[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"lib-751-21":3},{"library":4,"page":9,"limit":10,"total":11,"questions":12,"related":608},{"id":5,"name":6,"category":7,"favorite":8},751,"电气工程师发输变电专业","建筑工程",0,21,50,2670,[13,34,42,52,62,74,86,98,110,122,134,146,158,169,181,193,205,217,229,241,253,265,277,289,301,313,325,333,345,357,369,381,393,404,416,428,440,452,464,476,488,500,512,524,536,548,560,572,584,596],{"id":14,"libraryId":5,"type":15,"typeLabel":16,"stem":17,"options":18,"answer":27,"analysis":33},1022754,1,"单选题","某工程600MW发电机差动保护TA变比为25000\u002F5 A，5P20,差动保护采用比率制动式，发电机定子线电压为22kV，额定电流15746 A，发电机端的最大外部短路电流为224k A，请根据上述已知条件回答下列问题。 差动保护的最小动作电流为（）。",[19,23,26,30],{"key":20,"text":21,"correct":22},"A","3.15A；",false,{"key":24,"text":25,"correct":22},"B","1.56A；",{"key":27,"text":28,"correct":29},"C","0.63A；",true,{"key":31,"text":32,"correct":22},"D","0.16A,","",{"id":35,"libraryId":5,"type":15,"typeLabel":16,"stem":36,"options":37,"answer":20,"analysis":33},1022755,"某工程600MW发电机差动保护TA变比为25000\u002F5 A，5P20,差动保护采用比率制动式，发电机定子线电压为22kV，额定电流15746 A，发电机端的最大外部短路电流为224k A，请根据上述已知条件回答下列问题。 制动特性曲线在拐点处的制动电流为（）。 A.3.15A；",[38,39,40],{"key":20,"text":25,"correct":29},{"key":24,"text":28,"correct":22},{"key":27,"text":41,"correct":22},"0.16",{"id":43,"libraryId":5,"type":15,"typeLabel":16,"stem":44,"options":45,"answer":33,"analysis":33},1022756,"某工程600MW发电机差动保护TA变比为25000\u002F5 A，5P20,差动保护采用比率制动式，发电机定子线电压为22kV，额定电流15746 A，发电机端的最大外部短路电流为224k A，请根据上述已知条件回答下列问题。 在最大外部短路电流时差动保护不误动的条件下所对应的差动保护最大动作电流为（）。 A.22A；",[46,48,50],{"key":20,"text":47,"correct":22},"11A；",{"key":24,"text":49,"correct":22},"5.5A；",{"key":27,"text":51,"correct":22},"2.2",{"id":53,"libraryId":5,"type":15,"typeLabel":16,"stem":54,"options":55,"answer":20,"analysis":33},1022757,"某工程600MW发电机差动保护TA变比为25000\u002F5 A，5P20,差动保护采用比率制动式，发电机定子线电压为22kV，额定电流15746 A，发电机端的最大外部短路电流为224k A，请根据上述已知条件回答下列问题。 与上题差动保护最大动作电流相对应的最大制动电流为（）。",[56,58,59,60],{"key":20,"text":57,"correct":29},"44.8A；",{"key":24,"text":47,"correct":22},{"key":27,"text":49,"correct":22},{"key":31,"text":61,"correct":22},"2.2A。",{"id":63,"libraryId":5,"type":15,"typeLabel":16,"stem":64,"options":65,"answer":31,"analysis":33},1022758,"对发电机外部相间短路故障和作为发电机主保护的后备，当发电机容量为50MW及以上时，可装设负序过电流保护和单元件低压启动过电流保护. 负序电流元件的动作电流可取（）。",[66,68,70,72],{"key":20,"text":67,"correct":22},"发电机额定电流的0.1~0.2倍；",{"key":24,"text":69,"correct":22},"发电机額定电流的0.3~0.4倍；",{"key":27,"text":71,"correct":22},"发电机额定电流的0.4~0.5倍；",{"key":31,"text":73,"correct":29},"发电机额定电流的0.5~0.6倍。",{"id":75,"libraryId":5,"type":15,"typeLabel":16,"stem":76,"options":77,"answer":20,"analysis":33},1022759,"对发电机外部相间短路故障和作为发电机主保护的后备，当发电机容量为50MW及以上时，可装设负序过电流保护和单元件低压启动过电流保护. 