[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"lib-751-23":3},{"library":4,"page":9,"limit":10,"total":11,"questions":12,"related":597},{"id":5,"name":6,"category":7,"favorite":8},751,"电气工程师发输变电专业","建筑工程",0,23,50,2670,[13,34,46,58,70,78,90,98,110,118,130,142,154,166,178,190,202,214,226,238,250,262,274,284,294,306,318,330,342,354,366,377,389,401,413,424,434,444,453,465,477,489,501,513,525,537,549,561,573,585],{"id":14,"libraryId":5,"type":15,"typeLabel":16,"stem":17,"options":18,"answer":24,"analysis":33},1022854,1,"单选题","某工程网络控制室110V直流系统，设计采用51只GFM2型阀控铅酸蓄电池，事故 放电末期电压确定为1.83V，在此电压下蓄电池组的容量系数为0. 555。直流系统负荷统计 如下：经常电流53.2A,事故放电初期（0~1min)电流184.6 A，事故持续放电(1~60min)电流184.6 A，断路器采用弹簧操动机构，无事故冲击放电。蓄电池组在1.83V终 止电压下，电流比例系数为2. 342。已知蓄电池组在0. 3C10。下放电1h的单体蓄电池电压为 2. 02V,在0. 4 C10下放电1h的单体蓄电池电压为1. 955V,在0. 5C10。下放电1h的单体蓄电 池电压为1. 90V。另外请根据上述已知条件回答下列问题。 最严重放电情况下，蓄电池组电压计算值为（）。",[19,23,27,30],{"key":20,"text":21,"correct":22},"A","103.02V；",false,{"key":24,"text":25,"correct":26},"B","99.71V；",true,{"key":28,"text":29,"correct":22},"C","96.9V；",{"key":31,"text":32,"correct":22},"D","93.5V。","",{"id":35,"libraryId":5,"type":15,"typeLabel":16,"stem":36,"options":37,"answer":31,"analysis":33},1022855,"某工程110V控制负荷直流系统选用无端电池的500Ah铅酸蓄电池组，该工程事故初期(1min)放电电流为184.6A,蓄电池组在1.83V放电终止电压下放电1h的容量系数为0.656，蓄电池组至直流主屏的距离为50m，请根据上述数据回答下列问题。 蓄电池组至直流的允许压降为()。",[38,40,42,44],{"key":20,"text":39,"correct":22},"5.5V；",{"key":24,"text":41,"correct":22},"2.75V；",{"key":28,"text":43,"correct":22},"2.2V；",{"key":31,"text":45,"correct":26},"1.1V。",{"id":47,"libraryId":5,"type":15,"typeLabel":16,"stem":48,"options":49,"answer":24,"analysis":33},1022856,"某工程110V控制负荷直流系统选用无端电池的500Ah铅酸蓄电池组，该工程事故初期(1min)放电电流为184.6A,蓄电池组在1.83V放电终止电压下放电1h的容量系数为0.656，蓄电池组至直流主屏的距离为50m，请根据上述数据回答下列问题。 蓄电池组在1. 83V放电终止电压下放电1h的平均放电电流为（）。",[50,52,54,56],{"key":20,"text":51,"correct":22},"500A；",{"key":24,"text":53,"correct":26},"328A；",{"key":28,"text":55,"correct":22},"184.6A；",{"key":31,"text":57,"correct":22},"50A。",{"id":59,"libraryId":5,"type":15,"typeLabel":16,"stem":60,"options":61,"answer":20,"analysis":33},1022857,"某工程110V控制负荷直流系统选用无端电池的500Ah铅酸蓄电池组，该工程事故初期(1min)放电电流为184.6A,蓄电池组在1.83V放电终止电压下放电1h的容量系数为0.656，蓄电池组至直流主屏的距离为50m，请根据上述数据回答下列问题。 蓄电池组至直流主屏电缆的计算截面面积为（）。",[62,64,66,68],{"key":20,"text":63,"correct":26},"548.6mm2；",{"key":24,"text":65,"correct":22},"308.8mm2；",{"key":28,"text":67,"correct":22},"274.3mm2；",{"key":31,"text":69,"correct":22},"154.4mm2。",{"id":71,"libraryId":5,"type":15,"typeLabel":16,"stem":72,"options":73,"answer":31,"analysis":33},1022858,"110V直流系统的主屏至分屏距离为150m，最大负荷电流80 A，请回答下列问题。 