[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023762":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},1023762,751,1,"单选题","某35~110kV变电所若35kV出线8回，110kV出线为4回。 此时宜采用的接线方式为（）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","35kV双母线，110kV双母线；",false,{"key":16,"text":17,"correct":14},"B","35kV单母线分段，110kV单母线分段；",{"key":19,"text":20,"correct":14},"C","35kV双母线，110kV单母线；",{"key":22,"text":23,"correct":24},"D","35kV双母线，110kV单母线分段。",true,"按照《35kV?110kV变电所设计规范KGB 50059—1992)、《电力工程电气设计手册》 （1）的规定： GB 50059—1992 3. 2. 3条㈣35kV在8回及以上可采用双母线接线，110kV超过 2回出线时，宜采用单母线或单母线分段接线，现110kV出线已经4回，故应采用单母线分 段接线；",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]