[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023798":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},1023798,751,1,"单选题","某沿海电厂二期扩建4台600MW燃煤机组，电厂附近已建有400t的大件码头。电 厂一期以220kV升高电压接入系统，二期4X600MW机组均接入厂内500kV配电装置， 500kV出线规模为2回，厂内两级电压间交换容量为360MVA。 二期主变压器的型式为（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","双绕组三相变压器；",true,{"key":16,"text":17,"correct":18},"B","三绕组三相变压器;",false,{"key":20,"text":21,"correct":18},"C","双绕组单相变压器；",{"key":23,"text":24,"correct":18},"D","三绕组单相变压器。","根据《火力发电厂设计技术规程》（DL\u002FT 5000—2000)、《电力工程电气设计手册》（1) 的相关规定： DL\u002FT 5000-2000 13.1.7规定：200MW以上的机组不宜采用三绕组变压器，现该电厂附近又有大件码头，故二期主变压器的型式应为双绕组三相变压器",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]