[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023780":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},1023780,751,1,"单选题","某城市中有220kV变电站，降压为110kV及10kV, 220kV出线为4回，110kV出 线5回，10kV出线10回。220kV拟采用SF6组合电器（GIS)，110kV为户内一般设备配 SF6断路器，10kV为开关柜。 三种电压宜采用的接线组合为（）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","220kV双母线，110kV双母线，10kV单母线；",false,{"key":16,"text":17,"correct":14},"B","220kV双母线带旁路’ 110kV双母线帝旁路，10kV单母线；",{"key":19,"text":20,"correct":14},"C","220kV单母线，110kV双母线，10kV单母线；",{"key":22,"text":23,"correct":24},"D","220kV双母线，110kV单母线分段，10kV单母线分段。",true,"根据《220kV?500kV变电所设计技术规程》(DL\u002FT 5218-2005) 7.1. 4条的相关规定： 按DL\u002FT5218—2005 7.1.4条，本变电所属于重要变电所，220kV出线4回应采 用双母线；110kV出线5回宜采用单母线或单母线分段；10kV出线10回，采用单母线或 单母线分段均可。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]