[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023655":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},1023655,751,1,"单选题","某电厂新建两台135MW燃煤发电机组，电厂以220kV电压接入系统，出线2回,预留1回。两台机组均采用发电机一变压器组单元接线接入厂内220kV母线。发电机引出线及厂用分支线采用分相封闭母线。 已知启动\u002F备用变供电时IA段6kV母线三相短路电流周期分量起始有效值中，变压器提供的部分为18.5k A，电动机反馈的部分为9.57kA。假定6kV电缆选用铝芯，热稳定系数C值取82,短路切除时间15S,试计算6kV馈线回路电缆最小热稳定截面为（）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","87mm2；",false,{"key":16,"text":17,"correct":14},"B","103mm2；",{"key":19,"text":20,"correct":14},"C","130mm2；",{"key":22,"text":23,"correct":24},"D","134mm2。",true,"解答过程： 根据《电力工程电气设计手册》（1）936~937页公式（17-3）及表17-12和《电力工程电缆设计规范》（GB50217—1994）附录D或DL\u002FT5153—2002附录M表M3的有关公式",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]