直流主屏至分屏允许的最大压降为（）",[74,75,76,77],{"key":20,"text":39,"correct":22},{"key":24,"text":41,"correct":22},{"key":28,"text":43,"correct":22},{"key":31,"text":45,"correct":26},{"id":79,"libraryId":5,"type":15,"typeLabel":16,"stem":80,"options":81,"answer":31,"analysis":33},1022859,"110V直流系统的主屏至分屏距离为150m，最大负荷电流80 A，请回答下列问题。 直流主屏至直流分屏电缆的计算截面面积为（）。",[82,84,86,88],{"key":20,"text":83,"correct":22},"80mm2；",{"key":24,"text":85,"correct":22},"160mm2；",{"key":28,"text":87,"correct":22},"200mm2；",{"key":31,"text":89,"correct":26},"501mm2。",{"id":91,"libraryId":5,"type":15,"typeLabel":16,"stem":92,"options":93,"answer":20,"analysis":33},1022860,"110V直流系统的分屏至其中一回控制负荷的距离为50m，负荷电流为10 A，请回答下列问题。 分屏至该控制负荷的允许压降为（）。",[94,95,96,97],{"key":20,"text":39,"correct":26},{"key":24,"text":41,"correct":22},{"key":28,"text":43,"correct":22},{"key":31,"text":45,"correct":22},{"id":99,"libraryId":5,"type":15,"typeLabel":16,"stem":100,"options":101,"answer":20,"analysis":33},1022861,"110V直流系统的分屏至其中一回控制负荷的距离为50m，负荷电流为10 A，请回答下列问题。 分屏至该控制负荷的直流电缆截面计算面积为（）。",[102,104,106,108],{"key":20,"text":103,"correct":26},"3.3mm2；",{"key":24,"text":105,"correct":22},"6.7mm2；",{"key":28,"text":107,"correct":22},"8.4mm2；",{"key":31,"text":109,"correct":22},"16.7mm2。",{"id":111,"libraryId":5,"type":15,"typeLabel":16,"stem":112,"options":113,"answer":24,"analysis":33},1022862,"断路器110V直流电磁操动机构额定合闸电流为80 A，距离110V直流配电屏100m,请回答下列问题。 直流配电屏至该断路器的直流电缆允许压降为（）。",[114,115,116,117],{"key":20,"text":39,"correct":22},{"key":24,"text":41,"correct":26},{"key":28,"text":43,"correct":22},{"key":31,"text":45,"correct":22},{"id":119,"libraryId":5,"type":15,"typeLabel":16,"stem":120,"options":121,"answer":24,"analysis":33},1022863,"断路器110V直流电磁操动机构额定合闸电流为80 A，距离110V直流配电屏100m,请回答下列问题。 直流配电屏至该断路器的直流电缆截面面积计算值为（）。",[122,124,126,128],{"key":20,"text":123,"correct":22},"53.5mm2；",{"key":24,"text":125,"correct":26},"107.1mm2；",{"key":28,"text":127,"correct":22},"133.8mm2；",{"key":31,"text":129,"correct":22},"267.6mm2。",{"id":131,"libraryId":5,"type":15,"typeLabel":16,"stem":132,"options":133,"answer":31,"analysis":33},1022864,"断路器110V直流电磁操动机构额定合闸电流为80 A，距离110V直流配电屏100m,请回答下列问题。 若该回路采用熔断器作为保护，请问熔断器熔件的额定电流计算值为()。",[134,136,138,140],{"key":20,"text":135,"correct":22},"10OA；",{"key":24,"text":137,"correct":22},"80A；",{"key":28,"text":139,"correct":22},"40A；",{"key":31,"text":141,"correct":26},"16~24A。",{"id":143,"libraryId":5,"type":15,"typeLabel":16,"stem":144,"options":145,"answer":24,"analysis":33},1022866,"某工程单元控制室采用控制和动力直流系统分设的方式，动力采用无端电池220V直流系统，蓄电池浮充电压为2.25V，请回答下列问题。 事故放电末期单体蓄电池电压选择为()。",[146,148,150,152],{"key":20,"text":147,"correct":22},"1.90V；",{"key":24,"text":149,"correct":26},"1.87V；",{"key":28,"text":151,"correct":22},"1.85V；",{"key":31,"text":153,"correct":22},"1.80V。",{"id":155,"libraryId":5,"type":15,"typeLabel":16,"stem":156,"options":157,"answer":20,"analysis":33},1022867,"某工程单元控制室采用控制和动力直流系统分设的方式，动力采用无端电池220V直流系统，蓄电池浮充电压为2.25V，请回答下列问题。 