[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023997":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},1023997,751,2,"多选题","当采用有串联间隙金属氧化物避雷器和碳化桂阀式避雷器时，避雷器的额定电压在一般情况下应符合（）要求。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","35、66kV系统中性点避雷器的額定电压不低于0.5Um；",false,{"key":16,"text":17,"correct":18},"B","110kV及220kV有效接地系统不低于0.8Um；",true,{"key":20,"text":21,"correct":18},"C","35、66kV系统不低于1.OUm;",{"key":23,"text":24,"correct":18},"D","3~1OkV系统不低于1.1Um。（Um为系统最高电压）","BCD","",{"id":6,"name":28,"category":29,"favorite":30},"电气工程师发输变电专业","建筑工程",0]