[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1024707":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},1024707,751,2,"多选题","管型母线配电装置的设计应满足的要求有（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","管型母线应选用单管结构；",false,{"key":16,"text":17,"correct":14},"B","固定方式采用支持式或悬挂式，当地震动峰加速度为0.2g及以上时，应采用悬挂式；",{"key":19,"text":20,"correct":21},"C","对支持式管型母线在无冰无风时的挠度不宜大于（0.5~1.0)D(D为导体直径），对悬技式母线的挽度，在上述基础上可适当放宽；",true,{"key":23,"text":24,"correct":21},"D","采用管型母线时，还应分别采取接施，消除端部效应及微风振动。","CD","",{"id":6,"name":28,"category":29,"favorite":30},"电气工程师发输变电专业","建筑工程",0]