对于单相过电流元件的整定，正确的说法是（）。",[78,80,82,84],{"key":20,"text":79,"correct":29},"动作电流按发电机额定负荷下可靠返回的条件整定，可靠系数取1.3~1.5，返回系数取0.85~0.95；",{"key":24,"text":81,"correct":22},"动作电流按发电机額定负荷下可靠返闻的条件整定，可靠系数取1.5~2.0，返闻系数取0.7~0.8；",{"key":27,"text":83,"correct":22},"C灵敏系数按主变压器高压侧母线金属性两相短路时流过保护的最小短路电流效验，灵敏系数要求大于2.0；",{"key":31,"text":85,"correct":22},"灵敏系数按主变压器高压侧母线金属性三相短路时流过保护的最小短路电流效验，灵敏系数要求大于2.0。",{"id":87,"libraryId":5,"type":15,"typeLabel":16,"stem":88,"options":89,"answer":31,"analysis":33},1022760,"对发电机外部相间短路故障和作为发电机主保护的后备，当发电机容量为50MW及以上时，可装设负序过电流保护和单元件低压启动过电流保护. 对于低电压元件的整定，正确的说法是（）。",[90,92,94,96],{"key":20,"text":91,"correct":22},"低电压元件接相电压；",{"key":24,"text":93,"correct":22},"对汽轮发电机，动作电压为发电机額定电压的0.8倍；",{"key":27,"text":95,"correct":22},"灵敏系数按主变压器高压侧母线二相金属性短路的条件效猃；",{"key":31,"text":97,"correct":29},"灵敏系数应不小于1.2。",{"id":99,"libraryId":5,"type":15,"typeLabel":16,"stem":100,"options":101,"answer":20,"analysis":33},1022761,"对于定子绕组单相接地故障保护，请回答下列问题. 对于基波零序过电压保护，正确的说法是（）。",[102,104,106,108],{"key":20,"text":103,"correct":29},"动作电压按躲过正常运行时中性点单相电压互感器或机端电压互感器开口三角绕组的最大不平衡电压整定；",{"key":24,"text":105,"correct":22},"保护无死区；",{"key":27,"text":107,"correct":22},"为保证保护的灵敏度，不应设置三次谁波阻波环节；",{"key":31,"text":109,"correct":22},"动作电压整定时，可靠系数取2.0.",{"id":111,"libraryId":5,"type":15,"typeLabel":16,"stem":112,"options":113,"answer":27,"analysis":33},1022762,"对于定子绕组单相接地故障保护，请回答下列问题. 对于三次谐波电压单相接地保护，不正确的说法是（）。",[114,116,118,120],{"key":20,"text":115,"correct":22},"三次谐波分别取自机蝻和中性点侧TV(或配电变压器二次侧）；",{"key":24,"text":117,"correct":22},"该保护与基波零序电压保护一起可构成100%定子绕组单相接地故障保护;",{"key":27,"text":119,"correct":29},"都保护动作于延时停机；",{"key":31,"text":121,"correct":22},"如发电机中性点经配电变压器或消弧线B接地，保护装里应具有调平衡功能，否则应增设中间电压互感器。",{"id":123,"libraryId":5,"type":15,"typeLabel":16,"stem":124,"options":125,"answer":20,"analysis":33},1022763,"某工程600MW发电机保护TA变比为25000\u002F5A, 5P20,发电机定子线电压为22kV,额定电流15746A,发电机次暂态电抗X\"d=18.26%，请根据上述已知条件回答下列有关定子绕组过负荷保护问题。 对定子绕组过负荷保护，下列说法正确的是（）。",[126,128,130,132],{"key":20,"text":127,"correct":29},"定子绕组过负荷保护由定时限过负荷保护和反时限过电流保护组成；",{"key":24,"text":129,"correct":22},"定子绕组过负荷保护由定时限过负荷保护和过电流速断保护组成；",{"key":27,"text":131,"correct":22},"定时先负荷保护动作于信号或自动减负荷，反时限过电流保护动作于停机；",{"key":31,"text":133,"correct":22},"定时限过负荷保护动作于信号或自动减负荷，过电流速断保护动作于停机。",{"id":135,"libraryId":5,"type":15,"typeLabel":16,"stem":136,"options":137,"answer":24,"analysis":33},1022764,"某工程600MW发电机保护TA变比为25000\u002F5A, 5P20,发电机定子线电压为22kV,额定电流15746A,发电机次暂态电抗X\"d=18.26%，请根据上述已知条件回答下列有关定子绕组过负荷保护问题。 