[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1024268":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},1024268,751,2,"多选题","关于水电厂厂用变压器容量选择，下列描述正确的是（）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","装设两台互为备用的厂用电电源变压器时，每台变压器的額定容量应满足所有I、II类负荷或短时满足厂用电最大负荷的需要；",true,{"key":16,"text":17,"correct":14},"B","装设三台厂用电电源变压器互为备用或其中一台为明备用时，计及负荷分配不均匀等情况，每台的额定容量宜为厂用电最大负荷的50%~60%；",{"key":19,"text":20,"correct":14},"C","装设三台以上厂用电电源变压器时，应按其接线的运行方式及所连接的负荷分析确定；",{"key":22,"text":23,"correct":24},"D","厂用电变压器可采用铎迫A冷时持续输出容量作为额定容量选择的依据。",false,"ABC","",{"id":6,"name":28,"category":29,"favorite":30},"电气工程师发输变电专业","建筑工程",0]