[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023665":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1023665,751,1,"单选题","某2X300MW火力发电厂厂用电系统采用6kV和380V两级电压，其中每台机组设 A、B两段6kV工作段，全厂设01 A、OlB两段6kV公用段，考虑公用段工作电源取自1、2号机组6kV工作段，备用电源取自启动\u002F备用变压器。见示意图9。每台机组设一台电动给水泵，都接于机组6kV工作A段，髙压厂用分裂变压器容量为：40\u002F25—25MVA（无载调压）。 若接地电咀接于高压厂用变压器中心点的接地变压器的二次侧，二次侧电压取220V，电阻值按单相接地电容8.35A选取，接地电阻的电阻值为（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","1.55Ω；",false,{"key":16,"text":17,"correct":18},"B","1.67Ω；",true,{"key":20,"text":21,"correct":14},"C","2.15Ω；",{"key":23,"text":24,"correct":14},"D","2.71Ω。","解答过程：电阻值按单相接地电容选取，按公式：R N2=（RNX103）n2 式中RN为系统中心点等效电阻，RN2为接入接地变压器二次侧的电阻值，n为接地变压器的变比。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]