定时限过负荷保护的动作电流为（）。",[138,140,142,144],{"key":20,"text":139,"correct":22},"3.12A；",{"key":24,"text":141,"correct":29},"3.67A；",{"key":27,"text":143,"correct":22},"4.48A；",{"key":31,"text":145,"correct":22},"6.24A。",{"id":147,"libraryId":5,"type":15,"typeLabel":16,"stem":148,"options":149,"answer":24,"analysis":33},1022765,"某工程600MW发电机保护TA变比为25000\u002F5A, 5P20,发电机定子线电压为22kV,额定电流15746A,发电机次暂态电抗X\"d=18.26%，请根据上述已知条件回答下列有关定子绕组过负荷保护问题。 反时限过电流保护的上限电流为（）。",[150,152,154,156],{"key":20,"text":151,"correct":22},"5.48A；",{"key":24,"text":153,"correct":29},"21.56A；",{"key":27,"text":155,"correct":22},"8.22A；",{"key":31,"text":157,"correct":22},"10.96A。",{"id":159,"libraryId":5,"type":15,"typeLabel":16,"stem":160,"options":161,"answer":27,"analysis":33},1022766,"某工程600MW发电机保护TA变比为25000\u002F5A, 5P20,发电机定子线电压为22kV,额定电流15746A,发电机次暂态电抗X\"d=18.26%，请根据上述已知条件回答下列有关定子绕组过负荷保护问题。",[162,164,165,167],{"key":20,"text":163,"correct":22},"反时限过电流保护的下限电流为（）。",{"key":24,"text":139,"correct":22},{"key":27,"text":166,"correct":29},"3.74A； C3.85Af",{"key":31,"text":168,"correct":22},"6.24A,",{"id":170,"libraryId":5,"type":15,"typeLabel":16,"stem":171,"options":172,"answer":20,"analysis":33},1022767,"对于转子绕组过负荷保护，请回答下列问题。 下列说法正确的是（）。",[173,175,177,179],{"key":20,"text":174,"correct":29},"转子绕组过负荷保护由定时限和反时限两部分组成；",{"key":24,"text":176,"correct":22},"定时限部分的延时为2s；",{"key":27,"text":178,"correct":22},"定时限保护动作于解列；",{"key":31,"text":180,"correct":22},"反时限保护动作于停机。",{"id":182,"libraryId":5,"type":15,"typeLabel":16,"stem":183,"options":184,"answer":20,"analysis":33},1022768,"对于转子绕组过负荷保护，请回答下列问题。 下列关于转子绕组过负荷的定时限部分整定表述正确的是（）。",[185,187,189,191],{"key":20,"text":186,"correct":29},"动作电流按正常运行的颏定电流下能可靠返回的条件整定；",{"key":24,"text":188,"correct":22},"动作电流按正常运行的額定电流再乘以1.5的可靠系数整定；",{"key":27,"text":190,"correct":22},"动作电流按铎励工况电流下能可靠返面的条件整定；",{"key":31,"text":192,"correct":22},"动作电流按强励工况电流再乘以1.2的可靠系数整定。",{"id":194,"libraryId":5,"type":15,"typeLabel":16,"stem":195,"options":196,"answer":24,"analysis":33},1022769,"对于转子绕组过负荷保护，请回答下列问题。 下列关于转子绕组过负荷的反时限部分整定表述不正确的是（）。",[197,199,201,203],{"key":20,"text":198,"correct":22},"反时限的最小动作电流与定时限整定电流相同；",{"key":24,"text":200,"correct":29},"反时限的最小动作电流为定时限整定电流再乘以配合系数1.05；",{"key":27,"text":202,"correct":22},"反时限动作电流的上眼与励磁顶值倍数匹配；",{"key":31,"text":204,"correct":22},"如果崁励超过规定时间，保护动作于停机；铎励小于规定时间，则按反时眼特性动作，保护动作于解列灭磁。",{"id":206,"libraryId":5,"type":15,"typeLabel":16,"stem":207,"options":208,"answer":24,"analysis":33},1022770,"关于发电机转子表层负序过负荷保护，请回答下列问题。 发电机转子表层过负荷保护对下列故障形式没有保护作用的是（）。",[209,211,213,215],{"key":20,"text":210,"correct":22},"发电杌不对称过负荷；",{"key":24,"text":212,"correct":29},"发电机对称过负荷；",{"key":27,"text":214,"correct":22},"发电机进相运行；",{"key":31,"text":216,"correct":22},"发电机外部不对称故障。",{"id":218,"libraryId":5,"type":15,"typeLabel":16,"stem":219,"options":220,"answer":20,"analysis":33},1022771,"关于发电机转子表层负序过负荷保护，请回答下列问题。 