[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1024083":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},1024083,751,2,"多选题","火电厂电压互感器二次侧熔断器的选择应遵循的原则有（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","熔断器额定电流应按回路的最大负荷电流选释，并满足选择性的要求；",true,{"key":16,"text":17,"correct":18},"B","熔断器应按其最大负荷电流选择，但不应考虑双母线两组电压互感器切换时的工况；",false,{"key":20,"text":21,"correct":14},"C","熔断器的猿件必须保证在二次电压田路内发生短路时，懷件熔断的时间小于闭锁保护装置的动作时间；",{"key":23,"text":24,"correct":14},"D","聚件的額定电流应大于最大负荷电流（在双母线接线中，应考虑一组母线运行时，所有电压面路的负荷全部切换至另一组电压互感器上），可靠系数取1.5。","ACD","",{"id":6,"name":28,"category":29,"favorite":30},"电气工程师发输变电专业","建筑工程",0]