,"libraryId":5,"type":15,"typeLabel":16,"stem":549,"options":550,"answer":24,"analysis":33},1023555,"某500kV变电站装设2组750MVA主变压器，三级电压为：500、220、35kV,站用负荷统计为：P1动力负荷536kW，其中包括深井水泵20kW、生活水泵5kW和消防泵80kW,P2空调和电热负荷1OOkW；P3照明负荷80kW。 下面关于站用电的说明正确的是（），",[551,553,555,557],{"key":20,"text":552,"correct":22},"为了保证站用电的可靠性，2台工作站用变压器应并联运行；",{"key":24,"text":554,"correct":26},"站用变压器的接线组别宜采用Dynll；",{"key":28,"text":556,"correct":22},"对重要站用负荷应分别接于两段母线上，单回路供电；",{"key":31,"text":558,"correct":22},"消防泵为重要负荷，在站用变容量选择时，统计负荷应计入动力负荷中。",{"id":560,"libraryId":5,"type":15,"typeLabel":16,"stem":561,"options":562,"answer":28,"analysis":33},1023556,"某500kV变电站装设2组750MVA主变压器，三级电压为：500、220、35kV,站用负荷统计为：P1动力负荷536kW，其中包括深井水泵20kW、生活水泵5kW和消防泵80kW,P2空调和电热负荷1OOkW；P3照明负荷80kW。 关于站用变型式和阻抗选择，下面说法中错误的是（）。",[563,565,567,569],{"key":20,"text":564,"correct":22},"站用电低压系统应采取防止变压器并联运行的措施；",{"key":24,"text":566,"correct":22},"站用变压器阻抗应按低压电器对短路电流的承受能力确定，宜采用标准系列的普通变压器。",{"key":28,"text":568,"correct":26},"站用变压器的联结组应采用Yynll；",{"key":31,"text":570,"correct":22},"当高压例电压波动大，经常使站用母线电压偏移超过5%时，应采用有载调压变压器。",{"id":572,"libraryId":5,"type":15,"typeLabel":16,"stem":573,"options":574,"answer":24,"analysis":33},1023557,"某220kV变电站位于III级污区，装设180MVA主变压器2台，220kV母线短路电流为12kA；220kV出线6回，全部为负荷线，其中最大输送容量为150MVA；如果220kV出线电流互感器的瓷套平均直径为450mm，试回答以下各题。 选择出线回路电流互感器变比和准确K值系数（）。 A.1000\u002F5A,10倍；",[575,577,579,581],{"key":20,"text":576,"correct":22},"600\u002F5",{"key":24,"text":578,"correct":26},"20倍；",{"key":28,"text":580,"correct":22},"800\u002F5A,15倍；",{"key":31,"text":582,"correct":22},"750\u002F5A,18倍。",{"id":584,"libraryId":5,"type":15,"typeLabel":16,"stem":585,"options":586,"answer":28,"analysis":33},1023558,"某220kV变电站位于III级污区，装设180MVA主变压器2台，220kV母线短路电流为12kA；220kV出线6回，全部为负荷线，其中最大输送容量为150MVA；如果220kV出线电流互感器的瓷套平均直径为450mm，试回答以下各题。 电流互感器瓷套的爬电距离应为（）。",[587,589,591,593],{"key":20,"text":588,"correct":22},"6300mm；",{"key":24,"text":590,"correct":22},"5500mm；",{"key":28,"text":592,"correct":26},"6930mm；",{"key":31,"text":594,"correct":22},"4510mm。",{"id":596,"libraryId":5,"type":15,"typeLabel":16,"stem":597,"options":598,"answer":28,"analysis":33},1023559,"某220kV变电站位于III级污区，装设180MVA主变压器2台，220kV母线短路电流为12kA；220kV出线6回，全部为负荷线，其中最大输送容量为150MVA；如果220kV出线电流互感器的瓷套平均直径为450mm，试回答以下各题。 下面关于变电站电气设备绝缘配合的说明正确的是（）。",[599,601,603,605],{"key":20,"text":600,"correct":22},"各种电压的断路器，同极断口间灭弧室瓷套的爬电比距不应小于对地爬电比距要求值的1.1倍；",{"key":24,"text":602,"correct":22},"变电站电气设备应能承受一定幅值和时间的工频过电压和请抵过电压；",{"key":28,"text":604,"correct":26},"断路器和隔离开关的截波額定雷电冲击耐压应为全波顧定雷电冲击耐压的1.1倍；",{"key":31,"text":606,"correct":22},"变压器内、外绝缘的全波額定雷电冲击耐压与变电站避雷器标称放电电流下的残压间的配合系数取1.3。",{"id":608,"libraryId":5,"type":15,"typeLabel":16,"stem":609,"options":610,"answer":31,"analysis":33},1023560,"某220kV变电站位于III级污区，装设180MVA主变压器2台，220kV母线短路电流为12kA；220kV出线6回，全部为负荷线，其中最大输送容量为150MVA；如果220kV出线电流互感器的瓷套平均直径为450mm，试回答以下各题。 220kV母线载流量是（）。",[611,613,615,617],{"key":20,"text":612,"correct":22},"800A；",{"key":24,"text":614,"correct":22},"700A；",{"key":28,"text":616,"correct":22},"300A；",{"key":31,"text":618,"correct":26},"500A。",[620,623,626,629,632,635],{"id":15,"name":621,"category":7,"favorite":622},"领导干部任职前廉政法规知识测试题",92,{"id":624,"name":625,"category":7,"favorite":15},595,"建筑结构与设备",{"id":627,"name":628,"category":7,"favorite":15},715,"招标采购专业知识与法律法规",{"id":630,"name":631,"category":7,"favorite":15},848,"市政方向-通用基础",{"id":633,"name":634,"category":7,"favorite":8},534,"BIM工程师",{"id":636,"name":634,"category":7,"favorite":8},535]