[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1024009":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},1024009,751,2,"多选题","对于发电厂、变电所的35kV及以上的电缆进线段，设计中应该根据具体情况采取以下（）保护措施。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","在电缆与架空线的连接处应装设阀式避雷器，其接地端应与电缆金属外皮连接；",true,{"key":16,"text":17,"correct":18},"B","对三芯电覌，应经金属氧化物电缆护层保护器或保护间歇接地；",false,{"key":20,"text":21,"correct":14},"C","如电缆长度超过50m,且断路器在雷季可能经常断路运行，应在电缆末端装设排气式避雷器或阀式避雷器；",{"key":23,"text":24,"correct":14},"D","连接电缆段的1km架空线路应架设避雷线。","ACD","",{"id":6,"name":28,"category":29,"favorite":30},"电气工程师发输变电专业","建筑工程",0]