发电机转子表层负序过负荷保护由定时限和反时限两部分组成，下列对于定时限部分表述正确的是（）。",[221,223,225,227],{"key":20,"text":222,"correct":29},"动作电流按发电机长期允许的负序电流下能可靠返回的条件整定；",{"key":24,"text":224,"correct":22},"动作电流按发电机长期允许的负序电流再乘以2.0的可靠系数整定；",{"key":27,"text":226,"correct":22},"保护延时动作于程序跳闸他",{"key":31,"text":228,"correct":22},"保护动作于解列灭磁。",{"id":230,"libraryId":5,"type":15,"typeLabel":16,"stem":231,"options":232,"answer":20,"analysis":33},1022772,"关于发电机转子表层负序过负荷保护，请回答下列问题。 对于反时限部分表述正确的是（）。",[233,235,237,239],{"key":20,"text":234,"correct":29},"反时限部分的上限电流按主变压器髙压侧两相短路电流整定；",{"key":24,"text":236,"correct":22},"反时限部分的上眼电流按主变压器高压侧三相短路电流整定；",{"key":27,"text":238,"correct":22},"反时张部分的动作时限需要与相邻元件保护配合；",{"key":31,"text":240,"correct":22},"保护动作于解列。",{"id":242,"libraryId":5,"type":15,"typeLabel":16,"stem":243,"options":244,"answer":27,"analysis":33},1022773,"某工程300MW汽轮发电机装设了逆功率保护，请回答下列有关保护整定计算的问题。 逆功率保护动作功率整定计算时，其可靠系数取值为0.5，汽轮机在逆功率运行时的最小损耗P1为额定功率的3%，发电机在逆功率运行时的最小损耗P2为额定功率的1.4%,动作功率整定值是额定功率的（）。[Pop=Krel(P1+P2)]",[245,247,249,251],{"key":20,"text":246,"correct":22},"0.7%；",{"key":24,"text":248,"correct":22},"1.5%；",{"key":27,"text":250,"correct":29},"2.2%；",{"key":31,"text":252,"correct":22},"4.4%。",{"id":254,"libraryId":5,"type":15,"typeLabel":16,"stem":255,"options":256,"answer":20,"analysis":33},1022774,"某工程300MW汽轮发电机装设了逆功率保护，请回答下列有关保护整定计算的问题。 关于逆功率保护的动作时限和动作对象，下列答案正确的是（）.",[257,259,261,263],{"key":20,"text":258,"correct":29},"逆功率保护出口经主汽门触点时，延时1.0~1.5s动作于解列；",{"key":24,"text":260,"correct":22},"逆功率保护出口经主汽门触点时，延时3.0~5.Os动作于伴机；",{"key":27,"text":262,"correct":22},"逆功率保护出口未经主汽门触点时，延时15s动作于解列j",{"key":31,"text":264,"correct":22},"逆功率保护出口未经主汽门触点时，延时1~3min动作于停机。",{"id":266,"libraryId":5,"type":15,"typeLabel":16,"stem":267,"options":268,"answer":20,"analysis":33},1022775,"某工程300MW汽轮发电机装设了逆功率保护，请回答下列有关保护整定计算的问题。 用于程序跳闸的逆功率继电器作为闭锁元件，其动作功率定值是（）。",[269,271,273,275],{"key":20,"text":270,"correct":29},"额定功率的1%~3%；",{"key":24,"text":272,"correct":22},"额定功率的2%~4%",{"key":27,"text":274,"correct":22},"额定功率的3%~5%；",{"key":31,"text":276,"correct":22},"额定功率的4%~6%。",{"id":278,"libraryId":5,"type":15,"typeLabel":16,"stem":279,"options":280,"answer":27,"analysis":33},1022776,"对于汽轮发电机定子过电压保护，请回答下列问题。 对于200MW及以上汽轮发电机，定子过电压保护的动作电压一般取值为额定电压的（）。",[281,283,285,287],{"key":20,"text":282,"correct":22},"1.1倍；",{"key":24,"text":284,"correct":22},"1.2倍；",{"key":27,"text":286,"correct":29},"1.3倍；",{"key":31,"text":288,"correct":22},"1.4倍。",{"id":290,"libraryId":5,"type":15,"typeLabel":16,"stem":291,"options":292,"answer":20,"analysis":33},1022777,"下列说法正确的是（）。",[293,295,297,299],{"key":20,"text":294,"correct":29},"任何电力元件不得在无继电保护的状态下运行；",{"key":24