[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1024041":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},1024041,751,2,"多选题","在进行500kV电气设备操作过电压绝缘配合时，应遵循的原则是（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","电气设备内绝缘相对地額定操作冲击耐压与避雷器操作冲击保炉水平间的配合系数不应小于1.15;",true,{"key":16,"text":17,"correct":18},"B","电气设备外绝缘相对地干态额定操作冲击耐压与相应设备的内絶缘相对地额定操作冲击耐压相同，淋雨耐压值可低3%；",false,{"key":20,"text":21,"correct":14},"C","变压器内絶缘相间额定操作冲击耐压取其等于内绝缘相对地颏定操作冲击耐压的1.5倍；",{"key":23,"text":24,"correct":14},"D","变压器外绝缘相间干态額定操作冲击耐压与其于内绝缘相间额定操作冲击耐压相同。","ACD","",{"id":6,"name":28,"category":29,"favorite":30},"电气工程师发输变电专业","建筑工程",0]