直流系统母线允许最高电压选择为（）。",[158,160,162,164],{"key":20,"text":159,"correct":26},"247.5V,",{"key":24,"text":161,"correct":22},"242V；",{"key":28,"text":163,"correct":22},"231V；",{"key":31,"text":165,"correct":22},"220V。",{"id":167,"libraryId":5,"type":15,"typeLabel":16,"stem":168,"options":169,"answer":20,"analysis":33},1022868,"某工程单元控制室采用控制和动力直流系统分设的方式，动力采用无端电池220V直流系统，蓄电池浮充电压为2.25V，请回答下列问题。",[170,172,174,176],{"key":20,"text":171,"correct":26},"蓄电池组均衡充电时单体电池最高允许电压计算值为（）。",{"key":24,"text":173,"correct":22},"2.40V；",{"key":28,"text":175,"correct":22},"2.35V； C2.33V；",{"key":31,"text":177,"correct":22},"2.30V。",{"id":179,"libraryId":5,"type":15,"typeLabel":16,"stem":180,"options":181,"answer":28,"analysis":33},1022869,"某工程单元控制室采用控制和动力直流系统分设的方式，动力采用关端电池220V直流系统，蓄电池浮充电压为2.25V,该工程直流负荷统计如下： (1) O~1min放电电流为767.6A； (2) 1~60min放电电流为431.5A； (3) 60~90min放电电流为417.2A； (4) 90~180min放电电流为174.2A； (5) 180~480min放电电流为116.1A。 请根据上述参数回答下列问题。 蓄电池组0~1min的容量换算系数为0.867，请问第一阶段蓄电池组的计算容量为（）。",[182,184,186,188],{"key":20,"text":183,"correct":22},"1500Ah；",{"key":24,"text":185,"correct":22},"1440Ah；",{"key":28,"text":187,"correct":26},"1240Ah；",{"key":31,"text":189,"correct":22},"1200Ah.",{"id":191,"libraryId":5,"type":15,"typeLabel":16,"stem":192,"options":193,"answer":24,"analysis":33},1022870,"某工程单元控制室采用控制和动力直流系统分设的方式，动力采用关端电池220V直流系统，蓄电池浮充电压为2.25V,该工程直流负荷统计如下： (1) O~1min放电电流为767.6A； (2) 1~60min放电电流为431.5A； (3) 60~90min放电电流为417.2A； (4) 90~180min放电电流为174.2A； (5) 180~480min放电电流为116.1A。 请根据上述参数回答下列问题。 蓄电池组59min、60miri的容量换算系数分别为0. 415、0.410,请问第二阶段蓄电池组的计算容量为（）。",[194,196,198,200],{"key":20,"text":195,"correct":22},"2621Ah；",{"key":24,"text":197,"correct":26},"1487Ah；",{"key":28,"text":199,"correct":22},"1134Ah；",{"key":31,"text":201,"correct":22},"1034Ah。",{"id":203,"libraryId":5,"type":15,"typeLabel":16,"stem":204,"options":205,"answer":24,"analysis":33},1022871,"某工程单元控制室采用控制和动力直流系统分设的方式，动力采用关端电池220V直流系统，蓄电池浮充电压为2.25V,该工程直流负荷统计如下： (1) O~1min放电电流为767.6A； (2) 1~60min放电电流为431.5A； (3) 60~90min放电电流为417.2A； (4) 90~180min放电电流为174.2A； (5) 180~480min放电电流为116.1A。 请根据上述参数回答下列问题。 蓄电池组30、89, 90min的容量换算系数分别为0.578、0.338、0.326,请问第三阶段蓄电池组的计算容量为（）。",[206,208,210,212],{"key":20,"text":207,"correct":22},"3297Ah；",{"key":24,"text":209,"correct":26},"1870Ah；",{"key":28,"text":211,"correct":22},"1392Ah；",{"key":31,"text":213,"correct":22},"35Ah。",{"id":215,"libraryId":5,"type":15,"typeLabel":16,"stem":216,"options":217,"answer":28,"analysis":33},1022872,"选择某水电厂厂用电变压器容量。 已知条件：1)选用三台厂用电变压器互为备用； 2)所有同时参加最大负荷运行时，负荷的额定功率总和为1233. 73kW； 3)厂用电负荷的综合系数取0.75。 