,"text":296,"correct":22},"任何电力元件在无继电保护的状态下可以短时运行；",{"key":27,"text":298,"correct":22},"任何电力元件在无继电保护的状态下，只要值班人员加强对该元件的监视就可以运行；",{"key":31,"text":300,"correct":22},"任何电力元件在无继电保护的状态下，只要该元件的发热不超过允许的温度就可以运行。",{"id":302,"libraryId":5,"type":15,"typeLabel":16,"stem":303,"options":304,"answer":24,"analysis":33},1022778,"继电保护设计时应满足的要求是（）。",[305,307,309,311],{"key":20,"text":306,"correct":22},"可靠性（信赖性和安全性）、选择性、灵敏性和经济性；",{"key":24,"text":308,"correct":29},"可靠性（信赖性和安全性）、选择性、灵敏性和速动性；",{"key":27,"text":310,"correct":22},"可靠性（信赖性和安全性）、选择性、合理性和经济性；",{"key":31,"text":312,"correct":22},"可靠性（信赖性和安全性）、合理性、选择性和快速性。",{"id":314,"libraryId":5,"type":15,"typeLabel":16,"stem":315,"options":316,"answer":27,"analysis":33},1022779,"电力设备和线路短路故障的保护应有（）。",[317,319,321,323],{"key":20,"text":318,"correct":22},"发电机保护、变压器保护和线路保护；",{"key":24,"text":320,"correct":22},"高頻保护、距离保护、电流保护；",{"key":27,"text":322,"correct":29},"主保护和后备保护，必要时可再增设辅助保护；",{"key":31,"text":324,"correct":22},"相间短路保护、接地短路保护。",{"id":326,"libraryId":5,"type":15,"typeLabel":16,"stem":327,"options":328,"answer":27,"analysis":33},1022780,"电力系统承受大扰动能力和稳定标准分为()。 A.一级； B.二级； C三级； D.四级。",[329,330,331,332],{"key":20,"text":20,"correct":22},{"key":24,"text":24,"correct":22},{"key":27,"text":27,"correct":29},{"key":31,"text":31,"correct":22},{"id":334,"libraryId":5,"type":15,"typeLabel":16,"stem":335,"options":336,"answer":31,"analysis":33},1022781,"后备保护是指（）。",[337,339,341,343],{"key":20,"text":338,"correct":22},"高频保护；",{"key":24,"text":340,"correct":22},"母线保护；",{"key":27,"text":342,"correct":22},"电流速断保护；",{"key":31,"text":344,"correct":29},"当主保护或断路器拒动时，用于切除故障的保护。",{"id":346,"libraryId":5,"type":15,"typeLabel":16,"stem":347,"options":348,"answer":24,"analysis":33},1022782,"220kV接地后备保护，当接地电阻不大于（）Ω时，保护应能可靠动作，有选择地切除故障。",[349,351,353,355],{"key":20,"text":350,"correct":22},"50；",{"key":24,"text":352,"correct":29},"1OO；",{"key":27,"text":354,"correct":22},"150；",{"key":31,"text":356,"correct":22},"200。",{"id":358,"libraryId":5,"type":15,"typeLabel":16,"stem":359,"options":360,"answer":24,"analysis":33},1022783,"髙压输电线路的电流保护工作原理是()。",[361,363,365,367],{"key":20,"text":362,"correct":22},"以測量保护安装处电压量为作用量的继电保护；",{"key":24,"text":364,"correct":29},"以通过保护安装处的电流为作用量的继电保护；",{"key":27,"text":366,"correct":22},"以測量通过主变压器高压侧的电流为作用量的继电保护；",{"key":31,"text":368,"correct":22},"以測量通过发电机电流为作用量的继电保护。",{"id":370,"libraryId":5,"type":15,"typeLabel":16,"stem":371,"options":372,"answer":31,"analysis":33},1022784,"高频闭锁方向保护主要用于（）保护。",[373,375,377,379],{"key":20,"text":374,"correct":22},"母线；",{"key":24,"text":376,"correct":22},"断路器；",{"key":27,"text":378,"correct":22},"发电机；",{"key":31,"text":380,"correct":