[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023984":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},1023984,751,2,"多选题","交流系统中电力电缆缆芯与绝缘屏蔽或金属套之间额定电压的选择，应符合的规定有（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","中性点直接接地或经低阻抗接地的系统当接地保护动作不超过1mim切除故障时，应按100%的使用回路工作相电压；",true,{"key":16,"text":17,"correct":14},"B","对于A項外的供电系统，不宜低于133%的使用回路工作相电压；",{"key":19,"text":20,"correct":21},"C","在单项接地故陣可能持续5h以上，或发电机回路等安全性要求较高的情况，宜采用173%的使用回路工作相电压；",false,{"key":23,"text":24,"correct":21},"D","交流系统中电缆的冲击耐压水平，宜满足系统绝缘配合要求。","AB","",{"id":6,"name":28,"category":29,"favorite":30},"电气工程师发输变电专业","建筑工程",0]