厂用电变压器容量选（）（还须校验自启动时母线电压应满足规范要求)。",[218,220,222,224],{"key":20,"text":219,"correct":22},"315kVA；",{"key":24,"text":221,"correct":22},"400kVA；",{"key":28,"text":223,"correct":26},"500kVA；",{"key":31,"text":225,"correct":22},"600kVA,",{"id":227,"libraryId":5,"type":15,"typeLabel":16,"stem":228,"options":229,"answer":24,"analysis":33},1022873,"某中型水电厂，大坝距厂房约10km,有关坝区供电请回答（主接线为两个扩大单元接线）。 变电所两个电源（）。",[230,232,234,236],{"key":20,"text":231,"correct":22},"从两段电机电压母线上分别引出，架两回10kV架空线；",{"key":24,"text":233,"correct":26},"从一段发电机电压母线上引出，架一回10kV架空线；从地区电网接一回10kV线路；",{"key":28,"text":235,"correct":22},"从地区电网接一回10kV线路，装设一台柴油发电机组；",{"key":31,"text":237,"correct":22},"从一段发电机电压母线上引出，架一回10kV架空线，装设一台柴油发电机組，",{"id":239,"libraryId":5,"type":15,"typeLabel":16,"stem":240,"options":241,"answer":31,"analysis":33},1022874,"某中型水电厂，大坝距厂房约10km,有关坝区供电请回答（主接线为两个扩大单元接线）。 若电源选择“B”方案，变电所10kV宜采用（）接线。",[242,244,246,248],{"key":20,"text":243,"correct":22},"单母线分段；",{"key":24,"text":245,"correct":22},"单母线；",{"key":28,"text":247,"correct":22},"桥形接线；",{"key":31,"text":249,"correct":26},"在每台变压器高压侧装跌开式熔断器。",{"id":251,"libraryId":5,"type":15,"typeLabel":16,"stem":252,"options":253,"answer":24,"analysis":33},1022875,"某中型水电厂，大坝距厂房约10km,有关坝区供电请回答（主接线为两个扩大单元接线）。 已知：现区同时参加最大负荷运行时，负荷额定功率总和为251. 3kW,负荷综合系数取0.76。变电所变压器容量选（）。",[254,256,258,260],{"key":20,"text":255,"correct":22},"160VA?",{"key":24,"text":257,"correct":26},"200kVA5",{"key":28,"text":259,"correct":22},"250kVA；",{"key":31,"text":261,"correct":22},"315VA。",{"id":263,"libraryId":5,"type":15,"typeLabel":16,"stem":264,"options":265,"answer":20,"analysis":33},1022876,"计算某水电厂髙压厂用电系统短路电流（短路点为厂用电变压器二次侧出口）。已知：①电厂采用发电机一变压器单元接线，厂用电变压器接于机端、容量2000kVA,阻抗值为5%，二次侧电压10.5kV；②同时运行的高压电动机总容量小于1500kW。 高压厂用电系统短路电流计算原则，不妥的是（）。",[266,268,270,272],{"key":20,"text":267,"correct":26},"计算断路器开断时的直流分量和短路冲击电流；",{"key":24,"text":269,"correct":22},"同时运行的髙压电动机总容量不大于1500kW时，可不计电动机的反馈电流；",{"key":28,"text":271,"correct":22},"由机端或升高电压侧引接的电源，系统阻抗可忽略；",{"key":31,"text":273,"correct":22},"由地区电网引接的电源要计系统阻抗。",{"id":275,"libraryId":5,"type":15,"typeLabel":16,"stem":276,"options":277,"answer":24,"analysis":33},1022877,"计算某水电厂髙压厂用电系统短路电流（短路点为厂用电变压器二次侧出口）。已知：①电厂采用发电机一变压器单元接线，厂用电变压器接于机端、容量2000kVA,阻抗值为5%，二次侧电压10.5kV；②同时运行的高压电动机总容量小于1500kW。 短路点短路电流周期分量广为（）。 A.2.3kA；",[278,280,282],{"key":20,"text":279,"correct":22},"2.2kA；",{"key":24,"text":281,"correct":26},"2.1kA；",{"key":28,"text":283,"correct":22},"2.Ok",{"id":285,"libraryId":5,"type":15,"typeLabel":16,"stem":286,"options":287,"answer":28,"analysis":33},1022878,"计算某水电厂髙压厂用电系统短路电流（短路点为厂用电变压器二次侧出口）。已知：①电厂采用发电机一变压器单元接线，厂用电变压器接于机端、容量2000kVA,阻抗值为5%，二次侧电压10.5kV；②同时运行的高压电动机总容量小于1500kW。 短路点短路冲击电流ich为（）。 A.5.9kA；",[288,290,292],{"key":20,"text":289,"correct":22},"5.7kA；",{"key":24,"text":291,"correct":22},"5.5kA；",{"key":28,"text":293,"correct":26},"5.3k",{"id":295,"libraryId":5,"type":15,"typeLabel":16,"stem":296,"options":297,"answer":31,"analysis":33},1022879,"某水电厂髙压厂用电系统采用10kV级电压和单母线分段接线，有关配电装置应如何考虑。 