[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023653":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},1023653,751,1,"单选题","某电厂新建两台135MW燃煤发电机组，电厂以220kV电压接入系统，出线2回,预留1回。两台机组均采用发电机一变压器组单元接线接入厂内220kV母线。发电机引出线及厂用分支线采用分相封闭母线。 已知发电机额定功率Pe =135MW，cosφ=0.85。根据高压电动机容量表（其中II A、IIB段上无8~11项），假定给水泵电动机换算系数取1,其余电动机换算系数取0.8，试计算全厂高压电动机部分厂用电率为（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","6.44%；",true,{"key":16,"text":17,"correct":18},"B","6.50%；",false,{"key":20,"text":21,"correct":18},"C","6.84%；",{"key":23,"text":24,"correct":18},"D","7.12%。","解答过程： 根据《火力发电厂厂用电设计技术规定》（DL\u002FT5153—2002）附录A及附录G的有关公式。 ①1号机计算负荷 Sc1=3200X1+0.8X11010=12008（kVA） [280+2X（710+1250+630+900+4504-250+800）+3X250=11010（kW）] ②2号机计算负荷 Sc2=3200X1+0.8X8160=9728（kVA） [11010-2X（250+800）—3X250=8160（kW）] ③总的计算负荷 Sc=Sc1+Sc2=21736（kVA） ④厂用电率",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]