[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023778":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1023778,751,1,"单选题","某电厂有3台50MW机组，发电机电压为10. 5kV，负荷要求地方10kV送电。当地 区负荷较少时，应将富余功率外送，系统电网为35kV及110kV，地区送电线要求10kV 12 回，高压各2回。 经短路电流计算，3台发电机电压母线短路电流较大，为限制短路电流，在（） 设置电抗器为宜。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","发电机出口；",false,{"key":16,"text":17,"correct":14},"B","变压器低压例；",{"key":19,"text":20,"correct":21},"C","分段断路器侧或10kV出线侧；",true,{"key":23,"text":24,"correct":14},"D","变压器高压侧。","按DL\u002FT 5000—2000 13.2. 3条，为限制短路电流，宜在分段断路器侧或10kV出 线侧设置电抗器",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]