配电装置宜选用的型式是（)。",[298,300,302,304],{"key":20,"text":299,"correct":22},"装配式；",{"key":24,"text":301,"correct":22},"开启式固定开关柜；",{"key":28,"text":303,"correct":22},"箱型固定开关柜；",{"key":31,"text":305,"correct":26},"手车式（或中置式）开关柜。",{"id":307,"libraryId":5,"type":15,"typeLabel":16,"stem":308,"options":309,"answer":24,"analysis":33},1022880,"某水电厂髙压厂用电系统采用10kV级电压和单母线分段接线，有关配电装置应如何考虑。 宜选用断路器的类型为（）。",[310,312,314,316],{"key":20,"text":311,"correct":22},"少油断路器；",{"key":24,"text":313,"correct":26},"真空断路器；",{"key":28,"text":315,"correct":22},"SF6断路器；",{"key":31,"text":317,"correct":22},"电磁式空气断路器。",{"id":319,"libraryId":5,"type":15,"typeLabel":16,"stem":320,"options":321,"answer":31,"analysis":33},1022881,"某水电厂髙压厂用电系统采用10kV级电压和单母线分段接线，有关配电装置应如何考虑。 下列不属于开关柜应具有的防误功能的有（）。",[322,324,326,328],{"key":20,"text":323,"correct":22},"防止谈分合断路器；",{"key":24,"text":325,"correct":22},"防止带负荷分离隔离开关；",{"key":28,"text":327,"correct":22},"防止接地开关合上时送电；",{"key":31,"text":329,"correct":26},"防止影响设备安全运行的大量尘埃进入。",{"id":331,"libraryId":5,"type":15,"typeLabel":16,"stem":332,"options":333,"answer":28,"analysis":33},1022882,"某水电厂髙压厂用电系统采用10kV级电压和单母线分段接线，有关配电装置应如何考虑。 开关柜防护等级分四类，其中IP3X的含义是（）。",[334,336,338,340],{"key":20,"text":335,"correct":22},"能阻挡直径或厚度大于3. 5mm的工具、金属丝等物体进入；",{"key":24,"text":337,"correct":22},"能阻挡直径或厚度大于3. Omm的工具、金属丝等物体进入；",{"key":28,"text":339,"correct":26},"能阻挡直径或厚度大于2. 5mm的工具、金属丝等物体进入；",{"key":31,"text":341,"correct":22},"能阻挡直径或厚度大于2. Omm的工具、金属丝等物祕进入。",{"id":343,"libraryId":5,"type":15,"typeLabel":16,"stem":344,"options":345,"answer":24,"analysis":33},1022883,"高压厂用电系统中断路器是一个重要元件，它的一些技术条件如下。 使用环境条件可不考虑的是（）。",[346,348,350,352],{"key":20,"text":347,"correct":22},"周围空气温度和湿度；",{"key":24,"text":349,"correct":26},"风速；",{"key":28,"text":351,"correct":22},"海拔高度；",{"key":31,"text":353,"correct":22},"爬电比距.",{"id":355,"libraryId":5,"type":15,"typeLabel":16,"stem":356,"options":357,"answer":28,"analysis":33},1022884,"高压厂用电系统中断路器是一个重要元件，它的一些技术条件如下。 当主保护动作时间与断路器固有分闸时间之和大于0.15s时，短路参数可不考虑的是（）。",[358,360,362,364],{"key":20,"text":359,"correct":22},"开断电流；",{"key":24,"text":361,"correct":22},"关合电流；",{"key":28,"text":363,"correct":26},"非周期分量；",{"key":31,"text":365,"correct":22},"热稳定电流。",{"id":367,"libraryId":5,"type":15,"typeLabel":16,"stem":368,"options":369,"answer":20,"analysis":33},1022885,"高压厂用电系统中断路器是一个重要元件，它的一些技术条件如下。 断路器在不同场所使用，可以不考虑降容的是（）。",[370,371,373,375],{"key":20,"text":299,"correct":26},{"key":24,"text":372,"correct":22},"手车式开关柜；",{"key":28,"text":374,"correct":22},"中里式开关柜；",{"key":31,"text":376,"correct":22},"箱型固定式升关柜。",{"id":378,"libraryId":5,"type":15,"typeLabel":16,"stem":379,"options":380,"answer":20,"analysis":33},1022886,"计算某水电厂低压厂用电系统短路电流。 