[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1024035":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},1024035,751,2,"多选题","关于金属氧化锌避雷器与主变压器的最大电气距离，叙述正确的是（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","110kV系统，进线长度1km、进线回路2回，则金属氧化辞避雷器与主变压器的最大电气距离为85m；",true,{"key":16,"text":17,"correct":18},"B","110kV系统，进线长度1.5km、进线回路3回，则金属氧化锌避雷器与主变压器的最大电气距离为155m；",false,{"key":20,"text":21,"correct":14},"C","110kV系统，进线长度2km、进线回路4回，则金属氣化锌避雷器与主变压器的最大电气距离为230m；",{"key":23,"text":24,"correct":14},"D","220kV系统，进线长度2km、进线回路3回，则金属氧化辞避雷器与主变压器的最大电气距离为235m。","ACD","",{"id":6,"name":28,"category":29,"favorite":30},"电气工程师发输变电专业","建筑工程",0]