[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1024169":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},1024169,751,2,"多选题","对由外部相间短路引起的变压器过电流，按（）规定装设相应保护作为后备保护。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","单相式低电压启动过电流用于降压变压器；",false,{"key":16,"text":17,"correct":18},"B","复合电压启动的过电流保护，宜用于升压变压器、系统联络变压器、过电流保护不符合要求的降压变压器；",true,{"key":20,"text":21,"correct":18},"C","6.3MVA及以上升压变压器，可采用负序电流和单相式低电压启动过电流保护；",{"key":23,"text":24,"correct":18},"D","当以上选项不能满足灵敏度和选择性要求时，可采用阻抗保护。","BCD","",{"id":6,"name":28,"category":29,"favorite":30},"电气工程师发输变电专业","建筑工程",0]