[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023667":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1023667,751,1,"单选题","某交流500kV线路，海拔小于1000m，4XLGJ—400\u002F50导线，I级污区，采用标准型绝缘子XP—160，L=360mm,h=155mm,ke=1.0。 正常情况下适用的耐张串绝缘子强度为（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","双联160kN；",false,{"key":16,"text":17,"correct":14},"B","双联210kN；",{"key":19,"text":20,"correct":21},"C","双联300kN；",true,{"key":23,"text":24,"correct":14},"D","双联400kN。","根据 DL\u002FT5092—19997.0.3、8.0.1条的相关规定。 LGJ-400\u002F50导线计算拉断为123400N 导线安全系数不小于2.5，取2.5，则：123400X0.95X4\u002F2.5=187568（N） 绝缘子最大使用荷载时，安全系数不小于2.7 187568X2.7=506434N≈507kN 耐张串应至少由两串组成双联：507\u002F2=253.5kN 按目前国内绝缘子强度序列，应选用300kN的绝缘子组成双联串。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]