[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023701":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1023701,751,1,"单选题","关于高烈度地震地区配电装置的设计，下列论述中错误的是（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","电压为330kV及以上的电气设施设防烈度7度及以上时，应进行抗震设计；",false,{"key":16,"text":17,"correct":18},"B","当设防烈度为9度时，电压为11OkV及以上管型母线配电装置的管型母线宜采用支持式结构；",true,{"key":20,"text":21,"correct":14},"C","当设防烈度为8度或9度时，限流电抗器不宜采用三相垂直布置；",{"key":23,"text":24,"correct":14},"D","当设防烈度为7度及以上时，电气设备的引线和设备间连线宜釆用软导线，其长度应留有余量。","",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]