29},"输电线。",{"id":382,"libraryId":5,"type":15,"typeLabel":16,"stem":383,"options":384,"answer":24,"analysis":33},1022785,"髙频闭锁方向保护的基本原理是()。",[385,387,389,391],{"key":20,"text":386,"correct":22},"基于比较被保护线路两侧电压大小；",{"key":24,"text":388,"correct":29},"基于比较被保护线路两侧的功率方向；",{"key":27,"text":390,"correct":22},"基于比较被保护线路两侧电流的大小；",{"key":31,"text":392,"correct":22},"基于比较被保护线路两侧电流的相位关系。",{"id":394,"libraryId":5,"type":15,"typeLabel":16,"stem":395,"options":396,"answer":31,"analysis":33},1022786,"500kV线路接地后备保护，若能可靠地有选择性地切除故障，应保证接地电阻不大于（）Ω。",[397,399,400,402],{"key":20,"text":398,"correct":22},"100；",{"key":24,"text":354,"correct":22},{"key":27,"text":401,"correct":22},"200；",{"key":31,"text":403,"correct":29},"300。",{"id":405,"libraryId":5,"type":15,"typeLabel":16,"stem":406,"options":407,"answer":31,"analysis":33},1022787,"安全稳定控制装置的可靠性可用平均无故障工作时间（MTB F)表示，单个控制装置的MTBF—般不低于（）。",[408,410,412,414],{"key":20,"text":409,"correct":22},"14000h；",{"key":24,"text":411,"correct":22},"15000h；",{"key":27,"text":413,"correct":22},"16000h；",{"key":31,"text":415,"correct":29},"17OOOh。",{"id":417,"libraryId":5,"type":15,"typeLabel":16,"stem":418,"options":419,"answer":24,"analysis":33},1022788,"220~500kV母线保护的配置原则是（）。",[420,422,424,426],{"key":20,"text":421,"correct":22},"本例母线故障在对侧线路后备保护作用范围内时，可不装设母线保护，否则就装设一套母线保护；",{"key":24,"text":423,"correct":29},"应装设能快速有选择地切除故障的母线保护，对1个半断路器接线，每组母线宜装设两套母线保护；",{"key":27,"text":425,"correct":22},"当本侧的变压器后备保护能实现对母线的保护时，可不装置母线保护，否则应装设一套母线保护；",{"key":31,"text":427,"correct":22},"对于1个半断路器接线每组母线应装设一套母线保护。",{"id":429,"libraryId":5,"type":15,"typeLabel":16,"stem":430,"options":431,"answer":31,"analysis":33},1022789,"关于电力设备和线路短路故障的主保护的说法，（）是正确的.",[432,434,436,438],{"key":20,"text":433,"correct":22},"高頻保护；",{"key":24,"text":435,"correct":22},"阶段式距保护；",{"key":27,"text":437,"correct":22},"光纤纵联差动保护；",{"key":31,"text":439,"correct":29},"能满足系统稳定和设备安全要求，能以最快速度有选择地切徐被保护设备和线路故障的保护.",{"id":441,"libraryId":5,"type":15,"typeLabel":16,"stem":442,"options":443,"answer":24,"analysis":33},1022790,"继电保护整定计算时，短路电流计算的以下假设条件，()是不正确的。",[444,446,448,450],{"key":20,"text":445,"correct":22},"发电机及调相机的正序电抗可采用t=0对的初瞬值X\"d的饱和值；",{"key":24,"text":447,"correct":29},"应计及故障点的电阻和接地电阻；",{"key":27,"text":449,"correct":22},"不计线路电容电流和负荷电流的影响；",{"key":31,"text":451,"correct":22},"不计短路暂态电流中的非周期分量。",{"id":453,"libraryId":5,"type":15,"typeLabel":16,"stem":454,"options":455,"answer":27,"analysis":33},1022791,"继电保护整定计算时，以下配合原则中（）是不正确的。",[456,458,460,462],{"key":20,"text":457,"correct":22},"上下级保护之间，除有特殊规定外，必须道循逐级配合原则，在灵敏度与动作时间上均相互配合，以保证电网保护在电网发生故障时或出现异常运行情况下有选择地动作；",{"key":24,"text":459,"correct":22},"各种保护按阶段原则选择整定值和控制短路功率的方向（如果这是必要的话）来保证动作的选择性，具有“绝对选择性”的纵联或横联差动保护除外；",{"key":27,"text":461,"correct":29},"相邻保护之间，其主保护段应与相邻后备保护段配合；",{"key":31,"text":463,"correct":22},"两侧电源的保护，当无方向性时，则应按正反两个方向与相邻保护配合，当可选择带方向性时，则整定方向按同方向配合。",{"id":465,"libraryId":5,"type":15,"typeLabel":16,"stem":466,"options":467,"answer":24,"analysis":33},1022792,"继电保护整定计算时，以下常用系数中不正确的是（）。",[468,470,472,474],{"key":20,"text":469,"correct":22},"电流保护可靠系数Kk 