[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023802":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},1023802,751,1,"单选题","某沿海电厂二期扩建4台600MW燃煤机组，电厂附近已建有400t的大件码头。电 厂一期以220kV升高电压接入系统，二期4X600MW机组均接入厂内500kV配电装置， 500kV出线规模为2回，厂内两级电压间交换容量为360MVA。 自耦变压器的第三绕组容量宜为（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","90MVA；",true,{"key":16,"text":17,"correct":18},"B","60MVA；",false,{"key":20,"text":21,"correct":18},"C","210MVA；",{"key":23,"text":24,"correct":18},"D","50MVA。","在《手册》第五章四、1中，对自耦变压器的第三绕组容量的要求不应小于电磁容 量的35%，但最大值一般不超过其电磁容量。按此计算，即自耦变压器的第三绕组容量≥35%电磁容量=0.35 X 202 = 70. 7MVA，亦应小于202MVA。故符合此条件的应 是 90MVA。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]