[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1024425":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},1024425,751,2,"多选题","水电厂低压厂用电短路电流计算，应考虑()。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","应计及电阻，导体的电阻应取額定溫升的电阻值；",true,{"key":16,"text":17,"correct":18},"B","采用一级电压供电时，厂用变压器低压側的系统阻抗可忽略不计；",false,{"key":20,"text":21,"correct":14},"C","厂用电額定电压为380V时，计算三相短路电流，回路电压取400V；计算单相短路电流时，回路电压取220V；",{"key":23,"text":24,"correct":14},"D","计算配电盘母线短路电流时，应在第一周期内计及20kW及以上的异步电动机的反馈电流.","ACD","",{"id":6,"name":28,"category":29,"favorite":30},"电气工程师发输变电专业","建筑工程",0]