[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1024607":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},1024607,751,2,"多选题","送电线路对地下电信电缆线路的危险影响计算应符合（）规定。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","考虑地电流影响，并按中性点直接接地的送电线路发生单相接地短路故障时，流入或流出搶电线路种塔接地装置的短路电流计算；",true,{"key":16,"text":17,"correct":14},"B","当同时产生感性耦合和阻性耗合两种影响时，按两者平方和的平方根计算合成影响；",{"key":19,"text":20,"correct":21},"C","不考虑地电流影响；",false,{"key":23,"text":24,"correct":21},"D","地电流应为故障点的总零序电流。","AB","",{"id":6,"name":28,"category":29,"favorite":30},"电气工程师发输变电专业","建筑工程",0]