不符合低压厂用电系统短路电流计算原则的是（）。",[381,383,385,387],{"key":20,"text":382,"correct":26},"仅计电抗不考虑电阻；",{"key":24,"text":384,"correct":22},"采用一级低压供电的厂用电变压器高压侧系统阻抗不计；",{"key":28,"text":386,"correct":22},"采用二级电压供电的系统，低压厂用电变压器高压側系统阻抗要计；",{"key":31,"text":388,"correct":22},"计算主屏母线短路电流时，20kW以上异步电动机的反馈电流要计。",{"id":390,"libraryId":5,"type":15,"typeLabel":16,"stem":391,"options":392,"answer":31,"analysis":33},1022887,"计算某水电厂低压厂用电系统短路电流。 厂用电主母线三相短路，由厂用电变压器供给的短路电流周期分量为（）。(每相回路总电阻和总电抗分别为2.98MΩ和14.96MΩ）",[393,395,397,399],{"key":20,"text":394,"correct":22},"14.02kA；",{"key":24,"text":396,"correct":22},"14.38kA；",{"key":28,"text":398,"correct":22},"14.82kA；",{"key":31,"text":400,"correct":26},"15.14kA。",{"id":402,"libraryId":5,"type":15,"typeLabel":16,"stem":403,"options":404,"answer":24,"analysis":33},1022888,"计算某水电厂低压厂用电系统短路电流。 同上，由厂用电变压器供给的短路冲击电流为（）。",[405,407,409,411],{"key":20,"text":406,"correct":22},"29.1kA；",{"key":24,"text":408,"correct":26},"32.97kA；",{"key":28,"text":410,"correct":22},"36.82kA；",{"key":31,"text":412,"correct":22},"40.68kA。",{"id":414,"libraryId":5,"type":15,"typeLabel":16,"stem":415,"options":416,"answer":20,"analysis":33},1022889,"对采用主盘和分盘二级供电的低压厂用电系统中，干线上和支线上的保护电器组合方式，以下4种都是可行的，为使保护电器有选择性动作，干线上保护电器应选择。 干线上和支线上均装熔断器，要求（）。 A.干线上熔断器这体額定电流较支线上熔断器熔体额定电流大一定级差； B.同 A，大二级级差；",[417,419,421,422],{"key":20,"text":418,"correct":26},"同",{"key":24,"text":420,"correct":22},"大一级级差；",{"key":28,"text":418,"correct":22},{"key":31,"text":423,"correct":22},"大三级级差。",{"id":425,"libraryId":5,"type":15,"typeLabel":16,"stem":426,"options":427,"answer":28,"analysis":33},1022890,"对采用主盘和分盘二级供电的低压厂用电系统中，干线上和支线上的保护电器组合方式，以下4种都是可行的，为使保护电器有选择性动作，干线上保护电器应选择。 干线上装熔断器，支线上装断路器，要求（）。 A.干线上熔断器这体額定电流较支线上断路器額定电流大一定级差；",[428,429,430,432],{"key":20,"text":418,"correct":22},{"key":24,"text":420,"correct":22},{"key":28,"text":431,"correct":26},"干线上熔断器熔体的熔断时间计入误差后，大于支线上断路器的分闸时间；",{"key":31,"text":433,"correct":22},"同A,大二级级差。",{"id":435,"libraryId":5,"type":15,"typeLabel":16,"stem":436,"options":437,"answer":28,"analysis":33},1022891,"对采用主盘和分盘二级供电的低压厂用电系统中，干线上和支线上的保护电器组合方式，以下4种都是可行的，为使保护电器有选择性动作，干线上保护电器应选择。 干线上装断路器，支线上装熔断器，要求（）。 A.干线上断路器額定电流较支线上熔断器熔体额定电流大一定级差； B.同",[438,439,441,442],{"key":20,"text":420,"correct":22},{"key":24,"text":440,"correct":22},"干线上装延时动作的断路器；",{"key":28,"text":418,"correct":26},{"key":31,"text":443,"correct":22},"大二級级差。",{"id":445,"libraryId":5,"type":15,"typeLabel":16,"stem":446,"options":447,"answer":20,"analysis":33},1022892,"对采用主盘和分盘二级供电的低压厂用电系统中，干线上和支线上的保护电器组合方式，以下4种都是可行的，为使保护电器有选择性动作，干线上保护电器应选择。 干线上支线上均装断要求（）。 A.干线上装延时动作的断路器； B.