[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1024389":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},1024389,751,2,"多选题","火力发电厂高压用电系统，关于短路电流非周期分量对断路器开断电流的影响，下述正确的是（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","当主保护动作时间与断路器固有分闸时间之和大于0.15s时，应计及非周期分量影响；",false,{"key":16,"text":17,"correct":18},"B","B当主保护动作时间与断路器固有分闸时间之和小于0.11s时，应计及非周期分量影响；",true,{"key":20,"text":21,"correct":18},"C","当主保护动作时间与断年器固有分闸对间之和为0.11~0.15s,且短路电流周期分量为断路器额定开断电流的90%以上，应计及非周期分量影响；",{"key":23,"text":24,"correct":18},"D","当主保护动作时间和断路器固有分闸之和大于0.15s时，可不计及非周期分量影响。","BCD","",{"id":6,"name":28,"category":29,"favorite":30},"电气工程师发输变电专业","建筑工程",0]