[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023657":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1023657,751,1,"单选题","某电厂新建两台135MW燃煤发电机组，电厂以220kV电压接入系统，出线2回,预留1回。两台机组均采用发电机一变压器组单元接线接入厂内220kV母线。发电机引出线及厂用分支线采用分相封闭母线。 已知220kV母线单相短路电流16.25k A，发生单相接地短路时，流往发电厂接地中性点的接地短路电流为12.05kA,入地短路电流10.85k A，接地材料的热稳定系数C=70,短路等效持续时间te=0.65s，现按热稳定条件分别计算出接地线的最小截面值（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","187.16mm2；",false,{"key":16,"text":17,"correct":14},"B","138.79mm2；",{"key":19,"text":20,"correct":21},"C","124.96mm2；",true,{"key":23,"text":24,"correct":14},"D","219.20mm2。","解答过程： 根据《交流电气装置的接地》（DL\u002FT621—1997）附录C。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]