干线上断路器额定电流较支线上断路器额定电流大一定级差；",[448,449,450,451],{"key":20,"text":418,"correct":26},{"key":24,"text":420,"correct":22},{"key":28,"text":418,"correct":22},{"key":31,"text":452,"correct":22},"大二级级差。",{"id":454,"libraryId":5,"type":15,"typeLabel":16,"stem":455,"options":456,"answer":28,"analysis":33},1022893,"低压厂用电系统中，电器元件组合。 在重要的低压电动机回路中不装的电器为（）。",[457,459,461,463],{"key":20,"text":458,"correct":22},"隔离电器；",{"key":24,"text":460,"correct":22},"保护电器；",{"key":28,"text":462,"correct":26},"避雷器；",{"key":31,"text":464,"correct":22},"操作电器。",{"id":466,"libraryId":5,"type":15,"typeLabel":16,"stem":467,"options":468,"answer":31,"analysis":33},1022894,"低压厂用电系统中，电器元件组合。 以下电器不是隔离电器的有（）。",[469,471,473,475],{"key":20,"text":470,"correct":22},"插头；",{"key":24,"text":472,"correct":22},"刀开关；",{"key":28,"text":474,"correct":22},"组合开关；",{"key":31,"text":476,"correct":26},"熔断器。",{"id":478,"libraryId":5,"type":15,"typeLabel":16,"stem":479,"options":480,"answer":31,"analysis":33},1022895,"低压厂用电系统中，电器元件组合。 以下电器不是保护电器的有（）。",[481,483,485,487],{"key":20,"text":482,"correct":22},"断路器；",{"key":24,"text":484,"correct":22},"熔断器；",{"key":28,"text":486,"correct":22},"负荷开关；",{"key":31,"text":488,"correct":26},"组合开关，",{"id":490,"libraryId":5,"type":15,"typeLabel":16,"stem":491,"options":492,"answer":24,"analysis":33},1022896,"某水电厂调速器油压装置由主屏直接供电，电缆长180m，电动机功率37kW (计算电流70.2 A)。 电缆外护层型式选（）。",[493,495,497,499],{"key":20,"text":494,"correct":22},"聚氯乙烯护套；",{"key":24,"text":496,"correct":26},"聚氯乙烯护套钢带内铠装；",{"key":28,"text":498,"correct":22},"聚氯乙烯护套裸细钢丝铠装；",{"key":31,"text":500,"correct":22},"聚氯乙烯栌套裸粗钢丝铠装。",{"id":502,"libraryId":5,"type":15,"typeLabel":16,"stem":503,"options":504,"answer":24,"analysis":33},1022897,"某水电厂调速器油压装置由主屏直接供电，电缆长180m，电动机功率37kW (计算电流70.2 A)。 正常运行情况下，电动机允许电压降不宜超过（）。",[505,507,509,511],{"key":20,"text":506,"correct":22},"3%；",{"key":24,"text":508,"correct":26},"5%；",{"key":28,"text":510,"correct":22},"7%；",{"key":31,"text":512,"correct":22},"10%.",{"id":514,"libraryId":5,"type":15,"typeLabel":16,"stem":515,"options":516,"answer":24,"analysis":33},1022898,"某水电厂调速器油压装置由主屏直接供电，电缆长180m，电动机功率37kW (计算电流70.2 A)。 按电压损耗，该回路铜芯电缆截面选（）。",[517,519,521,523],{"key":20,"text":518,"correct":22},"3X16+1X6；",{"key":24,"text":520,"correct":26},"3X25+1X10；",{"key":28,"text":522,"correct":22},"3X35+1X10；",{"key":31,"text":524,"correct":22},"3X50+1X16。",{"id":526,"libraryId":5,"type":15,"typeLabel":16,"stem":527,"options":528,"answer":28,"analysis":33},1022899,"某水电厂取水口海拔高程3500m左右。 电动机额定功率（ ）。",[529,531,533,535],{"key":20,"text":530,"correct":22},"与常规使用一样，不修正；",{"key":24,"text":532,"correct":22},"一般认为温升随海拔增髙而递増，环境温度随海拔増高而递减，足以补偿因空气稀薄而造成的温度升高故不修正；",{"key":28,"text":534,"correct":26},"按规范计算确定；",{"key":31,"text":536,"correct":22},"电动机的允许极限工作温度每超过1℃,降低额定功率2%使用.",{"id":538,"libraryId":5,"type":15,"typeLabel":16,"stem":539,"options":540,"answer":20,"analysis":33},1022900,"某水电厂取水口海拔高程3500m左右。 