1；",{"key":24,"text":471,"correct":29},"距离保护可靠系数Kk 1；",{"key":27,"text":473,"correct":22},"过量动作的继电器返回系数Kf 1；",{"key":31,"text":475,"correct":22},"欠量运作的继电器返回系数Kf 1。",{"id":477,"libraryId":5,"type":15,"typeLabel":16,"stem":478,"options":479,"answer":27,"analysis":33},1022793,"220~500kV电网接地距离保护中应有对本线路末端故障有灵敏度的延时段保护，以下要求的灵敏系数中，（）是不正确的。",[480,482,484,486],{"key":20,"text":481,"correct":22},"50km以下线路不小于1.5；",{"key":24,"text":483,"correct":22},"50~200km线路不小于1.4；",{"key":27,"text":485,"correct":29},"200~300km以上线路不小于1.2；",{"key":31,"text":487,"correct":22},"220km以上线路不小于1.3。",{"id":489,"libraryId":5,"type":15,"typeLabel":16,"stem":490,"options":491,"answer":27,"analysis":33},1022794,"继电保护整定计算时，两个相邻保护装置动作时差△t，对采用电磁型时间继电器，一般采用（）S。",[492,494,496,498],{"key":20,"text":493,"correct":22},"0.3；",{"key":24,"text":495,"correct":22},"0.4；",{"key":27,"text":497,"correct":29},"0.5；",{"key":31,"text":499,"correct":22},"O.6。",{"id":501,"libraryId":5,"type":15,"typeLabel":16,"stem":502,"options":503,"answer":31,"analysis":33},1022795,"3~110kv电网相间距离n段阻抗定值对本线路末端相间金属性故障的灵敏系数，下列要求()是不正确的。",[504,506,508,510],{"key":20,"text":505,"correct":22},"对50km以上的线路不小于1.3；",{"key":24,"text":507,"correct":22},"对20~50km的线路不小于1.4；",{"key":27,"text":509,"correct":22},"对20km以下的线路不小于1.5；",{"key":31,"text":511,"correct":29},"对10km以下线路不小于1,6,",{"id":513,"libraryId":5,"type":15,"typeLabel":16,"stem":514,"options":515,"answer":24,"analysis":33},1022796,"3~110kV电网相间距离保护第III段整定原则中，下列要求中（）是不正确的。",[516,518,520,522],{"key":20,"text":517,"correct":22},"躲相邻线距离保护第II段或躲相邻线距离保护第III段；",{"key":24,"text":519,"correct":29},"与相邻线纵联保护配合；",{"key":27,"text":521,"correct":22},"与相邻变压器过流保护配合；",{"key":31,"text":523,"correct":22},"躲负荷阻抗，",{"id":525,"libraryId":5,"type":15,"typeLabel":16,"stem":526,"options":527,"answer":31,"analysis":33},1022797,"发电机低频保护应动作于（ ）。",[528,530,532,534],{"key":20,"text":529,"correct":22},"停机；",{"key":24,"text":531,"correct":22},"解列灭磁；",{"key":27,"text":533,"correct":22},"解列；",{"key":31,"text":535,"correct":29},"信号，并有累计时间显示。",{"id":537,"libraryId":5,"type":15,"typeLabel":16,"stem":538,"options":539,"answer":24,"analysis":33},1022798,"“四统一”设计的综合重合闸装置中“ B.”