[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023753":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1023753,751,1,"单选题","在双母线接线中，为在进出线断路器检修时保证连续供电，采取设置旁路母线措施。 采用设置母联兼旁路断路器方案时，下列说法不正确的是()",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","对双母线的固定连接的运行方式有影响；",false,{"key":16,"text":17,"correct":14},"B","可节约一台断路器；",{"key":19,"text":20,"correct":21},"C","C不増加隔离开关的倒闸操作；",true,{"key":23,"text":24,"correct":14},"D","节约一个断路器间隔。","根据《电力工程电气设计手册》（1)第2-2节第五条的相关规定。 第2-2节第五、（一）2.条，对母联兼旁路断路器方案时，就明确提出该接线的缺 点是要“增加隔离开关的倒闸操作”",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]