[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1024046":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},1024046,751,2,"多选题","送电线路塔头设计要便利带电作业，应考虑的规定有（）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","带电部分对杆塔接地部分的间隙应满足规定要求（如110kV时大于1.0m，220kV时大于1.8m,330kV时大于2.2m,500kV时大于3.2m）;",true,{"key":16,"text":17,"correct":14},"B","操作人员需要停留工作的部位，还应考虑人体活动范围30~50cm;",{"key":19,"text":20,"correct":14},"C","校验带电作业的间隙时，采用气温+15℃，风速10m\u002Fs的气象条件；",{"key":22,"text":23,"correct":24},"D","应考虑工頻过电压和谐振过电压对带电作业的影响。",false,"ABC","",{"id":6,"name":28,"category":29,"favorite":30},"电气工程师发输变电专业","建筑工程",0]