端子的功能为（）。",[540,542,544,546],{"key":20,"text":541,"correct":22},"接三相跳闸并允许进行一次三相重合闸的保护；",{"key":24,"text":543,"correct":29},"接三相跳闸后不进行重合闸的保护；",{"key":27,"text":545,"correct":22},"接非全相运行中不退出工作的保护；",{"key":31,"text":547,"correct":22},"接非全相运行中会谈动作的保护。",{"id":549,"libraryId":5,"type":15,"typeLabel":16,"stem":550,"options":551,"answer":20,"analysis":33},1022799,"220~500kV电网线路保护整定计算时，在环网中有并联回路的220kV线路，非全相运行最大零序电流一般可按不大于（）考虑。",[552,554,556,558],{"key":20,"text":553,"correct":29},"10OOA；",{"key":24,"text":555,"correct":22},"1100A；",{"key":27,"text":557,"correct":22},"1200A；",{"key":31,"text":559,"correct":22},"1300A。",{"id":561,"libraryId":5,"type":15,"typeLabel":16,"stem":562,"options":563,"answer":24,"analysis":33},1022800,"进行继电保护整定计算时，有3台及110kV变压器的双母线运行的发电厂，对变压器中性点接地方式的安排，正确的是（）。",[564,566,568,570],{"key":20,"text":565,"correct":22},"一般将1台变压器中性点接地运行；",{"key":24,"text":567,"correct":29},"一般将2台变压器中性点接地运行；",{"key":27,"text":569,"correct":22},"一般将3台变压器中性点接地运行；",{"key":31,"text":571,"correct":22},"一般将全部变压器中性点接地运行。",{"id":573,"libraryId":5,"type":15,"typeLabel":16,"stem":574,"options":575,"answer":27,"analysis":33},1022801,"当电力系统受到扰动后，对功率过剩与频率上升的一侧，下列措施中（）是错误的。",[576,578,580,582],{"key":20,"text":577,"correct":22},"对发电机快速减出力；",{"key":24,"text":579,"correct":22},"切除部分发电机；",{"key":27,"text":581,"correct":29},"切除部分负荷；",{"key":31,"text":583,"correct":22},"短时投入电气制动。",{"id":585,"libraryId":5,"type":15,"typeLabel":16,"stem":586,"options":587,"answer":27,"analysis":33},1022802,"事件顺序记录分辨率为（）。",[588,590,592,594],{"key":20,"text":589,"correct":22},"站内2~3ms，系统10~20ms(站间）",{"key":24,"text":591,"correct":22},"站内1~2ms，系统5~10ms(站间)；",{"key":27,"text":593,"correct":29},"站内1~2ms,系统10~20ms (站间）；",{"key":31,"text":595,"correct":22},"站内l~3ms，系统10~20ms(站间）。",{"id":597,"libraryId":5,"type":15,"typeLabel":16,"stem":598,"options":599,"answer":31,"analysis":33},1022803,"某工程单元控制室采用控制和动力直流系统分设的方式，动力采用关端电池220V直流系统，蓄电池浮充电压为2.25V,该工程直流负荷统计如下： (1) O~1min放电电流为767.6A； (2) 1~60min放电电流为431.5A； (3) 60~90min放电电流为417.2A； (4) 90~180min放电电流为174.2A； (5) 180~480min放电电流为116.1A。 请根据上述参数回答下列问题。 蓄电池组90、120、179、180min的容量换算系数分别0.326、0.298、0.232、0.231，请问第四阶段蓄电池组的计算容量为（）。",[600,602,604,606],{"key":20,"text":601,"correct":22},"4653Ah；",{"key":24,"text":603,"correct":22},"3139Ah；",{"key":27,"text":605,"correct":22},"2028Ah；",{"key":31,"text":607,"correct":29},"1512Ah。",[609,612,615,618,621,624],{"id":15,"name":610,"category":7,"favorite":611},"领导干部任职前廉政法规知识测试题",92,{"id":613,"name":614,"category":7,"favorite":15},595,"建筑结构与设备",{"id":616,"name":617,"category":7,"favorite":15},715,"招标采购专业知识与法律法规",{"id":619,"name":620,"category":7,"favorite":15},848,"市政方向-通用基础",{"id":622,"name":623,"category":7,"favorite":8},534,"BIM工程师",{"id":625,"name":623,"category":7,"favorite":8},535]