若使用地点实际环境最髙温度t为18℃,电动机额定功率应（）。",[541,543,545,547],{"key":20,"text":542,"correct":26},"可按电动机的额定功率运行；",{"key":24,"text":544,"correct":22},"降低电动机的额定功率运行；",{"key":28,"text":546,"correct":22},"可适当提高电动机额定功率运行；",{"key":31,"text":548,"correct":22},"可降低箱定功率1%运行。",{"id":550,"libraryId":5,"type":15,"typeLabel":16,"stem":551,"options":552,"answer":24,"analysis":33},1022901,"某水电厂取水口海拔高程3500m左右。 同上，若t为22℃应（ ）。",[553,555,557,559],{"key":20,"text":554,"correct":22},"按电动机額定功率运行；",{"key":24,"text":556,"correct":26},"降低电动机额定功率运行；",{"key":28,"text":558,"correct":22},"适当提髙电动机额定功率运行；",{"key":31,"text":560,"correct":22},"可提高額定功率运行。",{"id":562,"libraryId":5,"type":15,"typeLabel":16,"stem":563,"options":564,"answer":28,"analysis":33},1022902,"某500kV变电所装设2组750MVA主变压器（由3台单相三绕组自耦变压器组成）各侧电压为525\u002F√3kV\u002F230\u002F√3±3X2.5%kV\u002F35kV,35kV侧接无功补偿装置，每台主变压器35kV无功补偿母线接1台厂用工作变压器，采用630kVA变压器，所用工作变压器35kV接入点电压波动达到辆定电压的±5%。 变压器的阻抗电压为（）。",[565,567,569,571],{"key":20,"text":566,"correct":22},"Ud=4%；",{"key":24,"text":568,"correct":22},"Ud=12%;",{"key":28,"text":570,"correct":26},"Ud=6.5%；",{"key":31,"text":572,"correct":22},"Ud=13%。",{"id":574,"libraryId":5,"type":15,"typeLabel":16,"stem":575,"options":576,"answer":20,"analysis":33},1022903,"某500kV变电所装设2组750MVA主变压器（由3台单相三绕组自耦变压器组成）各侧电压为525\u002F√3kV\u002F230\u002F√3±3X2.5%kV\u002F35kV,35kV侧接无功补偿装置，每台主变压器35kV无功补偿母线接1台厂用工作变压器，采用630kVA变压器，所用工作变压器35kV接入点电压波动达到辆定电压的±5%。 变压器的电压调整方式，范围和级电压为（）。",[577,579,581,583],{"key":20,"text":578,"correct":26},"35±2X2.5%\u002F0.4kV无励磁调压变压器；",{"key":24,"text":580,"correct":22},"35±3X2.5%\u002F0.4kV有载调压变压器；",{"key":28,"text":582,"correct":22},"35±8X1.25%\u002F0.4kV有载调压变压器；",{"key":31,"text":584,"correct":22},"35±2X5%\u002F0.4kV无励磁调压变压器。",{"id":586,"libraryId":5,"type":15,"typeLabel":16,"stem":587,"options":588,"answer":24,"analysis":33},1022904,"某500kV变电所装设2组750MVA主变压器（由3台单相三绕组自耦变压器组成）各侧电压为525\u002F√3kV\u002F230\u002F√3±3X2.5%kV\u002F35kV,35kV侧接无功补偿装置，每台主变压器35kV无功补偿母线接1台厂用工作变压器，采用630kVA变压器，所用工作变压器35kV接入点电压波动达到辆定电压的±5%。 所用变压器的接线组别宜采用何种方式？",[589,591,593,595],{"key":20,"text":590,"correct":22},"Dyn11联结组；",{"key":24,"text":592,"correct":26},"Ynd11联结組；",{"key":28,"text":594,"correct":22},"DdO联结组；",{"key":31,"text":596,"correct":22},"YnyO联结组。",[598,601,604,607,610,613],{"id":15,"name":599,"category":7,"favorite":600},"领导干部任职前廉政法规知识测试题",92,{"id":602,"name":603,"category":7,"favorite":15},595,"建筑结构与设备",{"id":605,"name":606,"category":7,"favorite":15},715,"招标采购专业知识与法律法规",{"id":608,"name":609,"category":7,"favorite":15},848,"市政方向-通用基础",{"id":611,"name":612,"category":7,"favorite":8},534,"BIM工程师",{"id":614,"name":612,"category":7,"favorite":8},535]